HomeMy WebLinkAboutElectrical Permit31 0 M E T R O C I R C L E Wi l m i n g t o n , N C 2 8 4 0 8 SHEET NUMBER: 11.16.23 SHEET NAME: NOT FOR CONSTRUCTION DRAWN BY: CHECKED BY: DATE DESCRIPTION 11/16/2023 ISSUE / REVISIONS: PERMIT SET AN RD 5335 W 48th Ave Suite 103 Denver, CO 80212 720.779.3556 PROJECT # 323082 N O R T H C AR LI N A O 12/15/2023 REVISION 1 SITE PLAN E-1 SPECIFICATIONS SPECIFICATIONS ABBREVIATIONS AC AMP FUSEAF ABOVE FINISHED FLOORAFF BELOW FINISHED CEILINGBFC BREAKERBKR CONNECTED OR CONNECTIONCONN CTB DOWNDN EMPTY CONDUITEC ELECTRICALELEC FIRE ALARM CONTROL PANELFACP FAA G OR GRND GFCI OR GF ISOLATED GROUNDIG SHORT CIRCUIT CURRENTISC LIGHTINGLTG MOUNTEDMTD NATIONAL ELECTRICAL CODENEC PANELPNL RECEPTACLERECPT TELEPHONETELTELEPHONE TTB TELEVISIONTV SPD TYPICALTYP TRANSFORMERXFMR UNDERGROUNDUG WEATHERPROOFWP NEUTRALN COPPERCU ALUMINUMAL CONDUITCND NIGHT LIGHTNL TELEPHONE TERMINAL BOARD EQUIPMENT AS NOTED ON DRAWING. DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R 18" AFF DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R 18" AFF AC 18" AFF IN CEILINGJ J 42" AFFSSWITCH MOTORM SYMBOLS DESCRIPTION XX-# LEGEND 42" AFFSWITCH - 3 WAY DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R DUPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R IN CEILING 18" AFF TELEPHONE OUTLET 18" AFF TELEPHONE / DATA COMBINATION OUTLET 18" AFF TELEPHONE / DATA COMBINATION OUTLET DATA OUTLET DATA OUTLET 18" AFF D TV OUTLET 18" AFF H SMOKE DETECTOR. CEILING / WALL MOUNTEDD H HEAT DETECTOR. CEILING/WALL MOUNTED 80" AFF 80" AFF 80" AFF FIRE ALARM NOTIFICATION DEVICE. AUDIO. FIRE ALARM NOTIFICATION DEVICE. VISUAL. FIRE ALARM INITIATION DEVICE. PULL STATION.42" AFF 42" AFF 42" AFFSWITCH - WALL MTD, LOW VOLTAGE, PILOT LIGHT SWITCH - CEILING MOUNTED OCCUPANCY SENSOROS IN CEILING 42" AFFSWITCH - WALL MTD, DIMMING TELEPHONE / DATA COMBINATION OUTLET J S3 SOS SLV SD / / / ELECTRICAL GENERAL NOTES GENERAL CONTRACTOR SHALL REFER TO ALL RELATED DOCUMENTS, ARCHITECTURAL, STRUCTURAL, CIVIL AND MEP DRAWINGS, AND FULLY UNDERSTAND THE SCOPE OF WORK AND CONDITION OF CONSTRUCTION. THE WORK UNDER THIS SPECIFICATIONS AND DRAWINGS SHALL INCLUDE ALL LABOR. ALL INSTALLATION OF DEVICES AND CONNECTION OF CONDUCTORS SHALL BE PERFORMED BY LICENSED AND SKILLED ELECTRICIAN OR JOURNEYMAN. ALL WORK SHALL BE COMPLETED TO THE SATISFACTION OF THE OWNER. IF ANY PORTION OF THE WORK IS FOUND UNSATISFACTORY BY THE OWNER, IT SHALL BE REMOVED AND REINSTALLED WITHOUT DELAY AT NO COST TO THE OWNER. THE WORK INCLUDES, BUT NOT LIMITED TO: THE COMPLETE ELECTRICAL DISTRIBUTION SYSTEM. ROUGH-IN AND FINAL CONNECTIONS TO ALL DEVICES REQUIRING ELECTRICAL POWER, INCLUDING OWNER PROVIDED EQUIPMENT. LIGHTING CONTROL LIGHTING FIXTURES EACH CONTRACTOR SHALL OBTAIN ALL PERMITS AND INSPECTIONS REQUIRED BY THE REGULATORY AUTHORITIES. ALL FEES RELATED TO OBTAINING PERMITS AND INSPECTION SHALL BE PAID FOR BY EACH CONTRACTOR IN HIS TRADE. ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH LOCAL, COUNTY, STATE, AND NATIONAL ELECTRICAL CODE 2020, SPECIFICATIONS, UTILITY COMPANY REQUIREMENTS AND ALL INDUSTRY STANDARDS. ANY DIFFERENCES IN ABOVE MENTIONED REQUIREMENTS, THE MOST STERN SHALL OVERRULE ALL OTHERS. IN ADDITION TO ABOVE MENTIONED CODES AND SPECIFICATIONS, THE FOLLOWING INDUSTRY STANDARDS SHALL BE COMPLIED IF THEY ARE MORE STRINGENT. IEEE IES IECC 2015 ASHRAE 90.1 NFPA NEMA UL ADA THE MANUFACTURER'S PUBLISHED DIRECTIONS SHALL BE FOLLOWED IN THE DELIVERY, STORAGE, PROTECTION, INSTALLATION AND WIRING OF ALL EQUIPMENT AND MATERIAL. THE DRAWINGS SHOW DIAGRAMMATICALLY THE LOCATIONS OF THE VARIOUS LINES, CONDUITS, FIXTURES, AND EQUIPMENT AND THE METHOD OF CONNECTING AND CONTROLLING THEM. IT IS NOT INTENDED TO SHOW EVERY CONNECTION IN DETAIL AND ALL FITTINGS REQUIRED FOR A COMPLETE SYSTEM. THE SYSTEMS SHALL INCLUDE BUT ARE NOT LIMITED TO THE ITEMS SHOWN ON THE DRAWINGS. EXACT LOCATIONS OF THESE ITEMS SHALL BE DETERMINED BY REFERENCE TO THE GENERAL PLANS AND MEASUREMENTS AT THE BUILDING AND IN COOPERATION WITH THE OTHER SUBCONTRACTORS, AND IN ALL CASES, SHALL BE SUBJECT TO THE APPROVAL OF THE OWNER. THE OWNER RESERVES THE RIGHT TO MAKE ANY REASONABLE CHANGE IN THE LOCATION OF ANY PART OF THIS WORK WITHOUT ADDITIONAL COST TO THE OWNER. CONTRACTOR SHALL SEEK APPROVAL FROM THE OWNER FOR ANY CHANGES TO THE SPECIFICATIONS OR CONTRACT DOCUMENTS. ANY EXCEPTIONS, INCONSISTENCIES AND CONFLICTS IN CONTRACT DOCUMENTS, SPECIFICATIONS AND CONTRACT DOCUMENTS BY OTHER TRADE SHALL BE BROUGHT TO ATTENTION TO THE OWNER PRIOR TO BID. CONTRACTOR SHALL COORDINATE AND VERIFY THE WORK WITH EXISTING CONDITIONS AND THE WORK OF OTHER TRADE PRIOR TO ANY FABRICATIONS OR INSTALLATION. IF THE LAYOUT OF THE DEVICES ON DRAWINGS ARE IMPRACTICAL TO THE CONDITION IN FIELD, CONTRACTOR SHALL NOTIFY THE OWNER IMMEDIATELY PRIOR TO ANY FABRICATION OR INSTALLATION. ELECTRICAL DEVICES ARE INDICATED ON DRAWINGS AT APPROXIMATE LOCATIONS. THE OWNER RESERVE THE RIGHT TO MAKE REASONABLE CHANGES IN LOCATIONS WITHOUT ADDITIONAL COSTS. THE LINES INDICATING BRANCH CIRCUITS DO NOT REPRESENT THE ROUTING OF ELECTRICAL CONDUITS. THEY INDICATE THE LAYOUT AND CONTROL OF CIRCUITS. PRODUCTS AND WORK MATERIALS FURNISHED SHALL BE NEW AND BY STANDARD MANUFACTURERS AND MUST CONFORM TO THE NATIONAL BOARD OF FIRE UNDERWRITER'S REQUIREMENTS AND BEAR THE UNDERWRITER'S LABORATORIES' SEAL OF APPROVAL. LISTED MANUFACTURERS, MODELS, OR CATALOGUE NUMBERS IN PART OR ALL SHALL ENTAIL TO INCLUDE THE PUBLISHED MANUFACTURER'S DESCRIPTION AND SPECIFICATION. CONTRACTOR SHALL NOT INTERPRET THAT THE LISTED MANUFACTURERS IN SPECIFICATIONS OR DRAWINGS TO EXCLUDE ALL OTHER MANUFACTURERS. CONTRACTOR SHALL MAKE CERTAIN THAT ALL EQUIPMENT FIT IN THE SPACE DESIGNATED AND DESIGNED FOR THE SURROUNDINGS IT OCCUPIES. COMPLETE CATALOGUE ILLUSTRATION AND DESCRIPTIONS OF ALL EQUIPMENT SHALL BE SUBMITTED TO THE OWNER PRIOR TO ORDERING ANY EQUIPMENT. ALL HORIZONTAL RUNS OF CONDUITS SHALL BE SUPPORTED BY MEANS OF APPROVED HANGER FROM THE STRUCTURAL CEILING. COORDINATE THE WORK UNDER THIS SECTION WITH ALL OTHER TRADES. CONDUITS AND RACEWAYS: MANUFACTURERS: SQUARE D, B-LINE, ALLIED TUBE & CONDUIT, HOFFMAN, CARLON ELECTRICAL, WIREMOLD. OUTDOORS EXPOSED: RIGID STEEL. OUTDOORS CONCEALED ABOVE GROUND: RIGID STEEL. OUTDOORS UNDERGROUND: TYPE EPC-40-PVC OUTDOORS CONNECTION TO VIBRATING EQUIPMENT (INCLUDING TRANSFORMERS AND MOTOR DRIVEN EQUIPMENT): LFMC. BOXES AND ENCLOSURES ABOVE GROUND: NEMA 3R UNLESS NOTED OTHERWISE ON PLANS. INDOORS EXPOSED NOT SUBJECT TO PHYSICAL DAMAGE: EMT. INDOORS EXPOSED NOT SUBJECT TO SEVERE PHYSICAL DAMAGE: EMT. INDOORS EXPOSED SUBJECT TO SEVERE PHYSICAL DAMAGE: RIGID STEEL CONDUIT. INDOORS CONCEALED IN CEILINGS AND INTERIOR WALLS AND PARTITIONS: EMT. INDOORS CONNECTION TO VIBRATING EQUIPMENT: FMC, EXCEPT USE LFMC IN DAMP OR WET LOCATIONS. INDOORS DAMP OR WET LOCATIONS: IMC. INDOORS LOW-VOLTAGE CABLES: EMT. CONDUCTORS: COPPER CONDUCTORS #10 AND SMALLER: LABELED PER UL 83, TYPE THHN/THWN, SOLID COPPER 600 VOLT INSULATION, UNIFORM COLOR CODED JACKET WITH JACKET DATA. METAL CLAD (TYPE MC) CABLE WHERE INSTALLED IN ACCORDANCE WITH NEC ARTICLE 330. COPPER CONDUCTORS #8 OR LARGER: LABELED PER UL 83, TYPE THHN/THWN, STRANDED COPPER, 600VOLT INSULATION, UNIFORM COLOR CODED JACKET WITH JACKET DATA. ACCEPTABLE MANUFACTURERS OF CONDUCTORS: PIRELLIE SOUTHWIRE AETNA REPUBLIC AFC ENCORE WIRE KERITE CONTRACTOR MAY USE ALUMINUM CONDUCTORS FOR #4 AWG OR LARGER IN THE PLACE OF COPPER CONDUCTORS. CONTRACTOR SHALL REFER TO NEC TABLE 310-16 FOR EQUIVALENT AMPACITY AND SHALL COMPENSATE FOR VOLTAGE DROP. CONTRACTOR SHALL MAKE ADEQUATE ADJUSTMENT TO CONDUIT SIZES INDICATED SHOULD ALTERNATIVE CONDUCTOR INSULATION OR MATERIAL BE UTILIZED. MOLDED CASE CIRCUIT BREAKER: INCLUDE SCHEDULE OF ALL FUSES, RATINGS, TIME COORDINATION DATA, MANUFACTURER'S STANDARD DATA AND TIME-CURRENT CURVES. ALL DATA SHALL BE BASED ON TEST OF STANDARD PRODUCTS. APPROVED MANUFACTURERS: GENERAL ELECTRIC CUTLER HAMMER SQUARE D SIEMENS THERMAL-MAGNETIC BOLT-IN TYPE CIRCUIT BREAKERS WITH QUICK-MAKE, QUICK-BREAK CONTACTS; TRIP-FREE OPERATION WITH OVER-THE-CENTER TOGGLE HANDLE OR NON-REMOVABLE MONOLITHIC TIE-HANDLE. MULTI-POLE BREAKERS SHALL HAVE INTERNAL COMMON TRIP AND COMMON RESET WITH A SINGLE TOGGLE HANDLE OR NON-REMOVABLE MONOLITHIC TIE-HANDLE. TRIP RATINGS SHALL BE MOLDED ON THE HANDLE OR FACE OF BREAKER. BREAKER TERMINALS SHALL BE RATED TO ACCOMMODATE A MINIMUM OF 75 DEGREE C. CONDUCTORS. BREAKER SHALL BE RATED FOR MOUNTING AND OPERATION IN ANY POSITION; SHALL ACCOMMODATE AND MATCH THE TYPE OF TERMINATIONS REQUIRED. SINGLE POLE BREAKERS RATED 15 AND 20 AMPERES SHALL BE UL LABELED AS "SWITCHING BREAKERS" AT THE APPLIED CIRCUIT VOLTAGE. MULTI-POLE BREAKERS RATED 100 AMPERES AND LARGER SHALL BE MOLDED CASE THERMAL-MAGNETIC BOLT-IN TYPE BREAKER WITH ADJUSTABLE INSTANTANEOUS TRIP. LIGHTING FIXTURE SUBMITTAL: SCHEDULE BY TYPE DESIGNATION ALL LIGHTING FIXTURES, EACH COMPLETE WITH DATA SHEET WITH COMPLETE PHYSICAL, ELECTRICAL AND LIGHTING CHARACTERISTICS, LAMP TYPE AND LAMP DATA. REFER TO THE "LIGHTING FIXTURE SCHEDULE" \IN THE DRAWINGS FOR INDIVIDUAL FIXTURE DESCRIPTIONS AND MANUFACTURER TYPES. PROVIDE LAMPS FOR EACH FIXTURE OF QUANTITY, TYPE AND COLOR AS LISTED IN LIGHTING FIXTURE SCHEDULE. GE, SYLVANIA OR PHILIPS ARE ACCEPTABLE. EACH LIGHTING FIXTURE SHALL BE UL LABELED FOR PROPER OPERATION IN THE TYPE OF CEILING CONSTRUCTION AND FOR THE MOUNTING ARRANGEMENT ON/IN WHICH IT IS INSTALLED. FIELD VERIFY ACTUAL CEILING SLOPE FOR FIXTURES INSTALLED IN SAME AND ACTUAL FIELD DIMENSIONS AND ANGLES OF CONSTRUCTION FOR ANY FIXTURE CONFORMING THE SHAPE AND LENGTH OF SAME, FOR COORDINATION OF FIXTURE CONSTRUCTION. PANELBOARD SUBMITTAL: INCLUDE SCHEDULE OF EACH PANELBOARD WITH ALL DEVICES AND COMPLETE WITH PHYSICAL AND ELECTRICAL DATA AND WITH RATINGS FOR EACH COMPONENT INCLUDING BREAKER/FUSE OVERLAY CURVES. LABELED PER UL #67 AND #50, CONFORM WITH NEMA #250 AND PB1, NFPA #70-384 AND 70-373. ALL JUNCTION BOXES SHALL BE LABELED WITH PANEL AND CIRCUIT DESIGNATION. PROVIDE TYPED CIRCUIT DIRECTORY WITH EACH CIRCUIT SERVING DEVICES AND AREA IT'S SERVING. APPROVED MANUFACTURERS: GENERAL ELECTRIC CUTLER HAMMER SQUARE D SIEMENS GROUNDING AND BONDING ALL GROUNDING AND BONDING SHALL CONFORM TO NEC ARTICLE 250. COPPER WIRE OR CABLE INSULATED FOR 600V UNLESS REQUIRED BY APPLICABLE CODE OR AUTHORITIES HAVING JURISDICTION. INSTALL SOLID CONDUCTOR FOR #8 AWG AND SMALLER AND STRANDED CONDUCTORS FOR #6 OR LARGER. INSTALL INSULATED EQUIPMENT GROUNDING CONDUCTORS FOR ALL EQUIPMENT. THE DESIGN OF THIS SET OF DOCUMENT IS BASED ON NEC 2020. ELECTRICAL CONTRACTOR SHALL REFER TO ALL OTHER DESIGN DRAWINGS PRIOR TO BID AND RETAIN FULL UNDERSTANDING OF THE SCOPE OF WORK. FIXTURE TYPE INDICATED BY UPPER CASE CHARACTERS, SWITCHING AND GROUPING DESIGNATED BY LOWER CASE LETTER AND CIRCUIT BY NUMBER (WHERE APPLICABLE). REFER TO THE ARCHITECTURAL/INTERIORS REFLECTED CEILING PLANS FOR EXACT FIXTURE PLACEMENT AND DIMENSIONS. REFER TO THE ARCHITECTURAL/INTERIORS DOCUMENTS FOR ACTUAL DEVICE LOCATIONS AND DIMENSIONS. COORDINATE THE INSTALLATION OF ALL CEILING MOUNTED DEVICES (FIRE ALARM SYSTEM DEVICES AND SPEAKERS, SOUND SYSTEM SPEAKER, ETC.) TO BE SYMMETRICAL ABOUT LIGHT FIXTURES AND SPRINKLER HEADS. REFER TO THE ARCHITECTURAL REFLECTED CEILING PLAN. TYPICAL. ALL MOUNTING OF EQUIPMENT IS AS SHOWN UNLESS OTHERWISE NOTED. COORDINATE WITH ARCHITECT THE COLOR/FINISHES OF ALL ELECTRICAL DEVICES, OUTLETS, COVERPLATES AND TRIM. EMERGENCY BATTERY PACKS AND EXIT SIGNS SHALL BE CONNECTED AHEAD OF ANY SWITCHING DEVICES. REFER TO MECHANICAL DRAWINGS FOR DUCT SMOKE DETECTOR LOCATIONS AND QUANTITIES OPERATION SHALL INCLUDE DUAL CONTACT BASE WITH LOCAL EQUIPMENT SHUTDOWN AND FIRE ALARM SIGNAL INITIATION. WHEN CONDUCTOR OR CONDUIT SIZE IS INDICATED FOR BRANCH CIRCUIT HOME RUN, THE CONDUCTOR AND CONDUIT SIZE INDICATED SHALL BE USED FOR THE COMPLETE CIRCUIT. REFER TO THE APPROPRIATE DRAWINGS FOR THE EXACT LOCATION AND REQUIREMENTS OF EQUIPMENT INSTALLED UNDER OTHER DIVISIONS OF THE DOCUMENTS, WHICH REQUIRE ELECTRICAL SERVICE. EQUIPMENT GROUNDING CONDUCTORS SHALL BE INSTALLED IN ALL RACEWAYS. WALL SWITCHES CONTROLLING CIRCUITS OF OPPOSITE PHASES SHALL NOT BE INSTALLED IN COMMON BOX UNLESS PERMANENT BARRIER IS PROVIDED. ALL HOME RUNS SHALL RUN PARALLEL TO STRUCTURE AS MUCH AS POSSIBLE WHERE CEILING IS EXPOSED. ALL RACEWAY AND EQUIPMENT SUPPORTS AND HANGERS SHALL BE FULLY COORDINATED WITH STRUCTURAL DRAWINGS TO INSURE LOCATION OF SAME OCCURS WITHIN FOUR (4) INCHES OF PANEL POINT ON BAR JOISTS. COORDINATE LOCATION OF ALL FLOOR MOUNTED MECHANICAL AND PLUMBING EQUIPMENT IN ORDER TO VERIFY POWER & CONTROL RACEWAY CONCEALED IN SLABS TERMINATED AT PROPER LOCATION. DISCONNECT SWITCHES, MOTOR STARTERS AND OTHER ELECTRICAL EQUIPMENT INSTALLED ABOVE ACCESSIBLE CEILINGS, AND REQUIRING ACCESS FOR MAINTENANCE, SHALL BE INSTALLED WITH BOTTOM OF DEVICE ONE (1) FOOT ABOVE CEILING TO PROVIDE READY ACCESSIBILITY. MECHANICAL, PLUMBING, FIRE PROTECTION AND OTHER EQUIPMENT ARE SHOWN ON FLOOR PLAN IN APPROXIMATE LOCATION. COORDINATE WITH M, P, FP AND CONTRACT DRAWINGS/SUBMITTALS FOR EXACT LOCATION OF EQUIPMENT. GENERAL DIAGRAMMATIC RACEWAY INTERCONNECTIONS OF EQUIPMENT, FIXTURES AND DEVICES ARE INDICATED ON FLOOR AND REFLECTED CEILING PLANS, REFER TO STRUCTURAL AND ARCHITECTURAL PLANS FOR ELEVATION CHANGES AND RACEWAY ROUTES. RACEWAY FOR EXTERIOR LIGHTING MAY BE INDICATED OUTSIDE OF BUILDING FOOTPRINT FOR CLARITY. ROUTE ALL EXTERIOR LIGHTING RACEWAY WITHIN BUILDING STRUCTURE. POWER AND COMMUNICATIONS/DATA CONDUITS CAN CROSS AT 90°, BUT WHERE PARALLEL, SHALL BE A MINIMUM OF 8" APART. TELEVISION AND RADIO ANTENNAS CABLES SHALL HAVE SURGE PROTECTION. GROUND ALL MASTS. PROVIDE SURGE PROTECTION FOR ELECTRICAL AND TELEPHONE SERVICES. PROVIDE SPD FOR FIRE ALARM CONTROL PANEL. FIELD COORDINATE MECHANICAL AND PLUMBING EQUIPMENT ELECTRICAL CHARACTERISTICS WITH DIV.15 CONTRACTOR PRIOR TO ROUGH-IN. ADJUST ELECTRICAL CONNECTIONS IF NECESSARY TO MATCH ACTUAL EQUIPMENT IN FIELD. FOR EXAMPLE, COORDINATE THE NAMEPLATE OVERCURRENT PROTECTION DEVICE RATING OF MECHANICAL EQUIPMENT AMONG MECHANICAL AND ELECTRICAL SUBCONTRACTORS. ADJUST CIRCUIT BREAKER TO MATCH NAMEPLATE RATING OF EQUIPMENT AT NO ADDITIONAL COST. FIELD COORDINATE MECHANICAL AND PLUMBING EQUIPMENT REQUIREMENTS FOR ANY SUPPLEMENTAL POWER REQUIREMENTS, INCLUDING BUT NOT LIMITED TO CONTROL CIRCUITS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO BRING ALL EQUIPMENT TO ITS INTENDED OPERATIONAL STATUS. REFER TO FIRE PROTECTION DRAWINGS FOR LOCATIONS OF FLOW AND TAMPER SWITCHES. EACH PENETRATION OF A FIRE RESISTANT RATED ASSEMBLY BY A PIPE, TUBE WIRE OR CONDUIT SHALL BE PROTECTED BY A THROUGH PENETRATION FIRE STOP SYSTEM THAT HAS BEEN TESTED ACCORDING TO ASTME 814 OR E199. ELECTRIC RECEPTACLES, SWITCHES, OUTLETS, ETC. SHALL NOT BE INSTALLED BACK TO BACK ON FIRE RESISTANCE RATED WALLS. THEY SHALL BE AT LEAST 24-INCHES APART. LIGHT SWITCHES AND ELECTRICAL OUTLETS, LOCATED IN ROOMS ACCESSIBLE TO THE DISABLED SHALL BE LOCATED NO HIGHER THAN 48 INCHES AND NO LOWER THAN 15 INCHES ABOVE THE FINISHED FLOOR SURFACE. IF THE REACH OR THE CONTROL IS OVER AN OBSTRUCTION, THE MINIMUM HEIGHT SHALL BE REACHED TO 44 INCHES FOR A FORWARD APPROACH OR 46 INCHES FOR A SIDE APPROACH. REFER TO LOW VOLTAGE CONSULTANT'S DRAWINGS FOR VOICE, DATA AND CATV OUTLET LOCATIONS. REFER TO LV CONSULTANT'S DRAWINGS FOR ANY ADDITIONAL INFORMATION. CONNECT ALL EXIT SIGNS TO NEAREST UNSWITCHED PORTION OF THE LIGHTING CIRCUIT IN THE AREA. ELECTRICAL BOXES INSTALLED IN FIRE RATED WALLS SHALL MAINTAIN THE INTEGRITY OF THE RATED WALL. SUPPORT ALL VERTICAL RACEWAY PER NEC TABLE 300.19(A). MAKE ELECTRICAL CONNECTIONS TO ELECTRIC WATER COOLERS FROM GFCI PROTECTED OUTLET IN WALL BEHIND COOLER HOUSING. THE OUTLET AND CORD SHALL NOT BE VISIBLE FROM PUBLIC VIEW. COORDINATE WITH CUTSHEETS OF ALL EQUIPMENT TO BE INSTALLED AND PROVIDE ADDITIONAL CIRCUITS FOR CONTROLS IF REQUIRED BY MANUFACTURER. FINAL COLOR, FINISH AND OTHER AESTHETIC PORTIONS OF ALL DEVICES SHALL BE COORDINATED WITH ARCHITECT OR OWNER'S REPRESENTATIVE. THIS SET OF DRAWINGS DOES NOT SUPERCEDE ARCHITECTURAL OR INTERIOR DOCUMENTS. ALL EXPOSED HORIZONTAL RUNS OF CONDUITS SHALL BE EITHER PARALLEL OR PERPENDICULAR TO EXTERIOR WALLS. PROVIDE PLENUM RATED CABLES IF THE CABLES ARE EXPOSED AND ROUTED THROUGH PLENUM. FIRE ALARM ANNUNCIATOR PANEL GROUND FAULT CIRCUIT INTERRUPTER GROUND CABLE TV TERMINAL BACKBOARD 6" ABOVE COUNTER SPACE OR 42" AFF HOME RUN WITH WIRE TICKS. XX - PANEL DESIGNATION, # - CIRCUIT DESIGNATION. WIRE TICKS - (1) NEUTRAL , (3) HOT & (1) GROUND FIRE ALARM NOTIFICATION DEVICE. AUDIO AND VISUAL. ELECTRICAL PANELBOARD. REFER TO PANELBOARD SCHEDULE. FUSED DISCONNECT SWITCH. SUBSCRIPT: AMP / # OF POLES / ENCLOSURE / FUSE DISCONNECT SWITCH. SUBSCRIPT: AMP / # OF POLES / ENCLOSURE TELEPHONE OUTLET. SUBSCRIPT: F - FIREMAN'S PHONE, H - HOUSE PHONE, P - PAY PHONE SWITCH - WALL MTD, INTEGRAL OCCUPANCY SENSOR JUNCTION BOX FLUSH IN FINSHED FLOOR WITH COVER. SIZE PER NEC. JUNCTION BOX FLUSH IN CEILING WITH COVER. SIZE PER NEC. JUNCTION BOX FLUSH IN WALL WITH COVER. SIZE PER NEC. SPECIAL RECEPTACLE, CONFIGURATION AND ELECTRICAL CHARACTERISTIC AS NOTED ON DWG QUADRAPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R QUADRAPLEX RECEPTACLE, 120V, 20A, NEMA 5-20R 42" AFF OR 6" ABOVE COUNTER TOP 42" AFF OR 6" ABOVE COUNTER TOP FLUSH WITH FINISHED FLOOR FLUSH WITH FINISHED FLOOR 42" AFF OR 6" ABOVE COUNTER TOP FLUSH WITH FINISHED FLOOR 42" AFF OR 6" ABOVE COUNTER TOP 42" AFF OR 6" ABOVE COUNTER TOP AS INDICATED ON DWG AS INDICATED ON DWG SURFACE MOUNTED ON WALL SURFACE MOUNTED ON WALL TYPICAL MOUNTING HEIGHT UNLESS NOTED OTHERWISE SURGE PROTECTIVE DEVICE CONSTRUCTION FOR 03/28/2024 ONE-LINE DIAGRAM PANEL A 208/120V 2P 3W BUS AMPS: 60 MAIN: MLO DEMAND KVA: 4.56 3/4"C, 2#6, #6N, #8G M UTILITY CIRCUIT DESCRIPTION LOAD KVABKR CKT # CKT KVA CIRCUIT DESCRIPTIONBKR# LOADCKTCKT NOTE NEUTRAL BUS AMPS VOLTSPanel AIC MAIN BKR LUGSFED FROM MOUNTING ROOM STANDARD MLO 22,000 60 208/120V 2P 3W FLUSHAUTILITY 100% a 2120/1 20/10.3 0.3 b 4320/1 20/10.3 0.2 a 6520/1 20/11.0 0.0 b 8720/1 20/11.9 0.0 a 10920/1 20/10.0 0.0 CONN KVA CONN KVA CALC KVA CALC KVA LIGHTING 0.8 1.0 (125%) RECEPTACLES 0.2 0.2 (50%>10) CONTINUOUS 1.9 2.4 (125%) NONCONTINUOUS 1.0 1.0 (100%) TOTAL LOAD 4.6 BALANCED LOAD 21.9 A PHASE A 78.4% PHASE B 122% LIGHTING LIGHTING TEL BACKBOARD GATE SPACE LIGHTING RECEPTACLE SPACE SPACE SPACE LUMINAIRE SCHEDULE CALLOUT SYMBOL LAMP DESCRIPTION MODEL VOLTS A (1) 260W LED FLOOD LIGHT DUKE ENERGY PROGRESS FLOODLIGHT LED 120V 1P 2W 31 0 M E T R O C I R C L E Wi l m i n g t o n , N C 2 8 4 0 8 SHEET NUMBER: 11.16.23 SHEET NAME: NOT FOR CONSTRUCTION DRAWN BY: CHECKED BY: DATE DESCRIPTION 11/16/2023 ISSUE / REVISIONS: PERMIT SET AN RD 5335 W 48th Ave Suite 103 Denver, CO 80212 720.779.3556 PROJECT # 323082 N O R T H C AR LI N A O 12/15/2023 REVISION 1 SITE PLAN E-2 03/28/2024 CONSTRUCTION FOR OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH X X X X X X X X X X X X X X X X X X X X X X A A A 1 COORDINATE EXACT LOCATION OF PANEL A WITH ARCHITECT/CIVIL. POWER FOR TELEPHONE TERMINAL BOARD. ROUTE (2) 2"C FROM TELEPHONE UTILITY DEMARCATION POINT WITH PULL STRING. COORDINATE EXACT LOCATION WITH ARCH/CIVIL PRIOR TO ROUGH-IN. POWER FOR GATE. COORDINATE EXACT LOCATION WITH ARCH/CIVIL PRIOR TO ROUGH-IN. KEYNOTES 1 ALL RECEPTACLES SHALL BE GROUNDED AS REQUIRED BY ARTICLE 250-146. GENERAL NOTES METER WP GF TTB A A-1 #10 A-2 #10 A-3 #10 A-4A-5 2 J GATE A-7 #10 2 3 3 31 0 M E T R O C I R C L E Wi l m i n g t o n , N C 2 8 4 0 8 SHEET NUMBER: 11.16.23 SHEET NAME: NOT FOR CONSTRUCTION DRAWN BY: CHECKED BY: DATE DESCRIPTION 11/16/2023 ISSUE / REVISIONS: PERMIT SET AN RD 5335 W 48th Ave Suite 103 Denver, CO 80212 720.779.3556 PROJECT # 323082 N O R T H C AR LI N A O 12/15/2023 REVISION 1 SITE PLAN E-31 E-3 SITE PLAN 1" = 30'-0" 03/28/2024 CONSTRUCTION FOR GENERAL REQUIREMENTS APPLICABLE REQUIREMENTS OF GENERAL REQUIREMENTS/PROVISIONS SHALL BE CONSIDERED A PART OF THIS SECTION AND SHALL HAVE THE SAME FORCE AS IF PRINTED HEREIN FULL. IN ADDITION, ALL INFORMATION RELATED TO COMMUNICATIONS INFRASTRUCTURE THAT IS DOCUMENTED IN THE ARCHITECTURAL, STRUCTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS/DOCUMENTS SHALL BE INCLUDED AS PART OF THE COMMUNICATIONS DOCUMENTS ALL WORK SHALL BE IN ACCORDANCE WITH THE FOLLOWING: 2020 NEC WITH KY AMENDMENTS ANSI NEMA TIA BICSI EIA IEEE UL ASA FCC OSHA ASTM ADA LOCAL CITY AND COUNTY ORDINANCES GOVERNING ELECTRICAL WORK IN THE EVENT OF CONFLICTS, THE MORE STRINGENT PROVISIONS SHALL APPLY. THE WORK TO BE DONE UNDER THIS SECTION OF THE SPECIFICATIONS SHALL INCLUDE FURNISHING LABOR, MATERIAL, EQUIPMENT AND TOOLS REQUIRED FOR THE COMPLETE INSTALLATION OF THE WORK INDICATED ON THE DRAWINGS OR AS SPECIFIED HERE. ALL MATERIALS, OBVIOUSLY A PART OF THE COMMUNICATIONS INFRASTRUCTURE AND NECESSARY TO ITS PROPER OPERATION, BUT NOT SPECIFICALLY MENTIONED OR SHOWN ON THE DRAWINGS, SHALL BE FURNISHED AND INSTALLED WITHOUT ADDITIONAL CHARGE. THE DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY TO EACH OTHER AND WHAT IS CALLED FOR BY ONE SHALL BE AS BINDING AS IF CALLED FOR BY BOTH. IF A DISCREPANCY EXISTS BETWEEN THE DRAWING AND SPECIFICATIONS, THE HIGHER COST SHALL BE INCLUDED, AND THE ENGINEER SHALL BE NOTIFIED OF THE DISCREPANCY. THE COMMUNICATIONS INFRASTRUCTURE INSTALLED AND WORK PERFORMED SHALL INCLUDE BUT NOT NECESSARILY BE LIMITED TO: STRUCTURED CABLING INFRASTRUCTURE COMMUNICATIONS CONDUITS, RACEWAYS, CABLE TRAY, RACKS, CABINETS AND EQUIPMENT MOUNTING BOARDS GROUNDING AND BONDING UNDERGROUND RACEWAY EXCAVATION, BACKFILL, AND COMPACTION CONCRETE WORK FOR DUCT BANKS, MAINTENANCE HOLES, HANDHOLES, VAULTS AND RESTORATION (WHERE APPLICABLE) DRAWINGS ARE GENERALLY DIAGRAMMATIC AND SHOW THE ARRANGEMENT AND LOCATION OF PATHWAYS, OUTLETS, SUPPORT STRUCTURES AND EQUIPMENT. THE CONTRACTOR SHALL CAREFULLY INVESTIGATE THE STRUCTURAL AND FINISH CONDITIONS AFFECTING HIS WORK AND ARRANGE HIS WORK ACCORDINGLY. SHOULD CONDITIONS ON THE JOB MAKE IT NECESSARY TO MAKE ADJUSTMENTS TO PATHWAYS OR MATERIALS, THE CONTRACTOR SHALL ADVISE THE ENGINEER AND SECURE APPROVAL BEFORE PROCEEDING WITH SUCH WORK. MATERIALS, EQUIPMENT OR LABOR NOT INDICATED BUT WHICH CAN BE REASONABLY INFERRED TO BE NECESSARY FOR A COMPLETE INSTALLATION SHALL BE PROVIDED. DRAWINGS AND SPECIFICATIONS DO NOT UNDERTAKE TO INDICATE EVERY ITEM OF MATERIAL, EQUIPMENT, OR LABOR REQUIRED TO PRODUCE A COMPLETE AND PROPERLY OPERATING INSTALLATION. THE LOCATION OF EQUIPMENT, SUPPORT STRUCTURES, OUTLETS, AND SIMILAR DEVICES SHOWN ON THE DRAWINGS ARE APPROXIMATE ONLY. DO NOT SCALE DRAWINGS. OBTAIN LAYOUT DIMENSIONS FOR EQUIPMENT FROM ARCHITECTURAL PLANS UNLESS INDICATED ON COMMUNICATIONS PLANS. SCHEMATIC DIAGRAMS SHOWN ON THE DRAWINGS INDICATE THE REQUIRED FUNCTIONS ONLY. THE TECHNOLOGY OF A PARTICULAR MANUFACTURER MAY BE USED TO ACCOMPLISH THE FUNCTIONS INDICATED WITHOUT EXACT ADHERENCE TO THE SCHEMATIC DRAWINGS SHOWN. ADDITIONAL LABOR AND MATERIALS REQUIRED FOR SUCH DEVIATIONS SHALL BE FURNISHED AT THE CONTRACTOR'S EXPENSE. EQUIPMENT AND MATERIALS REQUIRED FOR INSTALLATION UNDER THESE SPECIFICATIONS SHALL BE THE CURRENT MODEL AND NEW (LESS THAN ONE [1] YEAR FROM THE DATE OF MANUFACTURE), UNUSED AND WITHOUT BLEMISH OR DEFECT. THE CONTRACTOR SHALL HAVE TOTAL RESPONSIBILITY FOR THE COORDINATION AND INSTALLATION OF THE WORK SHOWN AND DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS. THE CONTRACTOR SHALL BE A COMPANY SPECIALIZING IN THE DESIGN, FABRICATION AND INSTALLATION OF INTEGRATED COMMUNICATIONS SYSTEMS. COMMUNICATIONS SYSTEMS SPECIFIED SHALL BE INSTALLED UNDER THE DIRECTION OF A QUALIFIED CONTRACTOR. THE CONTRACTOR SHALL COORDINATE COMMUNICATIONS WORK WITH THAT OF OTHER SECTIONS AS REQUIRED TO ENSURE THAT THE ENTIRE COMMUNICATIONS WORK WILL BE CARRIED OUT IN AN ORDERLY, COMPLETE AND COORDINATED FASHION. OBTAIN ALL PERMITS AND INSPECTIONS FOR THE INSTALLATION OF THIS WORK AND PAY ALL CHARGES INCIDENT THERETO. DELIVER TO THE OWNER ALL CERTIFICATES OF SAID INSPECTION ISSUED BY AUTHORITIES HAVING JURISDICTION. PRODUCT SUBSTITUTIONS ARE NOT ALLOWED UNLESS NOTED AS, “OR APPROVED EQUAL (BY OWNER).” THE ENGINEER'S DECISION AS TO WHETHER THE SUBMITTED EQUIPMENT IS ACCEPTABLE SHALL BE FINAL AND BINDING. ALL MATERIALS USED IN THIS WORK SHALL BE NEW AND SHALL BEAR THE INSPECTION LABEL OF UNDERWRITERS' LABORATORIES INC. OR CERTIFICATION BY OTHER RECOGNIZED LABORATORY. DURING CONSTRUCTION, AND PRIOR TO OWNER ACCEPTANCE OF THE BUILDING, REMOVE FROM THE PREMISES AND DISPOSE OF PACKING MATERIAL AND DEBRIS CAUSED BY COMMUNICATIONS WORK. REMOVE DUST AND DEBRIS FROM INTERIORS AND EXTERIORS OF ELECTRICAL EQUIPMENT. CLEAN ACCESSIBLE CURRENT CARRYING ELEMENTS PRIOR TO BEING ENERGIZED. UPON COMPLETION OF THE WORK, REMOVE EXCESS DEBRIS, MATERIALS, EQUIPMENT, APPARATUS, TOOLS AND SIMILAR ITEMS. LEAVE THE PREMISES CLEAN, NEAT AND ORDERLY. SYSTEMS SHALL BE COMPLETE AND OPERATIONAL AND CONTROLS SHALL BE SET AND CALIBRATED. TESTING, START-UP AND CLEANING WORK SHALL BE COMPLETE. SPECIFICATIONS FIRESTOPPING FOR COMMUNICATIONS SYSTEMS APPROVED FIRESTOPPING MANUFACTURER(S): STI FIRESTOP PRODUCTS (FIRESTOP DEVICES, PUTTIES, CAULKS, SEALANTS, ETC.) HILTI (FIRESTOP DEVICES, PUTTIES, CAULKS, SEALANTS, ETC.) 3M FIRESTOP PRODUCTS (FIRESTOP DEVICES, PUTTIES, CAULKS, SEALANTS, ETC.) FLAMESTOPPER THRU-WALL FITTING - WIREMOLD COMPANY (FIRESTOP DEVICES) UNIQUE FIRESTOP PRODUCTS (FIRESTOP DEVICES) SEALANTS: INTUMESCENT FIRESTOP SEALANTS AND CAULKS, LATEX FIRESTOP SEALANT, ACRYLIC WATER-BASED SEALANT, SILICONE FIRESTOP SEALANTS AND CAULKS, FIRESTOP PUTTY, FIRESTOP COLLARS, FIRESTOP SLEEVES, WRAP STRIPS, 2-PART SILICONE FIRESTOP FOAM, FIRESTOP MORTAR, FIRESTOP PILLOWS, ELASTOMERIC SPRAY FIRESTOP DEVICES: THRU-WALL FITTING, THREADED FIRESTOP DEVICE, SMOOTH FIRESTOP DEVICE, SPLIT-SLEEVE FIRESTOP DEVICE, FIRE RATED CABLE PATHWAY UL CLASSIFICATION: THRU-WALL FITTING - THE FIRESTOP DEVICE FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS SHALL HAVE BEEN EXAMINED AND TESTED BY UNDERWRITERS LABORATORIES INC. TO UL1479 (ASTM E 814) AND BEAR THE U.S. AND CANADIAN UL CLASSIFICATION MARK. THREADED, SMOOTH AND SPLIT-SLEEVE FIRESTOP DEVICES -FIRESTOPPING SEALANTS AND DEVICES SHALL BE USED TOGETHER AS A FIRESTOP SYSTEM. ALL FIRESTOP SYSTEMS SHALL BEAR A UL CLASSIFICATION SYSTEM NUMBER. GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS A LICENSED ELECTRICAL CONTRACTOR SHALL PERFORM INSTALLATION AND TERMINATION OF THE MAIN BONDING CONDUCTOR TO THE BUILDING SERVICE ENTRANCE GROUND. APPROVED EQUIPMENT GROUNDING CONDUCTOR MANUFACTURER(S): SOUTHWIRE, BELDEN APPROVED GROUNDING LUG MANUFACTURER(S): BURNDY, THOMAS & BETTS, CHATSWORTH PRODUCTS, INC. CONDUCTOR SHALL BE TYPE THHN COPPER CONDUCTORS, INSULATED WITH HEAT AND MOISTURE RESISTANT PVC OVER WHICH A UL LISTED JACKET IS APPLIED. ALL RACKS, CABINETS, METALLIC ENCLOSURES, CONDUITS, METALLIC BACKBOARDS, CABLE SHEATHS, METALLIC STRENGTH MEMBERS, SPLICE CASES, CABLE TRAYS, ETC. ENTERING OR RESIDING IN THE MC/IC/TC SHALL BE GROUNDED TO THE RESPECTIVE BUSBAR USING A MINIMUM #6 AWG STRANDED COPPER BONDING CONDUCTOR AND COMPRESSION LUGS. PATHWAYS FOR COMMUNICATIONS SYSTEMS MANUFACTURERS: SQUARE D, B-LINE, ALLIED TUBE & CONDUIT, HOFFMAN, CARLON ELECTRICAL, WIREMOLD. OUTDOORS EXPOSED: RIGID STEEL. OUTDOORS CONCEALED ABOVE GROUND: RIGID STEEL. OUTDOORS UNDERGROUND: TYPE EPC-40-PVC OUTDOORS CONNECTION TO VIBRATING EQUIPMENT (INCLUDING TRANSFORMERS AND MOTOR DRIVEN EQUIPMENT): LFMC. BOXES AND ENCLOSURES ABOVE GROUND: NEMA 3R UNLESS NOTED OTHERWISE ON PLANS. INDOORS EXPOSED NOT SUBJECT TO PHYSICAL DAMAGE: EMT. INDOORS EXPOSED NOT SUBJECT TO SEVERE PHYSICAL DAMAGE: EMT. INDOORS EXPOSED SUBJECT TO SEVERE PHYSICAL DAMAGE: RIGID STEEL CONDUIT. INDOORS CONCEALED IN CEILINGS AND INTERIOR WALLS AND PARTITIONS: EMT. INDOORS CONNECTION TO VIBRATING EQUIPMENT: FMC, EXCEPT USE LFMC IN DAMP OR WET LOCATIONS. INDOORS DAMP OR WET LOCATIONS: IMC. INDOORS LOW-VOLTAGE CABLES: EMT. LEAVE ALL EMPTY CONDUITS WITH A 200 POUND TEST NYLON CORD PULL LINE. EXACT LOCATIONS OF THE OUTLET BOXES SHALL BE COORDINATED WITH THE ELECTRICAL CONTRACTOR AND OTHER TRADES. NON-METALLIC COMMUNICATIONS OUTLET BOXES SHALL NOT BE USED. THE APPROXIMATE LOCATIONS OF THE OUTLETS ARE INDICATED ON THE DRAWINGS. THE EXACT LOCATIONS OF OUTLETS SHALL BE DETERMINED AT THE BUILDING. THE RIGHT IS RESERVED TO CHANGE, WITHOUT ADDITIONAL COST, THE EXACT LOCATION OF ANY OUTLET, A MAXIMUM OF 10' BEFORE IT IS PERMANENTLY INSTALLED. UNDERGROUND DUCTS, RACEWAYS, AND HANDHOLES FOR COMMUNICATIONS SYSTEMS APPROVED MAINTENANCE HOLE/HANDHOLE MANUFACTURER(S): QUAZITE, PENCELL, OLD CASTLE MAINTENANCE HOLES SHALL BE PRE-CAST OR CAST IN PLACE CONCRETE WITH A STRENGTH OF 3,500 PSI AT 28 DAYS, AND STEEL REINFORCED. MAINTENANCE HOLES SHALL INCLUDE A CAST IRON FRAME WITH COVER, A HOT DIPPED GALVANIZED STEEL LADDER, AND HOT DIPPED GALVANIZED PULLING EYES EMBEDDED IN THE CONCRETE OPPOSITE EACH DUCT ENTRANCE AND IN THE FLOOR BENEATH THE COVER. MAINTENANCE HOLES SHALL BE EQUIPPED WITH GROUNDING BUSBAR. MAINTENANCE HOLES SHALL BE EQUIPPED WITH RACKING FOR CABLE STORAGE. GROUND SPLICES AND CONNECTIONS AT MAINTENANCE HOLES SHALL BE EXOTHERMIC WELDS, COPPER OR BRONZE COMPRESSION GROUND FITTINGS, OR BOLTED COMPRESSION RING LUGS. THE COVER FOR MAINTENANCE HOLES SHALL HAVE THE LETTERING, “COMMUNICATIONS.” HANDHOLES SHALL BE NON-CONDUCTIVE AND SHALL NOT REQUIRE GROUNDING FOR SAFETY. HANDHOLES SHALL BE UNAFFECTED BY FREEZE/THAW AND RESISTANT TO SUNLIGHT AND CHEMICALS. HANDHOLES SHALL BE PRE-CAST POLYMER CONCRETE, HEAVY DUTY RATED AND BOTTOMLESS. HANDHOLES SHALL BE EQUIPPED WITH RACKING FOR CABLE STORAGE. HANDHOLES SHALL HAVE THE WORD “COMMUNICATIONS” MOLDED IN THE COVER BY THE MANUFACTURER. THE COVER SHALL BE ATTACHED WITH PENTA-HEAD STAINLESS STEEL BOLTS. HANDHOLES SHALL BE ABLE TO WITHSTAND 10,000 LBS MINIMUM. SEE DRAWINGS FOR HANDHOLE LOCATIONS. MAINTENANCE HOLES/HANDHOLES SHALL BE INSTALLED ON A BASE OF PEA GRAVEL AT LEAST 12 INCHES DEEP. TOPS OF MAINTENANCE HOLES/HANDHOLES SHALL BE LEVEL WITH THE EXISTING GRADE. DUCTS SHOULD ENTER AS PERPENDICULAR TO THE WALL SURFACE AS POSSIBLE. MAINTENANCE HOLES SHALL BE GROUNDED WITH FOUR 3/4 INCH DIAMETER BY 8 FOOT LONG GROUND RODS, ONE DRIVEN INSIDE OF THE MAINTENANCE HOLE AT EACH CORNER. CONNECT THE GROUND RODS AND ANY DUCT BANK GROUND CONDUCTORS TOGETHER WITH A NO. 4/0 AWG BARE, STRANDED COPPER GROUND WIRE LOOP. A NO. 2 AWG BARE STRANDED COPPER PIGTAIL FROM THE GROUND WIRE LOOP SHALL BE USED TO GROUND THE MAINTENANCE HOLE COVER FRAME, LADDER SUPPORT BRACKET, ANY METALLIC CONCRETE INSERTS AND METALLIC CABLE RACKS, AND THE SHIELDS OF ANY CABLES THAT ARE SPLICED IN THE MAINTENANCE HOLE. SPECIFICATIONS NO CONDUIT RUN TO CONTAIN MORE THAN TWO (2) 90 DEGREE BENDS BETWEEN PULLING POINTS. PROVIDE JUNCTION BOXES WHERE REQUIRED TO MAINTAIN (2) 90 DEGREE BEND RULE. ALL WALL AND FLOOR PENETRATIONS TO BE SEALED AND FIREPROOFED. CONDUIT ROUTING PATHS TO BE COORDINATED WITH ALL OTHER SYSTEMS. ALL CABLES TO BE ROUTED DIRECT TO EQUIPMENT ROOMS WITHOUT SPLICES. NO JUNCTIONS OR SPLICES IN CABLES ARE ACCEPTABLE. ALL CONDUITS ROUTED BELOW GRADE TO BE SEALED TO PREVENT WATER INFILTRATION INTO EQUIPMENT ROOMS. ALL CONDUITS ROUTED BELOW GRADE TO BE SCHEDULE 40 PVC. CONDUIT ROUTED ABOVE GRADE TO BE EMT. NO ELECTRONIC DEVICES ARE ALLOWED TO BE INSTALLED IN HANDHOLE BOXES. ALL TERMINATIONS AND SPLICES IN HANDHOLE BOXES MUST BE WET RATED. ALL CONDUITS ARE TO INCLUDE PULL STRINGS INSTALLED WITHIN. GENERAL NOTES 31 0 M E T R O C I R C L E Wi l m i n g t o n , N C 2 8 4 0 8 SHEET NUMBER: 11.16.23 SHEET NAME: CONSTRUCTION DRAWN BY: CHECKED BY: DATE DESCRIPTION 03/28/2024 ISSUE / REVISIONS: PERMIT SET FOR 5335 W 48th Ave Suite 103 Denver, CO 80212 720.779.3556 PROJECT # 323082 N O R T H C AR LI N A O JS JS SITE PLAN LV-1 WEATHERPROOF ENCLOSURE PAN/TILT DRIVE 6" DIA GALVANIZED STEEL POLE WITH FINISH TO MATCH LIGHTING FIXTURE POLES 1" FLEXIBLE CONDUIT INSIDE POLE FOR VIDEO CABLES 4 ANCHOR BOLTS 1/2" x 4'-0" LONG GRADE 1" PVC FOR VIDEO CABLES CONCRETE BASE 1" PVC FOR 120V. POWER WIRING NOTE: CAMERA, ENCLOSURE, PAN/TILT & WIRING UNDER DIVISION 17. 4'-6" 24" 18" ROUND 18" 6" 14'-0" SEALTITE CONDUIT TO CAMERA 4' - 0 " 2'-0" CURB/FINISNED GROUND 1 1 CR KP 4 5 4 4 E 6 2 3 HH SECURITY GATE VEHICLE PRESENSE LOOP (PROVIDED BYGATE CONTRACTOR) VEHICLE SAFTY/CLOSE LOOP (PROVIDEDBY GATE CONTRACTOR) VEHICLE EXIT LOOP (PROVIDED BY GATECONTRACTOR) 31 0 M E T R O C I R C L E Wi l m i n g t o n , N C 2 8 4 0 8 SHEET NUMBER: 11.16.23 SHEET NAME: CONSTRUCTION DRAWN BY: CHECKED BY: DATE DESCRIPTION 03/28/2024 ISSUE / REVISIONS: PERMIT SET FOR 5335 W 48th Ave Suite 103 Denver, CO 80212 720.779.3556 PROJECT # 323082 N O R T H C AR LI N A O JS JS DETAILS LV-2 1 L-2 POLE MOUNT CAMERA 3/8" = 1'-0" PROVIDE NEMA 4 PULL BOX FOR LOW VOLTAGE SYSTEMS. PROVIDE SEPARATE 3/4" CONDUITS FOR LOW VOLTAGE SYSTEMS AND 120 VAC POWER. ALL CONDUIT ROUTED ABOVE GRADE TO BE EMT. PVC ACCEPTABLE BELOW GRADE. PROVIDE AND INSTALL GATE CONTROL CIRCUIT & INTERFACE WITH GATE OPERATORS AND GATE ARMS PROVIDED BY OTHERS. WIRE GATE POSITIONSWITCH TO MONITOR GATE POSITION. VEHICLE GATE TO BE CONTROLLED BY SECURITY AND ACCESS CONTROL SYSTEM. COORDINATE WITH ELECTRICAL CONTRACTOR FOR PLACEMENT OF 120 VAC/20 AMP CIRCUITS FOR USE BY GATE CONTROLS CONTRACTOR. CONTROL CIRCUIT FOR GATE CONTROLLER TO BE ROUTED TO SECURITY & ACCESS CONTROL SYSTEM. PROVIDE GOOSE NECK PEDESTAL. SEE INSTALLATION DETAIL. MOUNT INTERCOM AND CARD READER ON PEDESTAL. CARDREADER TO BE ROUTED TO BUILDING SECURITY & ACCESS CONTROL SYSTEM. INTERCOM STATION TO BE TELEPHONE-BASED AND WIRED TO TELECOM ROOM. INSTALL CONCRETE BASE TO MANUFACTURERS' SPECIFICATIONS ASREQUIRED. PROVIDE ALL LOOPS AS IDENTIFIED. FOLLOW MANUFACTURERINSTALLATION INSTRUCTIONS FOR CUTTING IN LOOPS AND PROPER CABLE CONFIGURE LOOPS TO ALLOW FOR ONLY ONE VEHICLE ENTRANCE PER CYCLE. FOR PROTECTION OF PEDESTAL AND GATE, INSTALL BOLLARDS. BOLLARDSTO BE 6” DIAMETER ALL WELDED STEEL GUARDS. BOLLARDS TO BE PROVIDEDWITH 8” X 8” MOUNTING PLATES WITH 1” HOLES PRE-DRILLED ON 1” CENTERS FROM PLATE EDGE. BOLLARDS TO BE PAINTED SAFETY YELLOW AND EXTEND 36” ABOVE GRADE. INSTALL CONCRETE BASE TO MANUFACTURERS' SPECIFICATIONS AS REQUIRED. INSTALL ONE (1) -1" CONDUIT FROM VEHICLE GATE ENCLOSURE TO CARDREADER/ INTERCOM STATION PEDESTAL. INSTALL TWO (2) - 1" CONDUITS BETWEEN GATE ENCLOSURES. KEY NOTES 1 2 3 4 5 6 2 L-2 MULLION MOUNT CARD READER 3/8" = 1'-0" OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH OH X X X X X X X X X X X X X X X X X X X X X X HH MAIN SITE HANDHOLE TO BE USED FOR TELECOMMUNICATIONS CABLES ONLY. 3 21 4 KP 5 6 6 6 7 31 0 M E T R O C I R C L E Wi l m i n g t o n , N C 2 8 4 0 8 SHEET NUMBER: 11.16.23 SHEET NAME: CONSTRUCTION DRAWN BY: CHECKED BY: DATE DESCRIPTION 03/28/2024 ISSUE / REVISIONS: PERMIT SET FOR 5335 W 48th Ave Suite 103 Denver, CO 80212 720.779.3556 PROJECT # 323082 N O R T H C AR LI N A O JS JS SITE PLAN LV-31 L-3 SITE PLAN 1" = 30'-0" CONTRACTOR TO PROVIDE AND INSTALL ONE (1) 24”X 36”X 26“QUAZITE HAND HOLE (SITE JUNCTION BOX) WITH BOLT ON COVER. COORDINATE LOCATION WITH OTHER TRADES AND WITH TELECOM SERVICE PROVIDER. CONTRACTOR TO INSTALL TWO (2) -4" SLEEVES IN HANDHOLE FOR SERVICE PROVIDER USE. SEAL SLEEVES AFTER INSTALLATION. CONTRACTOR TO INSTALL, BELOW GRADE, TWO (2) 40 PVC CONDUITS BETWEEN HAND HOLE AND SITE TELECOM CLOSET LOCATION (TO BE DETERMINED). INSTALL CONDUITS PER CURRENT NEC CODES. USE LONG RADIUS 90 DEGREE ELBOWS TO TURN CONDUITS UP INTO MDF/IDF ROOM. CONDUITS TO TURN-UP ~3”ABOVE GRADE SLAB. ALL CONDUIT OPENINGS ARE TO BE SEALED. INSTALL IN ONE CONDUIT TWO (2) -4”, THREE CELL, MAXCELL INNER DUCT SYSTEM FOR FUTURE USE. CONTRACTOR TO INSTALL, BELOW GRADE, TWO (2) 40 PVC CONDUITS BETWEEN HAND HOLE AND UTILITY SERVICE LINE LOCATION. COORDINATE UTILITY SERVICE LINE LOCATION WITH CIVIL DRAWINGS. INSTALL CONDUITS PER CURRENT NEC CODES. USE LONG RADIUS 90 DEGREE ELBOWS TO TURN CONDUITS UP INTO MDF/IDF ROOM. CONDUITS TO TURN-UP ~3”ABOVE GRADE SLAB. ALL CONDUIT OPENINGS ARE TO BE SEALED. INSTALL IN ONE CONDUIT TWO (2) -4”, THREE CELL, MAXCELL INNER DUCT SYSTEM FOR FUTURE USE. CONTRACTOR TO INSTALL CARD READER/KEYPAD ON MULLION. EXACT LOCATION TO BE DETERMINED BY LOCATION OF GATE ON SITE. CONTRACTOR TO MOUNT CAMERAS ON LIGHT POLES AS INDICATED BY OWNER. CAMERAS TO BE ADJUSTED AND FOCUSED BY CONTRACTOR TO OWNERS APPROVAL. POLES TO BE INSTALLED IN ISLAND CURB. CONTRACTOR TO ADJUST CAMERA TO FIT OWNERS NEED OF CAPTURING LICENSE PLATES. CAMERA TO BE MOUNTED ON LIGHT POLE AS INDICATED BY OWNER. KEY NOTES 1 2 3 4 5 6 7