HomeMy WebLinkAboutElectrical Permit31
0
M
E
T
R
O
C
I
R
C
L
E
Wi
l
m
i
n
g
t
o
n
,
N
C
2
8
4
0
8
SHEET NUMBER:
11.16.23
SHEET NAME:
NOT FOR
CONSTRUCTION
DRAWN BY:
CHECKED BY:
DATE DESCRIPTION
11/16/2023
ISSUE / REVISIONS:
PERMIT SET
AN
RD
5335 W 48th Ave Suite 103
Denver, CO 80212
720.779.3556
PROJECT # 323082
N O R T H C AR LI
N
A
O
12/15/2023 REVISION 1
SITE PLAN
E-1
SPECIFICATIONS SPECIFICATIONS
ABBREVIATIONS
AC
AMP FUSEAF
ABOVE FINISHED FLOORAFF
BELOW FINISHED CEILINGBFC
BREAKERBKR
CONNECTED OR CONNECTIONCONN
CTB
DOWNDN
EMPTY CONDUITEC
ELECTRICALELEC
FIRE ALARM CONTROL PANELFACP
FAA
G OR GRND
GFCI OR GF
ISOLATED GROUNDIG
SHORT CIRCUIT CURRENTISC
LIGHTINGLTG
MOUNTEDMTD
NATIONAL ELECTRICAL CODENEC
PANELPNL
RECEPTACLERECPT
TELEPHONETELTELEPHONE
TTB
TELEVISIONTV
SPD
TYPICALTYP
TRANSFORMERXFMR
UNDERGROUNDUG
WEATHERPROOFWP
NEUTRALN
COPPERCU
ALUMINUMAL
CONDUITCND
NIGHT LIGHTNL
TELEPHONE TERMINAL BOARD
EQUIPMENT AS NOTED ON DRAWING.
DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R 18" AFF
DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R
18" AFF
AC
18" AFF
IN CEILINGJ
J
42" AFFSSWITCH
MOTORM
SYMBOLS DESCRIPTION
XX-#
LEGEND
42" AFFSWITCH - 3 WAY
DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R
DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R IN CEILING
18" AFF
TELEPHONE OUTLET 18" AFF
TELEPHONE / DATA COMBINATION OUTLET 18" AFF
TELEPHONE / DATA COMBINATION OUTLET
DATA OUTLET
DATA OUTLET
18" AFF
D
TV OUTLET 18" AFF
H
SMOKE DETECTOR. CEILING / WALL MOUNTEDD
H HEAT DETECTOR. CEILING/WALL MOUNTED
80" AFF
80" AFF
80" AFF
FIRE ALARM NOTIFICATION DEVICE. AUDIO.
FIRE ALARM NOTIFICATION DEVICE. VISUAL.
FIRE ALARM INITIATION DEVICE. PULL STATION.42" AFF
42" AFF
42" AFFSWITCH - WALL MTD, LOW VOLTAGE, PILOT LIGHT
SWITCH - CEILING MOUNTED OCCUPANCY SENSOROS IN CEILING
42" AFFSWITCH - WALL MTD, DIMMING
TELEPHONE / DATA COMBINATION OUTLET
J
S3
SOS
SLV
SD
/
/
/
ELECTRICAL GENERAL NOTES
GENERAL
CONTRACTOR SHALL REFER TO ALL RELATED DOCUMENTS, ARCHITECTURAL, STRUCTURAL,
CIVIL AND MEP DRAWINGS, AND FULLY UNDERSTAND THE SCOPE OF WORK AND CONDITION
OF CONSTRUCTION.
THE WORK UNDER THIS SPECIFICATIONS AND DRAWINGS SHALL INCLUDE ALL LABOR.
ALL INSTALLATION OF DEVICES AND CONNECTION OF CONDUCTORS SHALL BE PERFORMED
BY LICENSED AND SKILLED ELECTRICIAN OR JOURNEYMAN.
ALL WORK SHALL BE COMPLETED TO THE SATISFACTION OF THE OWNER. IF ANY PORTION OF
THE WORK IS FOUND UNSATISFACTORY BY THE OWNER, IT SHALL BE REMOVED AND
REINSTALLED WITHOUT DELAY AT NO COST TO THE OWNER.
THE WORK INCLUDES, BUT NOT LIMITED TO:
THE COMPLETE ELECTRICAL DISTRIBUTION SYSTEM.
ROUGH-IN AND FINAL CONNECTIONS TO ALL DEVICES REQUIRING ELECTRICAL POWER,
INCLUDING OWNER PROVIDED EQUIPMENT.
LIGHTING CONTROL
LIGHTING FIXTURES
EACH CONTRACTOR SHALL OBTAIN ALL PERMITS AND INSPECTIONS REQUIRED BY THE
REGULATORY AUTHORITIES. ALL FEES RELATED TO OBTAINING PERMITS AND INSPECTION
SHALL BE PAID FOR BY EACH CONTRACTOR IN HIS TRADE.
ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH LOCAL, COUNTY, STATE, AND
NATIONAL ELECTRICAL CODE 2020, SPECIFICATIONS, UTILITY COMPANY REQUIREMENTS AND
ALL INDUSTRY STANDARDS.
ANY DIFFERENCES IN ABOVE MENTIONED REQUIREMENTS, THE MOST STERN SHALL
OVERRULE ALL OTHERS.
IN ADDITION TO ABOVE MENTIONED CODES AND SPECIFICATIONS, THE FOLLOWING INDUSTRY
STANDARDS SHALL BE COMPLIED IF THEY ARE MORE STRINGENT.
IEEE
IES
IECC 2015
ASHRAE 90.1
NFPA
NEMA
UL
ADA
THE MANUFACTURER'S PUBLISHED DIRECTIONS SHALL BE FOLLOWED IN THE DELIVERY,
STORAGE, PROTECTION, INSTALLATION AND WIRING OF ALL EQUIPMENT AND MATERIAL.
THE DRAWINGS SHOW DIAGRAMMATICALLY THE LOCATIONS OF THE VARIOUS LINES,
CONDUITS, FIXTURES, AND EQUIPMENT AND THE METHOD OF CONNECTING AND
CONTROLLING THEM. IT IS NOT INTENDED TO SHOW EVERY CONNECTION IN DETAIL AND ALL
FITTINGS REQUIRED FOR A COMPLETE SYSTEM. THE SYSTEMS SHALL INCLUDE BUT ARE NOT
LIMITED TO THE ITEMS SHOWN ON THE DRAWINGS. EXACT LOCATIONS OF THESE ITEMS
SHALL BE DETERMINED BY REFERENCE TO THE GENERAL PLANS AND MEASUREMENTS AT THE
BUILDING AND IN COOPERATION WITH THE OTHER SUBCONTRACTORS, AND IN ALL CASES,
SHALL BE SUBJECT TO THE APPROVAL OF THE OWNER. THE OWNER RESERVES THE RIGHT TO
MAKE ANY REASONABLE CHANGE IN THE LOCATION OF ANY PART OF THIS WORK WITHOUT
ADDITIONAL COST TO THE OWNER.
CONTRACTOR SHALL SEEK APPROVAL FROM THE OWNER FOR ANY CHANGES TO THE
SPECIFICATIONS OR CONTRACT DOCUMENTS.
ANY EXCEPTIONS, INCONSISTENCIES AND CONFLICTS IN CONTRACT DOCUMENTS,
SPECIFICATIONS AND CONTRACT DOCUMENTS BY OTHER TRADE SHALL BE BROUGHT TO
ATTENTION TO THE OWNER PRIOR TO BID.
CONTRACTOR SHALL COORDINATE AND VERIFY THE WORK WITH EXISTING CONDITIONS AND
THE WORK OF OTHER TRADE PRIOR TO ANY FABRICATIONS OR INSTALLATION. IF THE LAYOUT
OF THE DEVICES ON DRAWINGS ARE IMPRACTICAL TO THE CONDITION IN FIELD,
CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY PRIOR TO ANY FABRICATION OR
INSTALLATION.
ELECTRICAL DEVICES ARE INDICATED ON DRAWINGS AT APPROXIMATE LOCATIONS. THE
OWNER RESERVE THE RIGHT TO MAKE REASONABLE CHANGES IN LOCATIONS WITHOUT
ADDITIONAL COSTS.
THE LINES INDICATING BRANCH CIRCUITS DO NOT REPRESENT THE ROUTING OF ELECTRICAL
CONDUITS. THEY INDICATE THE LAYOUT AND CONTROL OF CIRCUITS.
PRODUCTS AND WORK
MATERIALS FURNISHED SHALL BE NEW AND BY STANDARD MANUFACTURERS AND MUST
CONFORM TO THE NATIONAL BOARD OF FIRE UNDERWRITER'S REQUIREMENTS AND BEAR THE
UNDERWRITER'S LABORATORIES' SEAL OF APPROVAL.
LISTED MANUFACTURERS, MODELS, OR CATALOGUE NUMBERS IN PART OR ALL SHALL ENTAIL
TO INCLUDE THE PUBLISHED MANUFACTURER'S DESCRIPTION AND SPECIFICATION.
CONTRACTOR SHALL NOT INTERPRET THAT THE LISTED MANUFACTURERS IN SPECIFICATIONS
OR DRAWINGS TO EXCLUDE ALL OTHER MANUFACTURERS.
CONTRACTOR SHALL MAKE CERTAIN THAT ALL EQUIPMENT FIT IN THE SPACE DESIGNATED
AND DESIGNED FOR THE SURROUNDINGS IT OCCUPIES.
COMPLETE CATALOGUE ILLUSTRATION AND DESCRIPTIONS OF ALL EQUIPMENT SHALL BE
SUBMITTED TO THE OWNER PRIOR TO ORDERING ANY EQUIPMENT.
ALL HORIZONTAL RUNS OF CONDUITS SHALL BE SUPPORTED BY MEANS OF APPROVED
HANGER FROM THE STRUCTURAL CEILING.
COORDINATE THE WORK UNDER THIS SECTION WITH ALL OTHER TRADES.
CONDUITS AND RACEWAYS:
MANUFACTURERS: SQUARE D, B-LINE, ALLIED TUBE & CONDUIT, HOFFMAN, CARLON
ELECTRICAL, WIREMOLD.
OUTDOORS EXPOSED: RIGID STEEL.
OUTDOORS CONCEALED ABOVE GROUND: RIGID STEEL.
OUTDOORS UNDERGROUND: TYPE EPC-40-PVC
OUTDOORS CONNECTION TO VIBRATING EQUIPMENT (INCLUDING TRANSFORMERS AND
MOTOR DRIVEN EQUIPMENT): LFMC.
BOXES AND ENCLOSURES ABOVE GROUND: NEMA 3R UNLESS NOTED OTHERWISE ON PLANS.
INDOORS EXPOSED NOT SUBJECT TO PHYSICAL DAMAGE: EMT. INDOORS EXPOSED NOT
SUBJECT TO SEVERE PHYSICAL DAMAGE: EMT.
INDOORS EXPOSED SUBJECT TO SEVERE PHYSICAL DAMAGE: RIGID STEEL CONDUIT.
INDOORS CONCEALED IN CEILINGS AND INTERIOR WALLS AND PARTITIONS: EMT.
INDOORS CONNECTION TO VIBRATING EQUIPMENT: FMC, EXCEPT USE LFMC IN DAMP OR
WET LOCATIONS.
INDOORS DAMP OR WET LOCATIONS: IMC.
INDOORS LOW-VOLTAGE CABLES: EMT.
CONDUCTORS:
COPPER CONDUCTORS #10 AND SMALLER: LABELED PER UL 83, TYPE THHN/THWN, SOLID
COPPER 600 VOLT INSULATION, UNIFORM COLOR CODED JACKET WITH JACKET DATA.
METAL CLAD (TYPE MC) CABLE WHERE INSTALLED IN ACCORDANCE WITH NEC ARTICLE 330.
COPPER CONDUCTORS #8 OR LARGER: LABELED PER UL 83, TYPE THHN/THWN, STRANDED
COPPER, 600VOLT INSULATION, UNIFORM COLOR CODED JACKET WITH JACKET DATA.
ACCEPTABLE MANUFACTURERS OF CONDUCTORS:
PIRELLIE
SOUTHWIRE
AETNA
REPUBLIC
AFC
ENCORE WIRE
KERITE
CONTRACTOR MAY USE ALUMINUM CONDUCTORS FOR #4 AWG OR LARGER IN THE PLACE OF
COPPER CONDUCTORS. CONTRACTOR SHALL REFER TO NEC TABLE 310-16 FOR
EQUIVALENT AMPACITY AND SHALL COMPENSATE FOR VOLTAGE DROP.
CONTRACTOR SHALL MAKE ADEQUATE ADJUSTMENT TO CONDUIT SIZES INDICATED SHOULD
ALTERNATIVE CONDUCTOR INSULATION OR MATERIAL BE UTILIZED.
MOLDED CASE CIRCUIT BREAKER:
INCLUDE SCHEDULE OF ALL FUSES, RATINGS, TIME COORDINATION DATA, MANUFACTURER'S
STANDARD DATA AND TIME-CURRENT CURVES. ALL DATA SHALL BE BASED ON TEST OF
STANDARD PRODUCTS.
APPROVED MANUFACTURERS:
GENERAL ELECTRIC
CUTLER HAMMER
SQUARE D
SIEMENS
THERMAL-MAGNETIC BOLT-IN TYPE CIRCUIT BREAKERS WITH QUICK-MAKE, QUICK-BREAK
CONTACTS; TRIP-FREE OPERATION WITH OVER-THE-CENTER TOGGLE HANDLE OR
NON-REMOVABLE MONOLITHIC TIE-HANDLE.
MULTI-POLE BREAKERS SHALL HAVE INTERNAL COMMON TRIP AND COMMON RESET WITH A
SINGLE TOGGLE HANDLE OR NON-REMOVABLE MONOLITHIC TIE-HANDLE.
TRIP RATINGS SHALL BE MOLDED ON THE HANDLE OR FACE OF BREAKER.
BREAKER TERMINALS SHALL BE RATED TO ACCOMMODATE A MINIMUM OF 75 DEGREE C.
CONDUCTORS.
BREAKER SHALL BE RATED FOR MOUNTING AND OPERATION IN ANY POSITION; SHALL
ACCOMMODATE AND MATCH THE TYPE OF TERMINATIONS REQUIRED.
SINGLE POLE BREAKERS RATED 15 AND 20 AMPERES SHALL BE UL LABELED AS "SWITCHING
BREAKERS" AT THE APPLIED CIRCUIT VOLTAGE.
MULTI-POLE BREAKERS RATED 100 AMPERES AND LARGER SHALL BE MOLDED CASE
THERMAL-MAGNETIC BOLT-IN TYPE BREAKER WITH ADJUSTABLE INSTANTANEOUS TRIP.
LIGHTING FIXTURE
SUBMITTAL:
SCHEDULE BY TYPE DESIGNATION ALL LIGHTING FIXTURES, EACH COMPLETE WITH DATA SHEET
WITH COMPLETE PHYSICAL, ELECTRICAL AND LIGHTING CHARACTERISTICS, LAMP TYPE AND
LAMP DATA.
REFER TO THE "LIGHTING FIXTURE SCHEDULE" \IN THE DRAWINGS FOR INDIVIDUAL FIXTURE
DESCRIPTIONS AND MANUFACTURER TYPES.
PROVIDE LAMPS FOR EACH FIXTURE OF QUANTITY, TYPE AND COLOR AS LISTED IN LIGHTING
FIXTURE SCHEDULE. GE, SYLVANIA OR PHILIPS ARE ACCEPTABLE.
EACH LIGHTING FIXTURE SHALL BE UL LABELED FOR PROPER OPERATION IN THE TYPE OF
CEILING CONSTRUCTION AND FOR THE MOUNTING ARRANGEMENT ON/IN WHICH IT IS
INSTALLED.
FIELD VERIFY ACTUAL CEILING SLOPE FOR FIXTURES INSTALLED IN SAME AND ACTUAL FIELD
DIMENSIONS AND ANGLES OF CONSTRUCTION FOR ANY FIXTURE CONFORMING THE SHAPE
AND LENGTH OF SAME, FOR COORDINATION OF FIXTURE CONSTRUCTION.
PANELBOARD
SUBMITTAL:
INCLUDE SCHEDULE OF EACH PANELBOARD WITH ALL DEVICES AND COMPLETE WITH PHYSICAL AND
ELECTRICAL DATA AND WITH RATINGS FOR EACH COMPONENT INCLUDING BREAKER/FUSE OVERLAY
CURVES.
LABELED PER UL #67 AND #50, CONFORM WITH NEMA #250 AND PB1, NFPA #70-384 AND 70-373.
ALL JUNCTION BOXES SHALL BE LABELED WITH PANEL AND CIRCUIT DESIGNATION.
PROVIDE TYPED CIRCUIT DIRECTORY WITH EACH CIRCUIT SERVING DEVICES AND AREA IT'S SERVING.
APPROVED MANUFACTURERS:
GENERAL ELECTRIC
CUTLER HAMMER
SQUARE D
SIEMENS
GROUNDING AND BONDING
ALL GROUNDING AND BONDING SHALL CONFORM TO NEC ARTICLE 250.
COPPER WIRE OR CABLE INSULATED FOR 600V UNLESS REQUIRED BY APPLICABLE CODE OR
AUTHORITIES HAVING JURISDICTION.
INSTALL SOLID CONDUCTOR FOR #8 AWG AND SMALLER AND STRANDED CONDUCTORS FOR
#6 OR LARGER.
INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTORS FOR ALL EQUIPMENT.
THE DESIGN OF THIS SET OF DOCUMENT IS BASED ON NEC 2020.
ELECTRICAL CONTRACTOR SHALL REFER TO ALL OTHER DESIGN DRAWINGS PRIOR TO BID AND
RETAIN FULL UNDERSTANDING OF THE SCOPE OF WORK.
FIXTURE TYPE INDICATED BY UPPER CASE CHARACTERS, SWITCHING AND GROUPING
DESIGNATED BY LOWER CASE LETTER AND CIRCUIT BY NUMBER (WHERE APPLICABLE).
REFER TO THE ARCHITECTURAL/INTERIORS REFLECTED CEILING PLANS FOR EXACT FIXTURE
PLACEMENT AND DIMENSIONS.
REFER TO THE ARCHITECTURAL/INTERIORS DOCUMENTS FOR ACTUAL DEVICE LOCATIONS AND
DIMENSIONS.
COORDINATE THE INSTALLATION OF ALL CEILING MOUNTED DEVICES (FIRE ALARM SYSTEM
DEVICES AND SPEAKERS, SOUND SYSTEM SPEAKER, ETC.) TO BE SYMMETRICAL ABOUT LIGHT
FIXTURES AND SPRINKLER HEADS. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN.
TYPICAL.
ALL MOUNTING OF EQUIPMENT IS AS SHOWN UNLESS OTHERWISE NOTED. COORDINATE WITH
ARCHITECT THE COLOR/FINISHES OF ALL ELECTRICAL DEVICES, OUTLETS, COVERPLATES AND
TRIM.
EMERGENCY BATTERY PACKS AND EXIT SIGNS SHALL BE CONNECTED AHEAD OF ANY
SWITCHING DEVICES.
REFER TO MECHANICAL DRAWINGS FOR DUCT SMOKE DETECTOR LOCATIONS AND QUANTITIES
OPERATION SHALL INCLUDE DUAL CONTACT BASE WITH LOCAL EQUIPMENT SHUTDOWN AND
FIRE ALARM SIGNAL INITIATION.
WHEN CONDUCTOR OR CONDUIT SIZE IS INDICATED FOR BRANCH CIRCUIT HOME RUN, THE
CONDUCTOR AND CONDUIT SIZE INDICATED SHALL BE USED FOR THE COMPLETE CIRCUIT.
REFER TO THE APPROPRIATE DRAWINGS FOR THE EXACT LOCATION AND REQUIREMENTS OF
EQUIPMENT INSTALLED UNDER OTHER DIVISIONS OF THE DOCUMENTS, WHICH REQUIRE
ELECTRICAL SERVICE.
EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSTALLED IN ALL RACEWAYS.
WALL SWITCHES CONTROLLING CIRCUITS OF OPPOSITE PHASES SHALL NOT BE INSTALLED IN
COMMON BOX UNLESS PERMANENT BARRIER IS PROVIDED.
ALL HOME RUNS SHALL RUN PARALLEL TO STRUCTURE AS MUCH AS POSSIBLE WHERE CEILING
IS EXPOSED.
ALL RACEWAY AND EQUIPMENT SUPPORTS AND HANGERS SHALL BE FULLY COORDINATED
WITH STRUCTURAL DRAWINGS TO INSURE LOCATION OF SAME OCCURS WITHIN FOUR (4)
INCHES OF PANEL POINT ON BAR JOISTS.
COORDINATE LOCATION OF ALL FLOOR MOUNTED MECHANICAL AND PLUMBING EQUIPMENT IN
ORDER TO VERIFY POWER & CONTROL RACEWAY CONCEALED IN SLABS TERMINATED AT
PROPER LOCATION.
DISCONNECT SWITCHES, MOTOR STARTERS AND OTHER ELECTRICAL EQUIPMENT INSTALLED
ABOVE ACCESSIBLE CEILINGS, AND REQUIRING ACCESS FOR MAINTENANCE, SHALL BE
INSTALLED WITH BOTTOM OF DEVICE ONE (1) FOOT ABOVE CEILING TO PROVIDE READY
ACCESSIBILITY.
MECHANICAL, PLUMBING, FIRE PROTECTION AND OTHER EQUIPMENT ARE SHOWN ON FLOOR
PLAN IN APPROXIMATE LOCATION. COORDINATE WITH M, P, FP AND CONTRACT
DRAWINGS/SUBMITTALS FOR EXACT LOCATION OF EQUIPMENT.
GENERAL DIAGRAMMATIC RACEWAY INTERCONNECTIONS OF EQUIPMENT, FIXTURES AND
DEVICES ARE INDICATED ON FLOOR AND REFLECTED CEILING PLANS, REFER TO STRUCTURAL
AND ARCHITECTURAL PLANS FOR ELEVATION CHANGES AND RACEWAY ROUTES.
RACEWAY FOR EXTERIOR LIGHTING MAY BE INDICATED OUTSIDE OF BUILDING FOOTPRINT FOR
CLARITY. ROUTE ALL EXTERIOR LIGHTING RACEWAY WITHIN BUILDING STRUCTURE.
POWER AND COMMUNICATIONS/DATA CONDUITS CAN CROSS AT 90°, BUT WHERE PARALLEL,
SHALL BE A MINIMUM OF 8" APART.
TELEVISION AND RADIO ANTENNAS CABLES SHALL HAVE SURGE PROTECTION. GROUND ALL
MASTS.
PROVIDE SURGE PROTECTION FOR ELECTRICAL AND TELEPHONE SERVICES.
PROVIDE SPD FOR FIRE ALARM CONTROL PANEL.
FIELD COORDINATE MECHANICAL AND PLUMBING EQUIPMENT ELECTRICAL CHARACTERISTICS
WITH DIV.15 CONTRACTOR PRIOR TO ROUGH-IN. ADJUST ELECTRICAL CONNECTIONS IF
NECESSARY TO MATCH ACTUAL EQUIPMENT IN FIELD. FOR EXAMPLE, COORDINATE THE
NAMEPLATE OVERCURRENT PROTECTION DEVICE RATING OF MECHANICAL EQUIPMENT AMONG
MECHANICAL AND ELECTRICAL SUBCONTRACTORS. ADJUST CIRCUIT BREAKER TO MATCH
NAMEPLATE RATING OF EQUIPMENT AT NO ADDITIONAL COST.
FIELD COORDINATE MECHANICAL AND PLUMBING EQUIPMENT REQUIREMENTS FOR ANY
SUPPLEMENTAL POWER REQUIREMENTS, INCLUDING BUT NOT LIMITED TO CONTROL CIRCUITS.
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO BRING ALL EQUIPMENT TO ITS INTENDED
OPERATIONAL STATUS.
REFER TO FIRE PROTECTION DRAWINGS FOR LOCATIONS OF FLOW AND TAMPER SWITCHES.
EACH PENETRATION OF A FIRE RESISTANT RATED ASSEMBLY BY A PIPE, TUBE WIRE OR
CONDUIT SHALL BE PROTECTED BY A THROUGH PENETRATION FIRE STOP SYSTEM THAT HAS
BEEN TESTED ACCORDING TO ASTME 814 OR E199.
ELECTRIC RECEPTACLES, SWITCHES, OUTLETS, ETC. SHALL NOT BE INSTALLED BACK TO BACK
ON FIRE RESISTANCE RATED WALLS. THEY SHALL BE AT LEAST 24-INCHES APART.
LIGHT SWITCHES AND ELECTRICAL OUTLETS, LOCATED IN ROOMS ACCESSIBLE TO THE
DISABLED SHALL BE LOCATED NO HIGHER THAN 48 INCHES AND NO LOWER THAN 15 INCHES
ABOVE THE FINISHED FLOOR SURFACE. IF THE REACH OR THE CONTROL IS OVER AN
OBSTRUCTION, THE MINIMUM HEIGHT SHALL BE REACHED TO 44 INCHES FOR A FORWARD
APPROACH OR 46 INCHES FOR A SIDE APPROACH.
REFER TO LOW VOLTAGE CONSULTANT'S DRAWINGS FOR VOICE, DATA AND CATV OUTLET
LOCATIONS. REFER TO LV CONSULTANT'S DRAWINGS FOR ANY ADDITIONAL INFORMATION.
CONNECT ALL EXIT SIGNS TO NEAREST UNSWITCHED PORTION OF THE LIGHTING CIRCUIT IN
THE AREA.
ELECTRICAL BOXES INSTALLED IN FIRE RATED WALLS SHALL MAINTAIN THE INTEGRITY OF THE
RATED WALL.
SUPPORT ALL VERTICAL RACEWAY PER NEC TABLE 300.19(A).
MAKE ELECTRICAL CONNECTIONS TO ELECTRIC WATER COOLERS FROM GFCI PROTECTED
OUTLET IN WALL BEHIND COOLER HOUSING. THE OUTLET AND CORD SHALL NOT BE VISIBLE
FROM PUBLIC VIEW.
COORDINATE WITH CUTSHEETS OF ALL EQUIPMENT TO BE INSTALLED AND PROVIDE
ADDITIONAL CIRCUITS FOR CONTROLS IF REQUIRED BY MANUFACTURER.
FINAL COLOR, FINISH AND OTHER AESTHETIC PORTIONS OF ALL DEVICES SHALL BE
COORDINATED WITH ARCHITECT OR OWNER'S REPRESENTATIVE. THIS SET OF DRAWINGS
DOES NOT SUPERCEDE ARCHITECTURAL OR INTERIOR DOCUMENTS.
ALL EXPOSED HORIZONTAL RUNS OF CONDUITS SHALL BE EITHER PARALLEL OR
PERPENDICULAR TO EXTERIOR WALLS.
PROVIDE PLENUM RATED CABLES IF THE CABLES ARE EXPOSED AND ROUTED THROUGH
PLENUM.
FIRE ALARM ANNUNCIATOR
PANEL
GROUND FAULT CIRCUIT
INTERRUPTER
GROUND
CABLE TV TERMINAL
BACKBOARD
6" ABOVE COUNTER SPACE OR
42" AFF
HOME RUN WITH WIRE TICKS. XX - PANEL
DESIGNATION, # - CIRCUIT DESIGNATION. WIRE
TICKS - (1) NEUTRAL , (3) HOT & (1) GROUND
FIRE ALARM NOTIFICATION DEVICE. AUDIO AND
VISUAL.
ELECTRICAL PANELBOARD. REFER TO
PANELBOARD SCHEDULE.
FUSED DISCONNECT SWITCH. SUBSCRIPT: AMP / #
OF POLES / ENCLOSURE / FUSE
DISCONNECT SWITCH. SUBSCRIPT: AMP / # OF
POLES / ENCLOSURE
TELEPHONE OUTLET. SUBSCRIPT: F - FIREMAN'S
PHONE, H - HOUSE PHONE, P - PAY PHONE
SWITCH - WALL MTD, INTEGRAL OCCUPANCY
SENSOR
JUNCTION BOX FLUSH IN FINSHED FLOOR WITH
COVER. SIZE PER NEC.
JUNCTION BOX FLUSH IN CEILING WITH COVER.
SIZE PER NEC.
JUNCTION BOX FLUSH IN WALL WITH COVER. SIZE
PER NEC.
SPECIAL RECEPTACLE, CONFIGURATION AND
ELECTRICAL CHARACTERISTIC AS NOTED ON DWG
QUADRAPLEX RECEPTACLE, 120V, 20A, NEMA
5-20R
QUADRAPLEX RECEPTACLE, 120V, 20A, NEMA
5-20R
42" AFF OR 6" ABOVE
COUNTER TOP
42" AFF OR 6" ABOVE
COUNTER TOP
FLUSH WITH FINISHED
FLOOR
FLUSH WITH FINISHED
FLOOR
42" AFF OR 6" ABOVE
COUNTER TOP
FLUSH WITH FINISHED
FLOOR
42" AFF OR 6" ABOVE
COUNTER TOP
42" AFF OR 6" ABOVE
COUNTER TOP
AS INDICATED ON
DWG
AS INDICATED ON
DWG
SURFACE MOUNTED
ON WALL
SURFACE MOUNTED
ON WALL
TYPICAL MOUNTING HEIGHT
UNLESS NOTED OTHERWISE
SURGE PROTECTIVE DEVICE
CONSTRUCTION
FOR
03/28/2024
ONE-LINE DIAGRAM
PANEL A
208/120V 2P 3W
BUS AMPS: 60
MAIN: MLO
DEMAND KVA: 4.56
3/4"C, 2#6, #6N, #8G
M
UTILITY
CIRCUIT DESCRIPTION
LOAD
KVABKR
CKT
#
CKT
KVA CIRCUIT DESCRIPTIONBKR#
LOADCKTCKT
NOTE
NEUTRAL
BUS AMPS
VOLTSPanel AIC
MAIN BKR
LUGSFED FROM
MOUNTING
ROOM
STANDARD
MLO
22,000
60
208/120V 2P 3W
FLUSHAUTILITY 100%
a 2120/1 20/10.3 0.3
b 4320/1 20/10.3 0.2
a 6520/1 20/11.0 0.0
b 8720/1 20/11.9 0.0
a 10920/1 20/10.0 0.0
CONN
KVA
CONN
KVA
CALC
KVA
CALC
KVA
LIGHTING 0.8 1.0 (125%)
RECEPTACLES 0.2 0.2 (50%>10)
CONTINUOUS 1.9 2.4 (125%)
NONCONTINUOUS 1.0 1.0 (100%)
TOTAL LOAD 4.6
BALANCED LOAD 21.9 A
PHASE A 78.4%
PHASE B 122%
LIGHTING
LIGHTING
TEL BACKBOARD
GATE
SPACE
LIGHTING
RECEPTACLE
SPACE
SPACE
SPACE
LUMINAIRE SCHEDULE
CALLOUT SYMBOL LAMP DESCRIPTION MODEL VOLTS
A (1) 260W LED FLOOD LIGHT DUKE ENERGY PROGRESS
FLOODLIGHT LED
120V 1P 2W
31
0
M
E
T
R
O
C
I
R
C
L
E
Wi
l
m
i
n
g
t
o
n
,
N
C
2
8
4
0
8
SHEET NUMBER:
11.16.23
SHEET NAME:
NOT FOR
CONSTRUCTION
DRAWN BY:
CHECKED BY:
DATE DESCRIPTION
11/16/2023
ISSUE / REVISIONS:
PERMIT SET
AN
RD
5335 W 48th Ave Suite 103
Denver, CO 80212
720.779.3556
PROJECT # 323082
N O R T H C AR LI
N
A
O
12/15/2023 REVISION 1
SITE PLAN
E-2
03/28/2024
CONSTRUCTION
FOR
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
A
A
A
1
COORDINATE EXACT LOCATION OF PANEL A WITH ARCHITECT/CIVIL.
POWER FOR TELEPHONE TERMINAL BOARD. ROUTE (2) 2"C FROM TELEPHONE UTILITY
DEMARCATION POINT WITH PULL STRING. COORDINATE EXACT LOCATION WITH
ARCH/CIVIL PRIOR TO ROUGH-IN.
POWER FOR GATE. COORDINATE EXACT LOCATION WITH ARCH/CIVIL PRIOR TO
ROUGH-IN.
KEYNOTES
1
ALL RECEPTACLES SHALL BE GROUNDED AS REQUIRED BY ARTICLE 250-146.
GENERAL NOTES
METER
WP
GF
TTB
A
A-1
#10
A-2
#10
A-3
#10
A-4A-5
2
J
GATE
A-7
#10
2
3
3
31
0
M
E
T
R
O
C
I
R
C
L
E
Wi
l
m
i
n
g
t
o
n
,
N
C
2
8
4
0
8
SHEET NUMBER:
11.16.23
SHEET NAME:
NOT FOR
CONSTRUCTION
DRAWN BY:
CHECKED BY:
DATE DESCRIPTION
11/16/2023
ISSUE / REVISIONS:
PERMIT SET
AN
RD
5335 W 48th Ave Suite 103
Denver, CO 80212
720.779.3556
PROJECT # 323082
N O R T H C AR LI
N
A
O
12/15/2023 REVISION 1
SITE PLAN
E-31
E-3
SITE PLAN
1" = 30'-0"
03/28/2024
CONSTRUCTION
FOR
GENERAL REQUIREMENTS
APPLICABLE REQUIREMENTS OF GENERAL REQUIREMENTS/PROVISIONS SHALL BE CONSIDERED A
PART OF THIS SECTION AND SHALL HAVE THE SAME FORCE AS IF PRINTED HEREIN FULL. IN
ADDITION, ALL INFORMATION RELATED TO COMMUNICATIONS INFRASTRUCTURE THAT IS
DOCUMENTED IN THE ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL
DRAWINGS/DOCUMENTS SHALL BE INCLUDED AS PART OF THE COMMUNICATIONS DOCUMENTS
ALL WORK SHALL BE IN ACCORDANCE WITH THE FOLLOWING:
2020 NEC WITH KY AMENDMENTS
ANSI
NEMA
TIA
BICSI
EIA
IEEE
UL
ASA
FCC
OSHA
ASTM
ADA
LOCAL CITY AND COUNTY ORDINANCES GOVERNING ELECTRICAL WORK
IN THE EVENT OF CONFLICTS, THE MORE STRINGENT PROVISIONS SHALL APPLY.
THE WORK TO BE DONE UNDER THIS SECTION OF THE SPECIFICATIONS SHALL INCLUDE
FURNISHING LABOR, MATERIAL, EQUIPMENT AND TOOLS REQUIRED FOR THE COMPLETE
INSTALLATION OF THE WORK INDICATED ON THE DRAWINGS OR AS SPECIFIED HERE.
ALL MATERIALS, OBVIOUSLY A PART OF THE COMMUNICATIONS INFRASTRUCTURE AND
NECESSARY TO ITS PROPER OPERATION, BUT NOT SPECIFICALLY MENTIONED OR SHOWN ON
THE DRAWINGS, SHALL BE FURNISHED AND INSTALLED WITHOUT ADDITIONAL CHARGE.
THE DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY TO EACH OTHER AND WHAT IS
CALLED FOR BY ONE SHALL BE AS BINDING AS IF CALLED FOR BY BOTH. IF A DISCREPANCY
EXISTS BETWEEN THE DRAWING AND SPECIFICATIONS, THE HIGHER COST SHALL BE INCLUDED,
AND THE ENGINEER SHALL BE NOTIFIED OF THE DISCREPANCY.
THE COMMUNICATIONS INFRASTRUCTURE INSTALLED AND WORK PERFORMED SHALL INCLUDE
BUT NOT NECESSARILY BE LIMITED TO:
STRUCTURED CABLING INFRASTRUCTURE
COMMUNICATIONS CONDUITS, RACEWAYS, CABLE TRAY, RACKS, CABINETS AND EQUIPMENT
MOUNTING BOARDS
GROUNDING AND BONDING
UNDERGROUND RACEWAY EXCAVATION, BACKFILL, AND COMPACTION
CONCRETE WORK FOR DUCT BANKS, MAINTENANCE HOLES, HANDHOLES, VAULTS AND
RESTORATION (WHERE APPLICABLE)
DRAWINGS ARE GENERALLY DIAGRAMMATIC AND SHOW THE ARRANGEMENT AND LOCATION OF
PATHWAYS, OUTLETS, SUPPORT STRUCTURES AND EQUIPMENT. THE CONTRACTOR SHALL
CAREFULLY INVESTIGATE THE STRUCTURAL AND FINISH CONDITIONS AFFECTING HIS WORK AND
ARRANGE HIS WORK ACCORDINGLY. SHOULD CONDITIONS ON THE JOB MAKE IT NECESSARY
TO MAKE ADJUSTMENTS TO PATHWAYS OR MATERIALS, THE CONTRACTOR SHALL ADVISE THE
ENGINEER AND SECURE APPROVAL BEFORE PROCEEDING WITH SUCH WORK. MATERIALS,
EQUIPMENT OR LABOR NOT INDICATED BUT WHICH CAN BE REASONABLY INFERRED TO BE
NECESSARY FOR A COMPLETE INSTALLATION SHALL BE PROVIDED. DRAWINGS AND
SPECIFICATIONS DO NOT UNDERTAKE TO INDICATE EVERY ITEM OF MATERIAL, EQUIPMENT, OR
LABOR REQUIRED TO PRODUCE A COMPLETE AND PROPERLY OPERATING INSTALLATION.
THE LOCATION OF EQUIPMENT, SUPPORT STRUCTURES, OUTLETS, AND SIMILAR DEVICES
SHOWN ON THE DRAWINGS ARE APPROXIMATE ONLY. DO NOT SCALE DRAWINGS. OBTAIN
LAYOUT DIMENSIONS FOR EQUIPMENT FROM ARCHITECTURAL PLANS UNLESS INDICATED ON
COMMUNICATIONS PLANS.
SCHEMATIC DIAGRAMS SHOWN ON THE DRAWINGS INDICATE THE REQUIRED FUNCTIONS ONLY.
THE TECHNOLOGY OF A PARTICULAR MANUFACTURER MAY BE USED TO ACCOMPLISH THE
FUNCTIONS INDICATED WITHOUT EXACT ADHERENCE TO THE SCHEMATIC DRAWINGS SHOWN.
ADDITIONAL LABOR AND MATERIALS REQUIRED FOR SUCH DEVIATIONS SHALL BE FURNISHED AT
THE CONTRACTOR'S EXPENSE.
EQUIPMENT AND MATERIALS REQUIRED FOR INSTALLATION UNDER THESE SPECIFICATIONS
SHALL BE THE CURRENT MODEL AND NEW (LESS THAN ONE [1] YEAR FROM THE DATE OF
MANUFACTURE), UNUSED AND WITHOUT BLEMISH OR DEFECT.
THE CONTRACTOR SHALL HAVE TOTAL RESPONSIBILITY FOR THE COORDINATION AND
INSTALLATION OF THE WORK SHOWN AND DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS.
THE CONTRACTOR SHALL BE A COMPANY SPECIALIZING IN THE DESIGN, FABRICATION AND
INSTALLATION OF INTEGRATED COMMUNICATIONS SYSTEMS.
COMMUNICATIONS SYSTEMS SPECIFIED SHALL BE INSTALLED UNDER THE DIRECTION OF A
QUALIFIED CONTRACTOR.
THE CONTRACTOR SHALL COORDINATE COMMUNICATIONS WORK WITH THAT OF OTHER
SECTIONS AS REQUIRED TO ENSURE THAT THE ENTIRE COMMUNICATIONS WORK WILL BE
CARRIED OUT IN AN ORDERLY, COMPLETE AND COORDINATED FASHION.
OBTAIN ALL PERMITS AND INSPECTIONS FOR THE INSTALLATION OF THIS WORK AND PAY ALL
CHARGES INCIDENT THERETO. DELIVER TO THE OWNER ALL CERTIFICATES OF SAID INSPECTION
ISSUED BY AUTHORITIES HAVING JURISDICTION.
PRODUCT SUBSTITUTIONS ARE NOT ALLOWED UNLESS NOTED AS, “OR APPROVED EQUAL (BY
OWNER).” THE ENGINEER'S DECISION AS TO WHETHER THE SUBMITTED EQUIPMENT IS
ACCEPTABLE SHALL BE FINAL AND BINDING.
ALL MATERIALS USED IN THIS WORK SHALL BE NEW AND SHALL BEAR THE INSPECTION LABEL OF
UNDERWRITERS' LABORATORIES INC. OR CERTIFICATION BY OTHER RECOGNIZED LABORATORY.
DURING CONSTRUCTION, AND PRIOR TO OWNER ACCEPTANCE OF THE BUILDING, REMOVE
FROM THE PREMISES AND DISPOSE OF PACKING MATERIAL AND DEBRIS CAUSED BY
COMMUNICATIONS WORK. REMOVE DUST AND DEBRIS FROM INTERIORS AND EXTERIORS OF
ELECTRICAL EQUIPMENT. CLEAN ACCESSIBLE CURRENT CARRYING ELEMENTS PRIOR TO BEING
ENERGIZED.
UPON COMPLETION OF THE WORK, REMOVE EXCESS DEBRIS, MATERIALS, EQUIPMENT,
APPARATUS, TOOLS AND SIMILAR ITEMS. LEAVE THE PREMISES CLEAN, NEAT AND ORDERLY.
SYSTEMS SHALL BE COMPLETE AND OPERATIONAL AND CONTROLS SHALL BE SET AND
CALIBRATED. TESTING, START-UP AND CLEANING WORK SHALL BE COMPLETE.
SPECIFICATIONS
FIRESTOPPING FOR COMMUNICATIONS SYSTEMS
APPROVED FIRESTOPPING MANUFACTURER(S):
STI FIRESTOP PRODUCTS (FIRESTOP DEVICES, PUTTIES, CAULKS, SEALANTS, ETC.)
HILTI (FIRESTOP DEVICES, PUTTIES, CAULKS, SEALANTS, ETC.)
3M FIRESTOP PRODUCTS (FIRESTOP DEVICES, PUTTIES, CAULKS, SEALANTS, ETC.)
FLAMESTOPPER THRU-WALL FITTING - WIREMOLD COMPANY (FIRESTOP DEVICES)
UNIQUE FIRESTOP PRODUCTS (FIRESTOP DEVICES)
SEALANTS: INTUMESCENT FIRESTOP SEALANTS AND CAULKS, LATEX FIRESTOP SEALANT,
ACRYLIC WATER-BASED SEALANT, SILICONE FIRESTOP SEALANTS AND CAULKS, FIRESTOP
PUTTY, FIRESTOP COLLARS, FIRESTOP SLEEVES, WRAP STRIPS, 2-PART SILICONE FIRESTOP
FOAM, FIRESTOP MORTAR, FIRESTOP PILLOWS, ELASTOMERIC SPRAY
FIRESTOP DEVICES: THRU-WALL FITTING, THREADED FIRESTOP DEVICE, SMOOTH FIRESTOP
DEVICE, SPLIT-SLEEVE FIRESTOP DEVICE, FIRE RATED CABLE PATHWAY
UL CLASSIFICATION: THRU-WALL FITTING - THE FIRESTOP DEVICE FOR USE IN
THROUGH-PENETRATION FIRESTOP SYSTEMS SHALL HAVE BEEN EXAMINED AND TESTED BY
UNDERWRITERS LABORATORIES INC. TO UL1479 (ASTM E 814) AND BEAR THE U.S. AND
CANADIAN UL CLASSIFICATION MARK. THREADED, SMOOTH AND SPLIT-SLEEVE FIRESTOP
DEVICES -FIRESTOPPING SEALANTS AND DEVICES SHALL BE USED TOGETHER AS A FIRESTOP
SYSTEM.
ALL FIRESTOP SYSTEMS SHALL BEAR A UL CLASSIFICATION SYSTEM NUMBER.
GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS
A LICENSED ELECTRICAL CONTRACTOR SHALL PERFORM INSTALLATION AND TERMINATION OF
THE MAIN BONDING CONDUCTOR TO THE BUILDING SERVICE ENTRANCE GROUND.
APPROVED EQUIPMENT GROUNDING CONDUCTOR MANUFACTURER(S): SOUTHWIRE, BELDEN
APPROVED GROUNDING LUG MANUFACTURER(S): BURNDY, THOMAS & BETTS, CHATSWORTH
PRODUCTS, INC.
CONDUCTOR SHALL BE TYPE THHN COPPER CONDUCTORS, INSULATED WITH HEAT AND
MOISTURE RESISTANT PVC OVER WHICH A UL LISTED JACKET IS APPLIED.
ALL RACKS, CABINETS, METALLIC ENCLOSURES, CONDUITS, METALLIC BACKBOARDS, CABLE
SHEATHS, METALLIC STRENGTH MEMBERS, SPLICE CASES, CABLE TRAYS, ETC. ENTERING OR
RESIDING IN THE MC/IC/TC SHALL BE GROUNDED TO THE RESPECTIVE BUSBAR USING A
MINIMUM #6 AWG STRANDED COPPER BONDING CONDUCTOR AND COMPRESSION LUGS.
PATHWAYS FOR COMMUNICATIONS SYSTEMS
MANUFACTURERS: SQUARE D, B-LINE, ALLIED TUBE & CONDUIT, HOFFMAN, CARLON
ELECTRICAL, WIREMOLD.
OUTDOORS EXPOSED: RIGID STEEL.
OUTDOORS CONCEALED ABOVE GROUND: RIGID STEEL.
OUTDOORS UNDERGROUND: TYPE EPC-40-PVC
OUTDOORS CONNECTION TO VIBRATING EQUIPMENT (INCLUDING TRANSFORMERS AND MOTOR
DRIVEN EQUIPMENT): LFMC.
BOXES AND ENCLOSURES ABOVE GROUND: NEMA 3R UNLESS NOTED OTHERWISE ON PLANS.
INDOORS EXPOSED NOT SUBJECT TO PHYSICAL DAMAGE: EMT.
INDOORS EXPOSED NOT SUBJECT TO SEVERE PHYSICAL DAMAGE: EMT.
INDOORS EXPOSED SUBJECT TO SEVERE PHYSICAL DAMAGE: RIGID STEEL CONDUIT.
INDOORS CONCEALED IN CEILINGS AND INTERIOR WALLS AND PARTITIONS: EMT.
INDOORS CONNECTION TO VIBRATING EQUIPMENT: FMC, EXCEPT USE LFMC IN DAMP OR WET
LOCATIONS.
INDOORS DAMP OR WET LOCATIONS: IMC.
INDOORS LOW-VOLTAGE CABLES: EMT.
LEAVE ALL EMPTY CONDUITS WITH A 200 POUND TEST NYLON CORD PULL LINE.
EXACT LOCATIONS OF THE OUTLET BOXES SHALL BE COORDINATED WITH THE ELECTRICAL
CONTRACTOR AND OTHER TRADES. NON-METALLIC COMMUNICATIONS OUTLET BOXES SHALL
NOT BE USED. THE APPROXIMATE LOCATIONS OF THE OUTLETS ARE INDICATED ON THE
DRAWINGS. THE EXACT LOCATIONS OF OUTLETS SHALL BE DETERMINED AT THE BUILDING. THE
RIGHT IS RESERVED TO CHANGE, WITHOUT ADDITIONAL COST, THE EXACT LOCATION OF ANY
OUTLET, A MAXIMUM OF 10' BEFORE IT IS PERMANENTLY INSTALLED.
UNDERGROUND DUCTS, RACEWAYS, AND HANDHOLES FOR COMMUNICATIONS SYSTEMS
APPROVED MAINTENANCE HOLE/HANDHOLE MANUFACTURER(S): QUAZITE, PENCELL, OLD CASTLE
MAINTENANCE HOLES SHALL BE PRE-CAST OR CAST IN PLACE CONCRETE WITH A STRENGTH OF
3,500 PSI AT 28 DAYS, AND STEEL REINFORCED. MAINTENANCE HOLES SHALL INCLUDE A CAST
IRON FRAME WITH COVER, A HOT DIPPED GALVANIZED STEEL LADDER, AND HOT DIPPED
GALVANIZED PULLING EYES EMBEDDED IN THE CONCRETE OPPOSITE EACH DUCT ENTRANCE AND
IN THE FLOOR BENEATH THE COVER. MAINTENANCE HOLES SHALL BE EQUIPPED WITH
GROUNDING BUSBAR. MAINTENANCE HOLES SHALL BE EQUIPPED WITH RACKING FOR CABLE
STORAGE. GROUND SPLICES AND CONNECTIONS AT MAINTENANCE HOLES SHALL BE
EXOTHERMIC WELDS, COPPER OR BRONZE COMPRESSION GROUND FITTINGS, OR BOLTED
COMPRESSION RING LUGS. THE COVER FOR MAINTENANCE HOLES SHALL HAVE THE LETTERING,
“COMMUNICATIONS.”
HANDHOLES SHALL BE NON-CONDUCTIVE AND SHALL NOT REQUIRE GROUNDING FOR SAFETY.
HANDHOLES SHALL BE UNAFFECTED BY FREEZE/THAW AND RESISTANT TO SUNLIGHT AND
CHEMICALS. HANDHOLES SHALL BE PRE-CAST POLYMER CONCRETE, HEAVY DUTY RATED AND
BOTTOMLESS. HANDHOLES SHALL BE EQUIPPED WITH RACKING FOR CABLE STORAGE.
HANDHOLES SHALL HAVE THE WORD “COMMUNICATIONS” MOLDED IN THE COVER BY THE
MANUFACTURER. THE COVER SHALL BE ATTACHED WITH PENTA-HEAD STAINLESS STEEL BOLTS.
HANDHOLES SHALL BE ABLE TO WITHSTAND 10,000 LBS MINIMUM. SEE DRAWINGS FOR
HANDHOLE LOCATIONS.
MAINTENANCE HOLES/HANDHOLES SHALL BE INSTALLED ON A BASE OF PEA GRAVEL AT LEAST 12
INCHES DEEP.
TOPS OF MAINTENANCE HOLES/HANDHOLES SHALL BE LEVEL WITH THE EXISTING GRADE.
DUCTS SHOULD ENTER AS PERPENDICULAR TO THE WALL SURFACE AS POSSIBLE.
MAINTENANCE HOLES SHALL BE GROUNDED WITH FOUR 3/4 INCH DIAMETER BY 8 FOOT LONG
GROUND RODS, ONE DRIVEN INSIDE OF THE MAINTENANCE HOLE AT EACH CORNER. CONNECT
THE GROUND RODS AND ANY DUCT BANK GROUND CONDUCTORS TOGETHER WITH A NO. 4/0
AWG BARE, STRANDED COPPER GROUND WIRE LOOP. A NO. 2 AWG BARE STRANDED COPPER
PIGTAIL FROM THE GROUND WIRE LOOP SHALL BE USED TO GROUND THE MAINTENANCE HOLE
COVER FRAME, LADDER SUPPORT BRACKET, ANY METALLIC CONCRETE INSERTS AND METALLIC
CABLE RACKS, AND THE SHIELDS OF ANY CABLES THAT ARE SPLICED IN THE MAINTENANCE
HOLE.
SPECIFICATIONS
NO CONDUIT RUN TO CONTAIN MORE THAN TWO (2) 90 DEGREE BENDS BETWEEN PULLING
POINTS. PROVIDE JUNCTION BOXES WHERE REQUIRED TO MAINTAIN (2) 90 DEGREE BEND RULE.
ALL WALL AND FLOOR PENETRATIONS TO BE SEALED AND FIREPROOFED. CONDUIT ROUTING
PATHS TO BE COORDINATED WITH ALL OTHER SYSTEMS.
ALL CABLES TO BE ROUTED DIRECT TO EQUIPMENT ROOMS WITHOUT SPLICES. NO JUNCTIONS
OR SPLICES IN CABLES ARE ACCEPTABLE.
ALL CONDUITS ROUTED BELOW GRADE TO BE SEALED TO PREVENT WATER INFILTRATION INTO
EQUIPMENT ROOMS.
ALL CONDUITS ROUTED BELOW GRADE TO BE SCHEDULE 40 PVC. CONDUIT ROUTED ABOVE
GRADE TO BE EMT.
NO ELECTRONIC DEVICES ARE ALLOWED TO BE INSTALLED IN HANDHOLE BOXES.
ALL TERMINATIONS AND SPLICES IN HANDHOLE BOXES MUST BE WET RATED.
ALL CONDUITS ARE TO INCLUDE PULL STRINGS INSTALLED WITHIN.
GENERAL NOTES
31
0
M
E
T
R
O
C
I
R
C
L
E
Wi
l
m
i
n
g
t
o
n
,
N
C
2
8
4
0
8
SHEET NUMBER:
11.16.23
SHEET NAME:
CONSTRUCTION
DRAWN BY:
CHECKED BY:
DATE DESCRIPTION
03/28/2024
ISSUE / REVISIONS:
PERMIT SET
FOR
5335 W 48th Ave Suite 103
Denver, CO 80212
720.779.3556
PROJECT # 323082
N O R T H C AR LI
N
A
O
JS
JS
SITE PLAN
LV-1
WEATHERPROOF
ENCLOSURE
PAN/TILT DRIVE
6" DIA GALVANIZED STEEL POLE
WITH FINISH TO MATCH
LIGHTING FIXTURE POLES
1" FLEXIBLE CONDUIT INSIDE
POLE FOR VIDEO CABLES
4 ANCHOR BOLTS
1/2" x 4'-0" LONG
GRADE
1" PVC FOR VIDEO CABLES
CONCRETE BASE
1" PVC FOR 120V. POWER
WIRING
NOTE:
CAMERA, ENCLOSURE, PAN/TILT
& WIRING UNDER DIVISION 17.
4'-6"
24"
18"
ROUND
18"
6"
14'-0"
SEALTITE CONDUIT
TO CAMERA
4'
-
0
"
2'-0"
CURB/FINISNED GROUND
1
1
CR
KP
4
5
4
4
E
6
2
3
HH
SECURITY GATE
VEHICLE PRESENSE LOOP (PROVIDED
BYGATE CONTRACTOR)
VEHICLE SAFTY/CLOSE LOOP
(PROVIDEDBY GATE CONTRACTOR)
VEHICLE EXIT LOOP (PROVIDED BY
GATECONTRACTOR)
31
0
M
E
T
R
O
C
I
R
C
L
E
Wi
l
m
i
n
g
t
o
n
,
N
C
2
8
4
0
8
SHEET NUMBER:
11.16.23
SHEET NAME:
CONSTRUCTION
DRAWN BY:
CHECKED BY:
DATE DESCRIPTION
03/28/2024
ISSUE / REVISIONS:
PERMIT SET
FOR
5335 W 48th Ave Suite 103
Denver, CO 80212
720.779.3556
PROJECT # 323082
N O R T H C AR LI
N
A
O
JS
JS
DETAILS
LV-2
1
L-2
POLE MOUNT CAMERA
3/8" = 1'-0"
PROVIDE NEMA 4 PULL BOX FOR LOW VOLTAGE SYSTEMS. PROVIDE SEPARATE 3/4"
CONDUITS FOR LOW VOLTAGE SYSTEMS AND 120 VAC POWER. ALL CONDUIT ROUTED
ABOVE GRADE TO BE EMT. PVC ACCEPTABLE BELOW GRADE.
PROVIDE AND INSTALL GATE CONTROL CIRCUIT & INTERFACE WITH GATE OPERATORS AND
GATE ARMS PROVIDED BY OTHERS. WIRE GATE POSITIONSWITCH TO MONITOR GATE
POSITION. VEHICLE GATE TO BE CONTROLLED BY SECURITY AND ACCESS CONTROL
SYSTEM. COORDINATE WITH ELECTRICAL CONTRACTOR FOR PLACEMENT OF 120 VAC/20
AMP CIRCUITS FOR USE BY GATE CONTROLS CONTRACTOR. CONTROL CIRCUIT FOR GATE
CONTROLLER TO BE ROUTED TO SECURITY & ACCESS CONTROL SYSTEM.
PROVIDE GOOSE NECK PEDESTAL. SEE INSTALLATION DETAIL. MOUNT INTERCOM AND
CARD READER ON PEDESTAL. CARDREADER TO BE ROUTED TO BUILDING SECURITY &
ACCESS CONTROL SYSTEM. INTERCOM STATION TO BE TELEPHONE-BASED AND WIRED
TO TELECOM ROOM. INSTALL CONCRETE BASE TO MANUFACTURERS' SPECIFICATIONS
ASREQUIRED.
PROVIDE ALL LOOPS AS IDENTIFIED. FOLLOW MANUFACTURERINSTALLATION
INSTRUCTIONS FOR CUTTING IN LOOPS AND PROPER CABLE CONFIGURE LOOPS TO
ALLOW FOR ONLY ONE VEHICLE ENTRANCE PER CYCLE.
FOR PROTECTION OF PEDESTAL AND GATE, INSTALL BOLLARDS. BOLLARDSTO BE 6”
DIAMETER ALL WELDED STEEL GUARDS. BOLLARDS TO BE PROVIDEDWITH 8” X 8”
MOUNTING PLATES WITH 1” HOLES PRE-DRILLED ON 1” CENTERS FROM PLATE EDGE.
BOLLARDS TO BE PAINTED SAFETY YELLOW AND EXTEND 36” ABOVE GRADE. INSTALL
CONCRETE BASE TO MANUFACTURERS' SPECIFICATIONS AS REQUIRED.
INSTALL ONE (1) -1" CONDUIT FROM VEHICLE GATE ENCLOSURE TO CARDREADER/
INTERCOM STATION PEDESTAL. INSTALL TWO (2) - 1" CONDUITS BETWEEN GATE
ENCLOSURES.
KEY NOTES
1
2
3
4
5
6
2
L-2
MULLION MOUNT CARD READER
3/8" = 1'-0"
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
OH
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
HH
MAIN SITE HANDHOLE TO BE USED FOR
TELECOMMUNICATIONS CABLES ONLY.
3
21
4
KP
5
6
6
6
7
31
0
M
E
T
R
O
C
I
R
C
L
E
Wi
l
m
i
n
g
t
o
n
,
N
C
2
8
4
0
8
SHEET NUMBER:
11.16.23
SHEET NAME:
CONSTRUCTION
DRAWN BY:
CHECKED BY:
DATE DESCRIPTION
03/28/2024
ISSUE / REVISIONS:
PERMIT SET
FOR
5335 W 48th Ave Suite 103
Denver, CO 80212
720.779.3556
PROJECT # 323082
N O R T H C AR LI
N
A
O
JS
JS
SITE PLAN
LV-31
L-3
SITE PLAN
1" = 30'-0"
CONTRACTOR TO PROVIDE AND INSTALL ONE (1) 24”X 36”X 26“QUAZITE HAND HOLE
(SITE JUNCTION BOX) WITH BOLT ON COVER. COORDINATE LOCATION WITH OTHER
TRADES AND WITH TELECOM SERVICE PROVIDER.
CONTRACTOR TO INSTALL TWO (2) -4" SLEEVES IN HANDHOLE FOR SERVICE PROVIDER
USE. SEAL SLEEVES AFTER INSTALLATION.
CONTRACTOR TO INSTALL, BELOW GRADE, TWO (2) 40 PVC CONDUITS BETWEEN HAND
HOLE AND SITE TELECOM CLOSET LOCATION (TO BE DETERMINED). INSTALL CONDUITS
PER CURRENT NEC CODES. USE LONG RADIUS 90 DEGREE ELBOWS TO TURN CONDUITS
UP INTO MDF/IDF ROOM. CONDUITS TO TURN-UP ~3”ABOVE GRADE SLAB. ALL
CONDUIT OPENINGS ARE TO BE SEALED. INSTALL IN ONE CONDUIT TWO (2) -4”, THREE
CELL, MAXCELL INNER DUCT SYSTEM FOR FUTURE USE.
CONTRACTOR TO INSTALL, BELOW GRADE, TWO (2) 40 PVC CONDUITS BETWEEN HAND
HOLE AND UTILITY SERVICE LINE LOCATION. COORDINATE UTILITY SERVICE LINE LOCATION
WITH CIVIL DRAWINGS. INSTALL CONDUITS PER CURRENT NEC CODES. USE LONG RADIUS
90 DEGREE ELBOWS TO TURN CONDUITS UP INTO MDF/IDF ROOM. CONDUITS TO
TURN-UP ~3”ABOVE GRADE SLAB. ALL CONDUIT OPENINGS ARE TO BE SEALED. INSTALL
IN ONE CONDUIT TWO (2) -4”, THREE CELL, MAXCELL INNER DUCT SYSTEM FOR FUTURE
USE.
CONTRACTOR TO INSTALL CARD READER/KEYPAD ON MULLION. EXACT LOCATION TO BE
DETERMINED BY LOCATION OF GATE ON SITE.
CONTRACTOR TO MOUNT CAMERAS ON LIGHT POLES AS INDICATED BY OWNER.
CAMERAS TO BE ADJUSTED AND FOCUSED BY CONTRACTOR TO OWNERS APPROVAL.
POLES TO BE INSTALLED IN ISLAND CURB.
CONTRACTOR TO ADJUST CAMERA TO FIT OWNERS NEED OF CAPTURING LICENSE PLATES.
CAMERA TO BE MOUNTED ON LIGHT POLE AS INDICATED BY OWNER.
KEY NOTES
1
2
3
4
5
6
7