E100 Site Elec Drawing 08-05-2023IPF 3 5 5 2 1 4 NOTES KEYED TO 1/E100: 1 (ALTERNATE #3) PROVIDE 3-3"C AND 1-1"C AND (ALTERNATE #4) 3-3"C AND 1-1"C. TURN UP 6"C ABOVE GRADE AND CAP. COORDINATE DISTANCE FROM EXISTING STRUCTURE WITH OWNER PRIOR TO BEGINNING WORK. (ALTERNATE #4) PROVIDE 3-3"C AND 1-1"C . CAP CONDUITS BELOW GRADE AND MARK WITH END OF DUCTBANK MARKER. (ALTERNATE #3) PROVIDE 3-3"C AND 1-1"C . CAP CONDUITS BELOW GRADE AND MARK WITH END OF DUCTBANK MARKER. (ALTERNATE #3) PROVIDE UL LISTED, CODE SIZED, OPEN BOTTOM HANDHOLE. MARKING ON COVER SHALL READ "ELECTRICAL". PROVIDE ON A 12" BED OF CRUSHED STONE. (ALTERNATE #3) PROVIDE 2-2"C AND 1-1"C . CAP CONDUITS BELOW GRADE AND MARK WITH END OF DUCTBANK MARKER. 2 GENERAL NOTES: 1.ALL CONDUITS SHALL BE INSTALLED TO CODE MINIMUMS. 2.ALL CONDUIT SHALL BE SCHEDULE 40 PVC. 3.PROVIDE TRACE WIRE IN EACH CONDUIT; PROVIDE MARKING TAPE AT 12" BELOW GRADE. 4.SPARE CONDUITS SHALL BE CAPPED WHETHER BELOW GRADE OR ON TURN-UPS. 3 4 5 E100 1 ELEC. SITE PLAN 5909 Falls of Neuse Rd. Suite 101 Raleigh NC 27609 Ph: 919.840.9300 www.sigmaes.com Sigma Project #: 23041 Sigma Engineered Solutions, PC NC ENG LIC# C-2490