E100 Site Elec Drawing 08-05-2023IPF
3
5
5
2
1
4
NOTES KEYED TO 1/E100:
1 (ALTERNATE #3) PROVIDE 3-3"C AND 1-1"C AND (ALTERNATE #4)
3-3"C AND 1-1"C. TURN UP 6"C ABOVE GRADE AND CAP.
COORDINATE DISTANCE FROM EXISTING STRUCTURE WITH
OWNER PRIOR TO BEGINNING WORK.
(ALTERNATE #4) PROVIDE 3-3"C AND 1-1"C . CAP CONDUITS
BELOW GRADE AND MARK WITH END OF DUCTBANK MARKER.
(ALTERNATE #3) PROVIDE 3-3"C AND 1-1"C . CAP CONDUITS
BELOW GRADE AND MARK WITH END OF DUCTBANK MARKER.
(ALTERNATE #3) PROVIDE UL LISTED, CODE SIZED, OPEN
BOTTOM HANDHOLE. MARKING ON COVER SHALL READ
"ELECTRICAL". PROVIDE ON A 12" BED OF CRUSHED STONE.
(ALTERNATE #3) PROVIDE 2-2"C AND 1-1"C . CAP CONDUITS
BELOW GRADE AND MARK WITH END OF DUCTBANK MARKER.
2
GENERAL NOTES:
1.ALL CONDUITS SHALL BE INSTALLED TO CODE MINIMUMS.
2.ALL CONDUIT SHALL BE SCHEDULE 40 PVC.
3.PROVIDE TRACE WIRE IN EACH CONDUIT; PROVIDE MARKING
TAPE AT 12" BELOW GRADE.
4.SPARE CONDUITS SHALL BE CAPPED WHETHER BELOW
GRADE OR ON TURN-UPS.
3
4
5
E100
1 ELEC. SITE PLAN
5909 Falls of Neuse Rd.
Suite 101
Raleigh NC 27609
Ph: 919.840.9300
www.sigmaes.com
Sigma Project #: 23041
Sigma Engineered Solutions, PC