HomeMy WebLinkAbout5505 Carolina Beach Road TRC Comments Full5505 Carolina Beach Road – Commercial Site Plan – TRC Review
To: BVC Myrtle Grove, LLC
Brad Schuler, Paramounte Engineering (bschuler@paramounte-eng.com)
From: Zach Dickerson
Current Planner
Date: September 6, 2023
Egov#: SITECN-23-000036
Subject: Myrtle Grove Restaurant – Major Site Plan – TRC Review
Address: 5505 Carolina Beach Road
The following comments have been received for the September 6, 2023, TRC meeting. Additional
comments may be made upon further review of subsequent revisions.
Please note: following the TRC meeting, a revised preliminary plan addressing each of the below items
must be resubmitted prior to receiving preliminary plan approval.
Planning, Zach Dickerson 910-798-7450
1. Zoning district: B-2
2. Parking
a. Parking is sufficient.
3. Access:
a. It does not appear that this site will require a new Driveway Permit as it is using existing
access on Piner Road and Carolina Beach Road. If NCDOT confirms no Driveway Permit
edits are necessary, please disregard the following comment.
b. Please provide all NCDOT approvals upon receipt. Please be aware that no building permit
will be issued until NCDOT has issued the Driveway Permit.
4. Tree Retention:
a. Please apply for a Tree Removal Permit.
b. Please refer to UDO Section 5.3 for Tree Retention Standards.
c. The two 24” pines, the 18” oak and the 24” oak will require mitigation.
5. Landscaping and Buffering:
a. Please provide a landscape plan detailing the plantings, including size and species, for the
foundation plantings, parking lot interior landscaping, and street yard.
5505 Carolina Beach Road – Commercial Site Plan – TRC Review
b. Please confirm total square footage of foundation plantings for landscaping, parking lot
islands/landscaping and street yard.
c. Please note that foundation plantings are not required for the portions of the building
adjacent to drive-thrus. They are required for the portions of the building facing parking
or internal drive aisles, but exceptions may be made where there is a drive thru. Please
see below screengrab for where foundation plantings would be required on this site plan.
d. Are the two clouded areas indicated in the screengrab below intended for interior parking
lot landscaping? UDO Section 5.4.5 provides guidelines for interior parking lot
landscaping.
6. Exterior Lighting:
a. Please provide a lighting plan- approval of the lighting plan is required before site plan
approval (Section 10.3.6, Site Plan) or zoning compliance approval (Section 10.3.8, Zoning
Compliance Approval), whichever comes first. A lighting plan must be provided to
illustrate that street lighting, all exterior lighting, and indoor lighting visible from outside
shall be designed and located so that the maximum illumination measured in foot candles
at ground level at a lot line, UDO Section 5.5. Please refer to Table 5.5.4.B of the UDO.
b. Before the building permit can be issued, documentation must be provided to illustrate
that illumination plan.
5505 Carolina Beach Road – Commercial Site Plan – TRC Review
NHC Fire, Sunnie Batson 910-798-7464
1. See NHC Fire appendix below
NHC Engineering (Stormwater), Galen Jamison 910-798-7072
1. A land disturbing permit issued by the County is required for this project. Please submit for
permit as the design is completed.
2. A revision to the stormwater permit (ATC# 329-01/18/07) issued by the County is required for
this project. Please submit for permit application documents to gjamison@nhcgov.com as the
design is completed.
3. Please contact the State for the stormwater permit modification requirements to SW8060740.
NHC Environmental Health, Dustin Fenske 910-798-7324
1. Site appears it can connect to public water and sewer. No well or septic system records on
adjoining properties or on this site. The restaurant must complete an Environmental Health
restaurant plan review with either local Environmental Health or State review. The review will
depend on if the restaurant is a franchise.
NHC Addressing, Katherine May
1. No comments.
CFPUA, Bernice Johnson 910-332-6620
1. CFPUA TRC Comments provided are preliminary comments only.
2. Engineer to confirm with CFPUA the scope of the project to determine/verify if CFPUA Plan
Review will be required.
3. Utility Plan Review required by CFPUA. CFPUA is moving toward becoming paperless. When
ready to submit plan review package, upload all documents to
https://www.cfpua.org/FormCenter/Engineering-3/Engineering-Plan-Review-103.
4. CFPUA water and sewer available.
5. CFPUA Meter Sizing Form may be required.
WMPO, Jamar Johnson 910-343-3915
1. See WMPO appendix below
NCDOT, Nick Drees, 910-398-9100
1. See NCDOT appendix below.
Army Corps of Engineers, Brad Shaver 910-251-4611
1. No comments.
New Hanover County Fire Rescue
230 Government Center Drive, Suite 130
Wilmington, NC 28403
Phone: (910) 798-7420 Fax: (910) 798-7052
Protecting the citizens and visitors of New Hanover County
TRC Plan Review - 2018 NC Fire Code
Pursuant to the North Carolina Fire Prevention Code and New Hanover County Ordinances Section 26
Required for Plan Review Submittal
• The complete TRC/Site plans comments from New Hanover County Fire staff shall be submitted
along with the building plans for review to New Hanover County Building Safety. This shall
include the complete set of civil plans. Failure to submit the comments or complete set of civil
plans will result in a resubmittal for review for verification of compliance.
• Any building with a generator or aboveground storage tank (AST) shall include an engineered
plan complying with the NCFC Chapter 23, 57 and NFPA 30 showing all applicable distances as
required from those specific requirements.
• Any plan involving an underground storage tank (UST) shall include an engineered plan
complying with the NCFC Chapter 23, 57 and NFPA 30 for Underground Storage Tank Cover
requirements. This plan shall also show all vent lines.
• Per NCFC 503.6, submit for review the details and manufacturer information for the gate across
the fire department access road. Include both the UL and ASTM Listing in the documentation
attachments for approval. This review shall include the written approval of the Fire Chief or any
New Hanover Deputy Fire Marshal and any additional details of approval during this review
process. (EMBEDDED ON PLANS) (WRITTEN TRC APPROVAL)
• Per NCFC 507.1, Provide an Engineered fire flow analysis report in accordance with the fire
code and Appendix B to include pertinent information. A fire flow test shall be conducted in
accordance with NFPA 291 and NCFC 507.4. This report shall be submitted by a P.E. and
include the stamp of the submitting individual on the report.
New Hanover County Fire Rescue
230 Government Center Drive, Suite 130
Wilmington, NC 28403
Phone: (910) 798-7420 Fax: (910) 798-7052
Protecting the citizens and visitors of New Hanover County
Accessibility
• All new structures larger than 7,500 square feet must comply with Section 510 of the NC Fire
code. An Emergency Responder Radio Coverage (ERRC) survey must be conducted, and results
given to the Building Safety Fire Plan Reviewer. All buildings that are more than one story,
underground, windowless or buildings with a basement must complete an ERRC survey. (It is
highly recommended that a pre-construction survey be conducted, however a pre-construction
survey is not required).
• All new structures must comply with Appendix J of the NC Fire Code, Building Information
Signs. An example can be provided upon request.
• Fire apparatus access roads are required at time of construction. They are to be capable of
handling the weight of fire apparatus and be passable in all weather conditions. Fire apparatus
access roads are to be a minimum of 20 feet wide (Chapter 5), unless there are fire hydrants
installed along the roadway then minimum is 26 feet wide (Appendix D). The fire code official
may increase this width as necessary based on potential for fire apparatus response. Dead end
roads greater than 150 feet in length shall require an approved means for fire apparatus to turn
around (Chapter 5 and Appendix D). Fire apparatus access roads shall provide a clear vertical
clearance of 14 feet including trees, canopies, bridges, etc. (Chapter 5 requirement is 13 feet 6
inches, however AHJ requires 14 feet based on local apparatus).
o The secondary, one-way access road shall be 16’ in width.
• Street and road signs are required, temporary signs during construction are acceptable as long as
they are legible and weather resistant. (Chapter 5).
New Hanover County Fire Rescue
230 Government Center Drive, Suite 130
Wilmington, NC 28403
Phone: (910) 798-7420 Fax: (910) 798-7052
Protecting the citizens and visitors of New Hanover County
• Parking shall not be allowed on either side of the above-mentioned roadway. If roadside parking
is desired the minimum road width shall be increased, contact the fire code official for further
information. No Parking signs shall be a minimum of 12 inches wide and 18 inches tall.
Commercial buildings shall have fire lanes marked (Chapter 5)
• Fire apparatus access roads shall provide access to within 150 feet of each side of the first-floor
exterior walls unless the building is equipped throughout with an approved automatic sprinkler
system then the distance increases to 200 feet (Chapter 5). If these options are not selected,
please contact the fire code official and fire department for guidance.
• Traffic calming devices are highly discouraged due to the delay in response. Speed
bumps/humps are prohibited. Requests for other traffic calming devices must be evaluated
during the Technical Review (TRC).
• Key Boxes (KNOX Boxes)
o Required if structure is required to have a fire alarm system or automatic sprinkler
system.
o Knox Box required at/adjacent to the front (main) entrance, at an elevation of 5 ft, +/- 6
in. A KNOX box(es) is(are) required at the exterior access nearest the fire sprinkler
riser(s). Larger facilities may require additional key boxes. All key box locations must be
shown on the building plans. All key boxes are required to be installed prior to final
inspection.
o The customer may order online from Knox.
• Premises identification is required. Address and or unit numbers are required on the street side as
well as unit identification on rear access doors. Letters and Numbers shall not be less than 6
inches tall and ¾ inches wide; must be weather resistant and contrasting in color to their
background. (Chapter 5). Buildings constructed under the 2018 code shall require additional
signage per Appendix J.
• Rooms containing controls for HVAC, fire sprinkler risers, fire alarm control panels, or other fire
detection/protection equipment must be identified with signage (Chapter 5).
• Generator and solar installations shall be in accordance with Chapter 6.
Water Supply (Chapter 5 and Appendix C)
• If a water supply is required for fire protection a fire hydrant system or other means approved by
the fire code official must be present prior to beginning construction and be maintained operable
during the construction period. (For construction, fire dept. water shuttle counts as long there is a
fill site within range)
New Hanover County Fire Rescue
230 Government Center Drive, Suite 130
Wilmington, NC 28403
Phone: (910) 798-7420 Fax: (910) 798-7052
Protecting the citizens and visitors of New Hanover County
• An engineered fire low calculation indicating the available fire flow shall be submitted to
Building Safety during plans review.
• If an approved water supply capable of supplying the required fire flow for fire protection is
available, fire hydrants shall be provided.
• If the approved water supply is not capable of supplying the required fire flow for fire protection
a private system shall be engineered to meet the required fire flow for both automatic sprinkler
systems and fire hydrants.
• Fire Hydrants
o An additional fire hydrant is required at the main entrance as shown above.
o All fire hydrants shall have a 5 ¼ inch barrel, a 5 ¼ inch valve opening, two 2 ½ inch
NST side discharges and a 5-inch pumper nozzle with a 5-inch STORZ connection.
Further information on the technical specifications is available from the fire code official
or Cape Fear Public Utility Authority.
o All fire hydrants shall be installed so they are visible from the fire apparatus access road
with unobstructed access and a clear space no less than 36 inches in all directions. They
shall be protected from vehicle impact by curbing, guard posts or other means approved
by the fire code official. They shall be oriented with the large discharge facing the nearest
street. All discharges shall meet the NFPA requirements for distance above grade.
o Fire hydrants in general residential areas shall be installed so that all insured properties
are within 500 feet of a hydrant (hydrant spacing approximately 1000 feet apart along a
fire apparatus access road, installed at intersections where possible). The first fire hydrant
should be installed at or near the entrance to the residential area.
o Fire hydrants in mixed use and commercial areas shall be installed so that all insured
properties are within 250 feet of a hydrant (hydrant spacing approximately 500 feet apart
along fire apparatus access roads and preferably located at intersections when possible).
o Fire hydrants for industrial and manufacturing areas shall be installed so that all
structures are within 250 feet of a fire hydrant; distances may be adjusted more or less
based on approval of the fire code official and based on the hazards present.
o Additional fire hydrants may be required by the fire code official based on the type of
hazard or use of the protected structure. (Appendix C)
o Fire hydrants should be located 50 feet or more from the structure they protect.
• Fire Department Connections (FDC)
New Hanover County Fire Rescue
230 Government Center Drive, Suite 130
Wilmington, NC 28403
Phone: (910) 798-7420 Fax: (910) 798-7052
Protecting the citizens and visitors of New Hanover County
o Fire Department connections shall utilize 5-inch Storz connections with a 30 degree
down angle. Remote FDC’s are discouraged.
o A fire hydrant shall be located no less than 50 feet from the structure and no greater than
100 feet from the fire department connection. For buildings with multiple fire department
connections, each one shall have a dedicated fire hydrant.
o The fire department connection shall be located so that the fire apparatus and the hoses
connecting it to the fire hydrant and to the fire department connection do not obstruct
access to the buildings for other fire apparatus.
o Fire department connections shall not be obstructed by fences, bushes, dumpsters,
utilities, or vehicles.
o Fire department connections are to be unobstructed with 36 inches clearance to both sides
and 78 inches vertically.
o An audible/visual device indicating water flow or fire alarm activation shall be located
above the fire department connection.
o The fire department connection shall be labeled with code compliant signage indicating
the type of connection and where more than one fire department connection exists
additional signage is required to indicate the area protected.
Demolition
o All demolition work must comply with Chapter 33.
TRC Comments
5505 Carolina Beach Road, Outparcel A
These are preliminary comments and are based on the plans as submitted for the proposed site. They
are subject to further review upon receipt of any additional information. Subsequently, additional
comments and/or requirements may be necessary for this site.
x NCDOT Driveway Permits, and Encroachments are submitted through the NCDOT Online Portal.
https://connect.ncdot.gov/municipalities/Utilities/Pages/help.aspx
x A NCDOT Driveway Permit is required. Submit plans in accordance with pages 14 and 15 of the
Policy on Street and Driveway Access to North Carolina Highways to include access locations
within 500’ of the proposed access on both sides of the State Road. Submit to the local NCDOT
District Engineer’s Office.
o Refer to the NCDOT checklist for submittal requirements (Documents, details, and
plans).
x Refer to the site plan for additional comments on the proposed design.
x Label the radius for the driveway connection.
x A NCDOT Encroachment Agreement is required for any utility connections or installations within
NCDOT right-of-way.
x This development is located within TIP U-5790. With that in mind, any accesses that conflict
with the planned transportation infrastructure may be modified and/or removed and there shall
not be any compensation made by NCDOT. The current TIP U-5790 adds an additional right turn
lane on Piner Road at the main driveway access to the shopping center.
NCDOT District 3 TRC Comments
8/24/23.
NCDOT District 3 TRC Comments
8/24/23.
NCDOT District 3 TRC Comments
8/24/23.
Recommend options for theconnection to avoid any
impacts to Piner Road:
1. Right in only (preferred).
2. Right in/out.3. Right in/out and a left in.
Add:SR 152145mph
This access point in relationto the drive thru will haveissues with the circulation
pattern unless a barrier isinstalled.
- Show the menu board.- Show the vehicle Que from themenu board.
NCDOT | Division 3 | District 3 Project Name:_____________________________ Date:_______________
Applicant
Checklist NCDOT
Checklist
Driveway Application Process and Site Plan Requirements
ALL APPLICATIONS SHALL BE ACCOMPANIED BY COMPLETE AND DETAILED SITE PLANS THAT ADHERE TO THE POLICIES LISTED IN THE POLICY ON STREET AND
DRIVEWAY ACCESS TO NORTH CAROLINA HIGHWAYS AND THIS DOCUMENT. FAILURE TO ADHERE TO THESE POLICIES WILL RESULT IN THE RETURN OF THE
APPLICATION TO THE APPLICANT FOR REVISION.
***THE NCDOT WILL NOT BEGIN THE REVIEW PROCESS ON INCOMPLETE APPLICATIONS***
Electronic Pre-Submittals
In an effort to save time and resources, we are happy to provide an initial assessment of a driveway permit submittal’s plans via email to
identify any major issues up front. This initial assessment can be followed up with a submittal ŽĨŽŶĞĚŝŐŝƚĂůĐŽƉLJŽĨƚŚĞƉůĂŶƐ along with all
other required documents.
ůůWĞƌŵŝƚĂƉƉůŝĐĂƚŝŽŶƐƐŚĂůůďĞƐƵďŵŝƚƚĞĚƚŚƌŽƵŐŚƚŚĞŽŶůŝŶĞƉŽƌƚĂůŚƚƚƉƐ͗ͬͬĐŽŶŶĞĐƚ͘ŶĐĚŽƚ͘ŐŽǀͬƐŝƚĞͬWĞƌŵŝƚƐͬWĂŐĞƐͬĚĞĨĂƵůƚ͘ĂƐƉdž
/ŶƚŚĞŶŽƚŝĨLJĞŵĂŝůƐĞĐƚŝŽŶŽĨƚŚĞƉŽƌƚĂůĂƉƉůŝĐĂƚŝŽŶƉůĞĂƐĞŝŶĐůƵĚĞƚŚĞŝƐƚƌŝĐƚKĨĨŝĐĞĞŵĂŝů;ŝǀϯŝƐƚϯΛŶĐĚŽƚ͘ŐŽǀͿ͘^ĞĞƚŚĞůĂƐƚƉĂŐĞƐĨŽƌĨƵƌƚŚĞƌŝŶƐƚƌƵĐƚŝŽŶ͘
Online resources:
x NCDOT Policy on Street and Driveway Access to North Carolina Highways:
https://connect.ncdot.gov/projects/Roadway/RoadwayDesignAdministrativeDocuments/Policy%20on%20Street%20an
d%20Driveway%20Access.pdf
x NCDOT Policies and Procedures for Accommodating Utilities on Highway Rights of Way:
https://connect.ncdot.gov/municipalities/Utilities/Pages/UtilitiesManuals.aspx
x Electronic Forms Database:
https://connect.ncdot.gov/Pages/default.aspx
1)
Ă͘Cover >etter
Include contact information for applicant and engineer, including email address, mailing address, and phone
number. Include ƚŚĞƉĂƌĐĞůŶƵŵďĞƌ;ƐͿ͕description of all phases of the development and future land uses to be
served by the permit,ĂŶĚa description of the adjoining land owned or controlled by the applicant.
ď͘NCDOT Street and Driveway Access Permit Application (form downloadable via link below)
https://connect.ncdot.gov/resources/BusinessForms/TEB-65-04.doc
Đ͘$50.00 /nspection &eeWĞƌĐĐĞƐƐWŽŝŶƚ
Attach to Permit Application form (not applicable for municipalities, churches, and schools)
Ě͘NPDES Stormwater Permit Compliance Certification (form downloadable via link below)
https://connect.ncdot.gov/municipalities/Utilities/EncroachmentForms/NPDESstatement.doc
Ğ͘Verification of Compliance with Environmental Regulations (form downloadable via link below)
https://connect.ncdot.gov/municipalities/Utilities/EncroachmentForms/VCER-1.pdf
Ĩ͘Site Plans (to include the “Master Plan” of a tract even if only a small portion is being developed first)Additional
site plan requirement details can be found in section 2 of this document.
Ő͘ĞƐŝŐŶ PlanZĞƋƵŝƌĞŵĞŶƚƐ ĨŽƌƉƌŽũĞĐƚƐŝŶǀŽůǀŝŶŐƌŽĂĚǁĂLJŝŵƉƌŽǀĞŵĞŶƚƐ
If roadway improvements are required as part of the permit, ƚŚĞŶroadway plans͕ƉĂǀĞŵĞŶƚŵĂƌŬŝŶŐƉůĂŶƐ͕
ƐŝŐŶŝŶŐƉůĂŶƐ͕ĂŶĚƚƌĂĨĨŝĐĐŽŶƚƌŽůƉůĂŶƐǁŝůůďĞƌĞƋƵŝƌĞĚͲ^ĞĞ^ĞĐƚŝŽŶϲĨŽƌŵŽƌĞŝŶĨŽƌŵĂƚŝŽŶ
Y N n/a
Engineering Studies
The applicant may be required by the District Engineer to submit studies based on, but not limited to, the parameters outlined
herein. If study requirements of the local government agency are more restrictive than the NCDOT requirements, then local
government requirements will govern. However, this does not imply that the NCDOT is obligated to approve entrance designs
that are too constrictive to allow smooth and safe traffic flow. All studies including, but not limited to, Traffic Impact Analyses
(TIA), traffic signal studies, and drainage studies, must be prepared under the direct charge of and sealed by a North Carolina
licensed Professional Engineer.
Section 1: Requi
red Documents
|Required documents to accompany all /ŶŝƚŝĂůƌŝǀĞway Application Submittals
WůĞĂƐĞŶŽƚĞƚŚĂƚƚŚĞƐĞĂƌĞƚŚĞŵŝŶŝŵƵŵƌĞƋƵŝƌĞŵĞŶƚƐŽĨĂůůĚƌŝǀĞǁĂLJƉĞƌŵŝƚĂƉƉůŝĐĂƚŝŽŶƐ͘
ůůƌĞƋƵŝƌĞĚĚŽĐƵŵĞŶƚĂƚŝŽŶƐŚĂůůďĞƐƵďŵŝƚƚĞĚƚŚƌŽƵŐŚƚŚĞŽŶůŝŶĞƉŽƌƚĂůĂƐW&ĨŝůĞƐ͕ǁŝƚŚƚŚĞĞdžĐĞƉƚŝŽŶŽĨƚŚĞ
WĞƌĨŽƌŵĂŶĐĞĂŶĚ/ŶĚĞŵŶŝƚLJŽŶĚĂŶĚƚŚĞΨϱϬ/ŶƐƉĞĐƚŝŽŶ&ĞĞ;ƐͿ͕ƚŚĞƐĞƐŚŽƵůĚďĞŵĂŝůĞĚŽƌĚĞůŝǀĞƌĞĚƚŽϱϱϬϭ
ĂƌďĂĚŽƐůǀĚ͕ĂƐƚůĞ,ĂLJŶĞ͕EϮϴϰϮϵ͘
If a Traffic Impact Analysis and/or roadway improvements are deemed necessary as a condition of the permit͕ƚŚĞƌĞ
ŵĂLJďĞĂĚĚŝƚŝŽŶĂůƐƵďŵŝƚƚĂůŵĂƚĞƌŝĂůƐƌĞƋƵŝƌĞĚ͘
State of North Carolina | Department of Transportation | Division 3 | District 3
%DUEDGRV%OYG,&DVWOH+D\QH, NC 284
Form Updated/20(910) T NCDOT Permit #___________________
Y N n/a
Section 1: Required Documents (continued)
2)Required documents to accompany all Driveway Applications PRIOR TO FINAL APPROVAL
Ă͘Site Plans
Kne (1) digital copy (PDF) unless otherwise requested bythe District Office. Additional site plan requirement
details can be found in section 2 of this document.
ď͘Performance and Indemnity Bond/ŶĨŽƌŵĂƚŝŽŶͬFormƐ
^ĞĞůĂƐƚƉĂŐĞŽĨĚŽĐƵŵĞŶƚĨŽƌďŽŶĚŝŶĨŽƌŵĂƚŝŽŶĂŶĚĨŽƌŵƐ
Đ͘Performance and Indemnity Bond Amount
100% of ƚŚĞĐŽƐƚŽĨƚŚĞǁŽƌŬwithin NCDOT Zight-of-tay;ZͬtͿ based on ƚŚĞattached estimatedetermined by
ƚŚĞĂƉƉůŝĐĂŶƚΖƐĞŶŐŝŶĞĞƌĂŶĚĂƉƉƌŽǀĞĚďLJƚŚĞDistrict Engineer. ŽŶĚŚŽůĚůĞƚƚĞƌƌĞƋƵŝƌĞĚĨŽƌĨŽƌŵƵŶŝĐŝƉĂůŝƚŝĞƐ͕
ĐŚƵƌĐŚĞƐ͕ĂŶĚƐĐŚŽŽůƐ͘See pages 101-105 in the Policies and ProceduresforAccommodatingUtilities on Highway
Rights of Way for acceptable bond types
Ě͘Radius Encroachment Letter (if applicable)
If driveway radius encroaches on the frontage of an adjacent property, a Radius Encroachment will be required
Ğ͘Hold Harmless Letter (if applicable)
If the Wermit is within ƚŚĞůŝŵŝƚƐŽĨĂŶ active NCDOT project, a Hold Harmless letter from the NCDOT contractorwill
be required͘/ĨƚŚĞƉƌŽũĞĐƚŝƐŝŶƉƌĞĐŽŶƐƚƌƵĐƚŝŽŶ͕ĐŽŽƌĚŝŶĂƚĞǁŝƚŚƚŚĞĞƉĂƌƚŵĞŶƚΖƐWƌŽũĞĐƚĞǀĞůŽƉŵĞŶƚhŶŝƚ
Section 2: General Site Plan Requirements | All site plans shall include and show, at a minimum, the items listed below
Page numbers reference the NCDOT Policy on Street and Driveway Access to North Carolina Highways
ϭͿ Drawn to a scale of 20, 30, 40, or 50 feet per inch and the scale shall be shown
ϮͿ North arrow, vicinity map, date of plan, and date of most-recent revision if applicable
ϯͿ Contact information of applicant and engineer, including mailing address, phone number, and email address
ϰͿ Show Zͬt lines, highway control of access, and property lines
ϱͿ All existing utilities (including handholes) and easements
ϲͿ Rͬt width
ϳͿ Existing posted speed limit(s) and design speed limit(s)
ϴͿ Show all property lines, intersections, signals, signal loops, railroads, or crossovers within 500’ in all directions of
the property lines of the proposed development
ϵͿ Show location of sidewalks, crosswalks, greenways, multi-use paths, curb ramps, railroads, bus stops, and any
other relevant transportation facilities in the development area
ϭϬͿ Include a plan sheet showing full site build-out and land use
ϭϭͿ Buildings shown with “gross leasable area”
ϭϮͿ Width of property frontage
ϭϯͿ Distance from Rͬt to buildings and gasoline service islands
ϭϰͿ Distance from Rͬt to existing/proposed ĚŐĞŽĨWĂǀĞŵĞŶƚ;KWͿ (pages 32 & 34)
ϭϱͿ All streams, bridges, retaining walls, signs, or other fixed objects such as trees, utility poles, traffic signals, etc.
Section 3: Driveway Plan Requirements
|
All driveway plans shall include and show, at a minimum, the items listed below
ϭͿ WƌŽǀŝĚĞĐŽŵƉƌĞŚĞŶƐŝǀĞƐƵƌǀĞLJǁŝƚŚŝŶƚŚĞĞdžŝƐƚŝŶŐZͬtŽŶďŽƚŚƐŝĚĞƐŽĨƚŚĞƌŽĂĚĨŽƌĂĚŝƐƚĂŶĐĞŽĨϱϬϬ͛ŝŶĂůů
ĚŝƌĞĐƚŝŽŶƐĨƌŽŵƚŚĞĚĞǀĞůŽƉŵĞŶƚ͛ƐƉƌŽƉĞƌƚLJůŝŶĞƐ͘WƌŽǀŝĚĞĂĚĚŝƚŝŽŶĂůŚLJĚƌĂƵůŝĐƐƵƌǀĞLJĚĂƚĂƚŽƚŚĞŶĞĂƌĞƐƚƐƚŽƌŵ
ǁĂƚĞƌŝŶůĞƚͬŽƵƚůĞƚŝŶĐůƵĚŝŶŐĚŝƚĐŚůŝŶĞƐĂŶĚƐƚŽƌŵǁĂƚĞƌƉŝƉĞƐ͕ŝĨůŽĐĂƚĞĚŽƵƚƐŝĚĞŽĨƚŚĞϱϬϬΖĚŝƐƚĂŶĐĞ͘
ϮͿ Lane configurations and widths of all existing and proposed driveways, roadways, and adjacent roadways
ϯͿ All driveway widths (2-way: 20’ minimum, 36’ maximum | 1-way: 12’ minimum, 24’ maximumͮǁŝƚŚŝƐůĂŶĚ͗ϭϰΖ
ŝŶŐƌĞƐƐ͕ϭϴΖĞŐƌĞƐƐ) (pageƐϱϬΘϳϳ)
ϰͿ ƌŝǀĞǁĂLJWƌŽĨŝůĞͲ/ŶƐŚŽƵůĚĞƌƐĞĐƚŝŽŶƐ͕ŵaintain minimum 2% fall from edge of travel way for required
shoulder width ĚŝƐƚĂŶĐĞWƌŝŵĂƌLJ͗ϴ͛ŵŝŶŝŵƵŵͮ^ĞĐŽŶĚĂƌLJ͗ϲ͛ŵŝŶŝŵƵŵ
ϱͿ All existing and/or proposed driveway radii (20’ minimum, 50’ maximum, 30’ typical) (pages 34 & 51)
In curb and gutter sections, use City of Wilmington flare (SD 3-03.3)Ͳ;ƐĞĞĂƚƚĂĐŚĞĚͿ
In shoulder sections, show grades at the KW and centerline
ϲͿ No curbing is allowed within NCDOT RͬW along shoulder sections except as part of a driveway island(page 31)
ϳͿ Driveway angles of approach to existing roadway (90° preferred, 75°-90° required for 2-way driveways, 45°-90°
allowed for right-in/right-out on a case-by-case basis) (page 51)
ϴͿ Driveway Wrofile (pages 42- 43)
Y N n/a Y N n/a
පප පපප ප
Y N n/a Y N n/a
Y N n/a Y N n/a
Section 3: Driveway Plan Requirements (continued)
ϵͿ Driveway Pavement Cross Section (to be in place from KW to edge of RͬW)
Asphalt: 8” ABC stone and 1.5” S9.5
Concrete: 6” of concrete
ϭϬͿ Driveway Offset (driveway KW to property line; page 75): Minimum: 20’
ϭϭ)Corner Clearance (radius point to radius point; page 52) Minimum: 50’ Desirable: 100’ or DƵŶŝĐŝƉĂů std.
ϭϮͿ Minimum 10’x70’ sight triangles at driveways (measured from and along the Zͬt line) (page 31)
ϭϯͿ Sight Distance (ůength of sight-distance in both directions shown for each driveway; pages 27-29)
ϭϰͿ Driveways should be aligned with existing opposing driveways or correct offset should be provided (pages 40-41)
ϭϱͿ Distance between driveways being requested (if applicable; page 51)
ϭϲͿ Minimum internal storage areasǁŝƚŚƐƉĞĐŝĨŝĞĚƋƵĞƵĞƐ (pages 31-33)
ϭϳͿ Minimum protected driveway stem(s) provided and indicated (pages 33-34)
ϭϴͿ Indicate any gated entrances (100’ minimum setback from RͬW required)ͲƚƌĂĨĨŝĐƋƵĞƵŝŶŐƐƚƵĚLJŵĂLJďĞƌĞƋƵŝƌĞĚ
|
Section ϲ: Roadway
Plan Requirements
If off-site improvements are required, roadway plans shall show, at a minimum, the items below
ϭͿ Full width typical sections must be shown (paved shoulders to match the typical section of the adjacent roadway)
ϮͿ Minimum Asphalt Typical Section (for turn lanes and/or paved shoulders)
Adjacent recently-completed or upcoming TIP projects w/ different typical sections may supersede those below
x Primary Routes (US & NC) and Secondary Routes with ŶŶƵĂůǀĞƌĂŐĞĂŝůLJdƌĂĨĨŝĐ;AADTͿшϭϬ,000
5͘ϱ” B25.0, 3” I19.0, ϭ͘ϱ” S9.5; any overlay of existing pavement is to be a minimum of 1.5” S9.5
x Secondary Routes with AADT<ϭϬ,000
5͘ϱ” B25.0, ϭ͘ϱ” Sϵ͘ϱ; any overlay of existing pavement is to be a minimum of 1.5” Sϵ͘ϱ
ϯͿ Pavement overlay is required if modification of existing pavement markings and/or lanes is necessary
The grinding of pavement markings will not be allowed
ϰͿ Shoulder Widths (Paved + Unpaved)WƌŝŵĂƌLJ͗ϴ͛ŵŝŶŝŵƵŵͮ^ĞĐŽŶĚĂƌLJ͗ϲ͛ŵŝŶŝŵƵŵ
ϱͿ ŝƚĐŚ^ůŽƉĞƐͲĨƌŽŶƚĂŶĚďĂĐŬƐůŽƉĞƐͲŵŝŶŝŵƵŵϯ͗ϭŽƌĨůĂƚƚĞƌ
ϲͿ Indicate existing roadway grade
ϳͿ All taper lengths and deceleration lengths should be appropriately designed for the given design speed (page78)
ϴͿ All turn lanes should be designed according to the Driveway Manual and Roadway Standard Drawings (page 79)
See 1205.04 Sheets 1 & 2 and 1205.05 Sheet 1 of the Roadway Standard Drawings for details
ϵͿ Pavement markingĂŶĚƐŝŐŶŝŶŐ planƐ ĂƌĞƌĞƋƵŝƌĞĚͲplans must be approved by Division Traffic Services
ϭϬͿ dƌĂĨĨŝĐĐŽŶƚƌŽůƉůĂŶƐĂƌĞƌĞƋƵŝƌĞĚͲĞƚĂŝůĞĚƉŚĂƐŝŶŐƉůĂŶƐŵĂLJďĞƌĞƋƵŝƌĞĚďĂƐĞĚŽŶƉƌŽũĞĐƚƚLJƉĞĂŶĚůŽĐĂƚŝŽŶ
ϭϭͿ EĞǁĂŶĚͬŽƌƌĞǀŝƐĞĚƐŝŐŶĂůƉůĂŶƐŵƵƐƚďĞŝŶĐůƵĚĞĚĨŽƌŶĞǁŝŶƐƚĂůůĂƚŝŽŶƐĂŶĚŝĨƐŝŐŶĂůŵŽĚŝĨŝĐĂƚŝŽŶƐĂƌĞƌĞƋƵŝƌĞĚ
ůůsignal plans must be reviewed and approved by Division Traffic Services and the Signal Design Unit. ATraffic
Agreement must be completed to facilitate the review. Contact Division Traffic Services at (910) 341-ϮϮϬϬ.
|
Section ϰ: Drainag e Requirements
All drainage features on NCDOT Right-of-Way shall adhere to, at a minimum, the items listed below
Section ϱ: Internal Circ ulation Requirements
|All internal circulation details shall adhere to, at a minimum, the items listed below
ϭͿ Interior driveway channelization stems
Minimum 100’ from the RKW or at the discretion of the District Engineer
ϮͿ Traffic flow pattern
ϯͿ Traffic control devices
ϰͿ Pavement Markings
Y N n/a Y N n /a
Y N n/a Y N n/a
Y N n/a Y N n/a
Y N n/a Y N n/a
ϭͿ Pipe Cover Minimums (measured from top of pipe to subgrade)
High Density Polyethylene (HDPE): Ϯϰ” | Corrugated Aluminum (CAP): 12” | Reinforced Concrete (RCP): 12”
ϮͿ WŝƉĞŶĚdƌĞĂƚŵĞŶƚ;ƐĞĞZŽĂĚǁĂLJĞƐŝŐŶDĂŶƵĂůϱͲϮϬ͕ͲϮͿ
WŝƉĞƐчϮϰΗŽŶŵƵůƚŝůĂŶĞŚŝŐŚǁĂLJƐƉŽƐƚĞĚĂďŽǀĞϰϱŵƉŚƌĞƋƵŝƌĞWĂƌĂůůĞůWŝƉĞŶĚ^ĞĐƚŝŽŶƐ^ĞĞϯϭϬ͘ϬϮĂŶĚ
ϯϭϬ͘ϬϰŽĨƚŚĞZŽĂĚǁĂLJ^ƚĂŶĚĂƌĚƌĂǁŝŶŐƐĨŽƌĚĞƚĂŝůƐ
WŝƉĞƐхϯϬΗŽŶŵƵůƚŝůĂŶĞŚŝŐŚǁĂLJƐƉŽƐƚĞĚĂďŽǀĞϰϱŵƉŚƌĞƋƵŝƌĞŐƵĂƌĚƌĂŝů
WŝƉĞƐшϯϲΗƌĞƋƵŝƌĞĂŶĞŶĚǁĂůůŽŶƚŚĞŝŶůĞƚĞŶĚ
ϯͿ ůůƉƌŽƉŽƐĞĚƌĂŝŶĂŐĞŝƐƚŽďĞƉƌŽǀŝĚĞĚŝŶƐŝĚĞĞdžŝƐƚŝŶŐZͬt͘KƚŚĞƌǁŝƐĞ͕ĂĚĚŝƚŝŽŶĂůZͬtŽƌĂƉĞƌŵĂŶĞŶƚůLJ
ĚĞĚŝĐĂƚĞĚĚƌĂŝŶĂŐĞĞĂƐĞŵĞŶƚǁŝůůďĞƌĞƋƵŝƌĞĚƚŽĂĐĐŽŵŵŽĚĂƚĞƚŚĞƉƌŽƉŽƐĞĚƉƌŽũĞĐƚĚƌĂŝŶĂŐĞ
ϰͿ All sizes, types, and invert elevations of existing/proposed pipes and drainage structures must be shown
;ƐĞĞ^ĞĐ͘ϯηϭĨŽƌƐƵƌǀĞLJƌĞƋƵŝƌĞŵĞŶƚƐͿ
ϱͿ Provide spot elevations along frontage of driveway (at EKW and centerline)
ϲͿ Provide grades and spot elevations for existing and proposed ditches
ϳͿ Show how drainage will be accommodated along property frontage
(District Engineer may require applicant to provide drainage calculations whĞŶǁĂƌƌĂŶƚĞĚͿ
MEMORANDUM
To: New Hanover County Technical Review Committee
Date: 8/30/23
Subject: 5505 Carolina Beach Rd – Fast Food Restaurant
Comments:
• A TIA has been completed for the Villages at Myrtle Grove shopping center. All required
improvements have been installed and accepted. NCDOT will not require an update to
the original approved 2006 TIA.
• Show ordering board/menu on plans.
• Please show total storage available for the drive-thru beginning at the menu
board/ordering station per NCDOT Policy on Street and Driveway Access. Note:
Assumed length of a car is 25’.
• Please label all radii on plans.
• Please show ADA detectable warning pad at all curb ramps.
• Recommend making the circulation pattern around the structure to be one way due to
potential conflicts with drive-thru stacking.
2
NCDOT Projects:
U-5790 Road Widening and Flyovers @ US 421 and NC 132
Location: From College Rd to Sanders Rd
ROW Year: 2027
Construction Year: 2029
WMPO 2045 Projects: N/A
New Hanover County CTP: N/A
TIA: Based on the 11th edition ITE Trip Generation Manual.
Land Use (ITE Code) Intensity Unit 24 Hour
Volumes
AM Peak
Hour Trips
PM Peak
Hour Trips
ITE 934 Fast Food w/
Drive-Through 2,325 SF 1,089 104 77