24140 Electrical, Fire, Mechanical and Plumbing Combined
PE PP CB OS swin g SO SO S SO SD S SS S S SAFC S OS OS S SO OS OS S SM ES ML DC MD CR T T1 1 FBO FURNISHED BY OTHERS FLA FULL LOAD AMPS FLUOR FLUORESCENT FLR FLOOR FWE FURNISHED WITH EQUIPMENT GEN GENERATOR G, GND GROUND GFI, GFCI GROUND FAULT CIRCUIT INTERRUPTER HH HANDHOLE HID HIGH INTENSITY DISCHARGE HOA HAND-OFF-AUTO HP HORSE POWER HPF HIGH POWER FACTOR HPS HIGH PRESSURE SODIUM HTR HEATER HV HIGH VOLTAGE Hz HERTZ A, AMP AMPERE AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AHU AIR HANDLING UNIT AIC AMPERE INTERRUPTING CAPACITY ATS AUTOMATIC TRANSFER SWITCH AWG AMERICAN WIRE GAUGE BOF BOTTOM OF FIXTURE BRKR BREAKER C, CND CONDUIT CAB CABINET CAT CATALOG CL CHLORINE CB CIRCUIT BREAKER CCTV CLOSED CIRCUIT TELEVISION CKT CIRCUIT CLG CEILING CP CONTROL PANEL CR CONTROL RELAY, CORROSION RESISTANT CS CONTROL SWITCH CV CONTROL VALVE CT CURRENT TRANSFORMER CU COPPER EF EXHAUST FAN EM EMERGENCY EMT ELECTRICAL METALLIC TUBING ENCL ENCLOSURE EQ, EQIP EQUIPMENT EWC ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER EPRF EXPLOSION PROOF FA FIRE ALARM FAAP FIRE ALARM ANNUNCIATOR PANEL FACP FIRE ALARM CONTROL PANEL IMC INTERMEDIATE METALLIC CONDUIT INCAND INCANDESCENT JB JUNCTION BOX K THOUSAND Kcmil THOUSAND CIRCULAR MILLS KVA KILOVOLT AMPERE KW KILOWATTS KWH KILOWATT-HOURS LP LIGHTING PANEL, LIGHT POLE LTG LIGHTING MCB MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MCP MOTOR CIRCUIT PROTECTOR MDP MAIN DISTRIBUTION PANEL MFR MANUFACTURER MH MANHOLE MLO MAIN LUGS ONLY MTD MOUNTED MTG MOUNTING MTS MANUAL TRANSFER SWITCH MV MEDIUM VOLTAGE N, NEUT NEUTRAL N/A NOT APPLICABLE NC NORMALLY CLOSED NEC NATIONAL ELECTRIC CODE NIC NOT IN CONTRACT NL NIGHT LIGHT NO NORMALLY OPEN NTS NOT TO SCALE P POLE PA PUBLIC ADDRESS PB PULL BOX, PUSH-BUTTON PF POWER FACTOR PH,ɸ PHASE PLC PROGRAMMABLE LOGIC CONTROLLER PNL PANEL PP POWER PANEL, POWER POLE PT POTENTIAL TRANSFORMER PWR POWER RECPT,RCPRECEPTACLE REQ'D REQUIRED RGS RIGID GALVANIZED STEEL CONDUIT RM ROOM RTU REMOTE TELEMETRY UNIT SCR DC MOTOR DRIVE SH SHEET SM SURFACE MOUNTED SPEC SPECIFICATION SS SELECTOR SWITCH SST STAINLESS STEEL SW SWITCH SWBD SWITCHBOARD SWGR SWITCH GEAR TEL TELEPHONE TPS TWISTED PAIR SHIELDED TVSS, SPD TRANSIENT VOLTAGE SURGE SUPPRESSER TYP TYPICAL UG, UGND UNDERGROUND UH UNIT HEATER UON UNLESS OTHERWISE NOTED UTIL UTILITY V VOLTS VFD VARIABLE FREQUENCY DRIVE W WIRE, WATT WH WATT-HOUR WP WEATHERPROOF XFMR TRANSFORMER (X) EXISTING TYPICAL ABBREVIATIONS: 1 1 J ## J TV 2 T F WP 4 3 D DESCRIPTIONSYMBOL 2x4 LIGHT FIXTURE, RECESSED OR SURFACE MOUNTED 2x2 LIGHT FIXTURE, RECESSED OR SURFACE MOUNTED 4FT OR 8FT LIGHT FIXTURE, RECESSED OR SURFACE MOUNTED RECESSED LIGHT FIXTURE CEILING FAN, SEE LIGHTING FIXTURE SCHEDULE FOR TYPE TRACK WITH LIGHT KIT UNDER COUNTER LIGHT FIXTURE ELECTRICAL LEGEND 4FT OR 8FT CHANNEL LIGHT FIXTURE, SUSPENDED OR SURFACE MOUNTED DIRECT/INDIRECT FIXTURE, SUSPENDED SURFACE LIGHT FIXTURE WALL MOUNTED LIGHT FIXTURE RECESSED WALL WASH LIGHT FIXTURE EXIT SIGN, SINGLE FACE, CEILING, CHEVRON INDICATES DIRECTION. EXIT SIGN, DOUBLE FACE, CEILING MOUNTED, CHEVRON INDICATES DIRECTION. EXIT SIGN W/EMERGENCY LIGHTING UNIT, CEILING MOUNTED, CHEVRON INDICATES DIRECTION. EMERGENCY LIGHTING UNIT, 2-HEAD WITH BATTERY BACK-UP, WALL MOUNTED, "NOT SWITCHED" PHOTOCELL, REMOTE MOUNTED, 120V, 10 SECOND TIME DELAY, UL WET LOCATION, RATED FOR 1500 W @ 120 VAC AND 4000 W @ 277 VAC (FOR USE WITH LAMP SOURCE(S) SHOWN. EXIT SIGN, SINGLE FACE, WALL/END MOUNTED, CHEVRON INDICATES DIRECTION. EXIT SIGN, DOUBLE FACE, WALL/END MOUNTED, CHEVRON INDICATES DIRECTION. EXIT SIGN W/EMERGENCY LIGHTING UNIT, WALL/END MOUNTED, CHEVRON INDICATES DIRECTION. EMERGENCY LIGHTING UNIT, 2-HEAD WITH BATTERY BACK-UP, CEILING MOUNTED, "NOT SWITCHED" WEATHERPROOF SWITCH, SINGLE POLE 120/277 VAC, 20A, MOUNTED AT 46" AFF UNLESS OTHERWISE NOTED. 3-WAY SWITCH, 120/277 VAC, 20A, MOUNTED AT 46" AFF UNLESS OTHERWISE NOTED SEE ELECTRICAL DEVICES MOUNTING HEIGHT DETAIL. LOWER CASE LETTER INDICATES FIXTURE SWITCHING, WHEN INDICATED. DIMMER SWITCH, 0-10V OR LINE VOLTAGE RATING AS REQUIRED BY LIGHTING FIXTURE(S). LINE VOLTAGE RATED DIMMERS MUST BE 1500W FOR 120 VAC AND 4000W 277VAC MINIMUM. ADJUSTABLE FAN CONTROL, 120/277VAC, SINGLE POLE, 20A, MOUNTED AT 46" AFF UNLESS OTHERWISE NOTED, SEE ELECTRICAL DEVICES MOUNTING HEIGHT DETAIL. LOWER CASE LETTER INDICATES FIXTURE SWITCHING, WHEN INDICATED INDICATES BI-LEVEL SWITCHING, 1 SWITCH SWITCHES OUTSIDE LAMPS, 1 SWITCH SWITCHES INSIDE LAMPS. SEE ELECTRICAL DEVICES MOUNTING HEIGHT DETAIL. LOWER CASE LETTER INDICATES FIXTURE SWITCHING, WHEN INDICATED. SWITCH, SINGLE POLE, 120/277VAC, 20A, MOUNTED AT 46" AFF UNLESS OTHERWISE NOTED, SEE ELECTRICAL DEVICES MOUNTING HEIGHT DETAIL. LOWER CASE LETTER INDICATES FIXTURE SWITCHING, WHEN INDICATED. 4-WAY SWITCH 120/277 VAC, 20A, MOUNTED AT 46" AFF UNLESS OTHERWISE NOTED SEE ELECTRICAL DEVICES MOUNTING HEIGHT DETAIL. LOWER CASE LETTER INDICATES FIXTURE SWITCHING, WHEN INDICATED. DESCRIPTIONSYMBOL MANUAL MOTOR STARTER, ELECTRICAL CONTRACTOR SHALL COORDINATE POLES AND SIZE WITH EQUIPMENT ## = AMPERAGE RATING WHEN INDICATED ON DRAWING COMBINATION DATA/TELEPHONE OUTLET, MOUNTED 18" AFF UNLESS OTHERWISE NOTED. PROVIDE 11/4" CONDUIT TO ABOVE ACCESSIBLE GRID CEILING W/PULL STRING FOR OUTLETS LOCATED BELOW HARD (GYPBOARD) CEILINGS, ROUTE 11/4" CONDUIT TO TELEPHONE/DATA ROOM. #V = NUMBER OF VOICE CONNECTIONS / #D = NUMBER OF DATA CONNECTIONS, IF INDICATED 1V/1D COMBINATION DATA/TELEPHONE OUTLET, RECESSED CEILING MOUNTED (LAY-IN / GYPBOARD) PROVIDE 11/4" CONDUIT TO ABOVE ACCESSIBLE GRID CEILING W/PULL STRING FOR OUTLETS LOCATED BELOW HARD (GYPBOARD) CEILINGS, ROUTE 11/4" CONDUIT TO TELEPHONE/DATA ROOM. #V = NUMBER OF VOICE CONNECTIONS / #D = NUMBER OF DATA CONNECTIONS, IF INDICATED COMBINATION POWER/DATA/TELEPHONE BOX, RECESSED FLOOR MOUNTED (POKE-THROUGH SIMILAR TO HUBBELL S1PT4X4BRS ). PROVIDE BRASS COVER PLATE WITH FLUSH ACCESS COVERS FOR EACH PLUG IN CONNECTION. PROVIDE PULL STRING IN CONDUIT. SEE DETAIL #, SHEET E### 1V/1D 1V/1D 1V/1D COMBINATION POWER/DATA/TELEPHONE BOX, RECESSED FLOOR MOUNTED (CAST-IN-PLACE). PROVIDE BRASS COVER PLATE WITH FLUSH ACCESS COVERS FOR EACH PLUG IN CONNECTION. PROVIDE PULL STRING IN CONDUIT.SEE DETAIL #, SHEET E### #V = NUMBER OF VOICE CONNECTIONS / #D = NUMBER OF DATA CONNECTIONS; 1"CND UNDER SLAB TO NEAREST WALL, STUB ABOVE CEILING #G = GANG FLOOR BOX WITH TWO DUPLEX RECEPTACLES, VOICE AND DATA2G RECESSED SINGLE/DOUBLE GANG BOX WITH BLANK COVER PLATE, MOUNTED 24" AFF, UNLESS OTHERWISE NOTED RECESSED DEDICATED/PICTURE/CLOCK SINGLE OUTLET, 120VAC, 20A, MOUNTED AS INDICATED ON DRAWING. RECEPTACLE, DUPLEX, 120VAC, 20A, MOUNTED 24" AFF, UNLESS OTHERWISE NOTED. (SEE ELECTRICAL MOUNTING HEIGHT DETAIL) RECEPTACLE, DUPLEX, 120VAC, 20A, MOUNTED 6" ABOVE COUNTER TOP OR BACK SPLASH. RECEPTACLE, QUADPLEX, 120VAC, 20A MOUNTED 24"AFF UNLESS OTHERWISE NOTED (SEE ELECTRICAL MOUNTING HEIGHT DETAIL) RECEPTACLE, QUADPLEX, 120VAC, 20A, MOUNTED 6" ABOVE COUNTER TOP OR BACK SPLASH. RECEPTACLE, 250VAC, 2 POLE, 3 WIRE, WALL MOUNTED, SIZE AS INDICATED ON DRAWING RECEPTACLE, 480VAC, 2 POLE, 3 WIRE, WALL MOUNTED, SIZE AS INDICATED ON DRAWING RECEPTACLE, DUPLEX, 120VAC, 20A CEILING MOUNTED (LAY-IN / GYPBOARD / SUSPENDED) RECEPTACLE, DUPLEX, 120VAC, 20A RECESSED FLOOR MOUNTED. UPS FED RECEPTACLE, DUPLEX, 120VAC, 20A, MOUNTED 24" AFF, UNLESS OTHERWISE NOTED. (SEE ELECTRICAL MOUNTING HEIGHT DETAIL) UPS FED RECEPTACLE, QUADPLEX, 120VAC, 20A, MOUNTED 24" AFF, UNLESS OTHERWISE NOTED. (SEE ELECTRICAL MOUNTING HEIGHT DETAIL) CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR, 360° COVERAGE 2 = SECOND CONTACT TO BE PROVIDED FOR CONNECTION TO BUILDING MANAGEMENT CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR, LONG RANGE COVERAGE 2 = SECOND CONTACT TO BE PROVIDED FOR CONNECTION TO BUILDING MANAGEMENT WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR, SINGLE BUTTON ON/OFF CONTROL, 180° COVERAGE, MOUNTED AT 46" AFF UNLESS OTHERWISE NOTED. WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR, DUAL BUTTON ON/OFF CONTROL, 180° COVERAGE, MOUNTED AT 46" AFF UNLESS OTHERWISE NOTED. CABLE TRAY, LADDER TYPE SERVICE POLE, HUBBEL, LEGRAND, OR EQUAL, EXTRUDED ALUMINUM SERVICE POLE, 2-CHANNELS WITH CEILING TRIM, ANODIZED ALUMINUM, MULTI-SERVICE, TWO-CHANNEL POLE WITH (2) KNOCKOUTS, (2) 20AMP RECEPTACLES. ADJUSTABLE T-BAR ASSEMBLY FOR MOUNTING POLES IN MIDDLE OF CEILING. UL LISTED. EACH POWER POLE SHOWN ON PLAN SHALL HAVE PROVISIONS FOR(2) DATA DROPS AND (1) VOICE DROP. CABLE TRAY, CENTER HUNG TYPE DISCONNECT SWITCH, FUSED, HEAVY (GENERAL)DUTY, SIZE AS INDICATED ON DRAWINGS(SIZE AS INDICATED IN THE EQUIPMENT CONNECTION SCHEDULE) ##A = DISCONNECT SIZE / # = NUMBER OF POLES / # = NEMA RATING, /##AF = FUSE SIZE 30A/3/3R, W/ 30AF ENCLOSED BREAKER, HEAVY DUTY, SIZE AS INDICATED ON DRAWINGS ##A = BREAKER SIZE / # = NUMBER OF POLES / # = NEMA RATING, COMBINATION STARTER WITH CIRCUIT BREAKER DISCONNECT, FULL VOLTAGE, NON-REVERSING, (600V, 3P, NEMA)SIZE AS INDICATED ON DRAWINGS "Equip" #AMP HMCP (#HP) NEMA # PANELBOARD, SURFACE OR RECESSED MOUNTED AS SHOWN. SIZE, RATINGS, AND MOUNTING AS INDICATED ON PANEL SCHEDULE. CONTRACTOR IS RESPONSIBLE FOR REQUIRED CLEARANCE IN FRONT OF ELECTRICAL PANEL. SEE NEC TABLE 110.26 WORKING SPACES FOR ADDITIONAL CLEARANCE CONDITIONS. 208/120V 480/277V CONDUIT, HOME RUN TO PANEL BOARD METER ELECTRICAL MOTOR 2 HOUR RATED FIRE WALL 1 HOUR RATED FIRE WALL 3 HOUR RATED FIRE WALL HATCHING INDICATES ITEMS TO BE DEMOLISHED. REMOVE DEVICE, EQUIPMENT, FIXTURE INDICATED, CIRCUIT, AND CONDUIT BACK TO SOURCE UNLESS OTHERWISE NOTED. VARIABLE FREQUENCY DRIVE (VFD) 3 UP/STOP/DN PUSHBUTTON CONTROLLER WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR, 180° COVERAGE 2 = SECOND CONTACT TO BE PROVIDED FOR CONNECTION TO BUILDING MANAGEMENT WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR, DUAL BUTTON ON/OFF CONTROL, 180° COVERAGE, ADDITIONAL POWER SUPPLY FOR FAN OPERATION, MOUNTED AT 46" AFF UNLESS OTHERWISE NOTED. WALL MOUNTED DIGITAL TIMED SWITCH (5 MIN'S TO 12 HR'S), SINGLE BUTTON ON/OFF CONTROL, MOUNTED AT 46" AFF UNLESS OTHERWISE NOTED. JUNCTION BOX - WALL MOUNTED +##" - INDICATES MOUNTING HEIGHT OF DEVICE IN INCHES AFF (if given) JUNCTION BOX - CEILING/ABOVE CEILING MOUNTED JUNCTION BOX - FLOOR MOUNTED TRANSFORMER, SIZE AS INDICATED ON DRAWING WALL MOUNTED DOUBLE GANG BOX FOR TELEVISION MOUNTED AT 72" AFF UNLESS NOTED OTHERWISE. BOX SHALL HAVE DUPLEX RECEPTACLE AND DATA CONNECTIONS FOR TELEVISION AS DIRECTED BYOWNER/CLIENT/TENANT. BOX SHALL BE PASS & SEYMOUR TV2MW OR APPROVED EQUIVALENT. CEILING MOUNTED DOUBLE GANG BOX FOR TELEVISION RECESSED IN CEILING. BOX SHALL HAVE DUPLEX RECEPTACLE AND DATA CONNECTIONS FOR TELEVISION AS DIRECTED BYOWNER/CLIENT/TENANT. BOX SHALL BE PASS & SEYMOUR TV2MW OR APPROVED EQUIVALENT. GROUND BUS, "E" INDICATES ELECTRICAL GROUND BAR, "TG" INDICATES TELECOMMUNICATIONS GROUND BAR WAPWP WIRELESS ACCESS POINT, 1 DATA IN A DUAL GANG BOX WITH A SINGLE GANG PLASTER RING, OWNER SHALL PROVIDE SURGE PROTECTOR AND WAP DEVICE, THE ELECTRICAL CONTRACTOR SHALL INSTALL. WP - LISTED WEATHER-RESISTANT TYPE DEVICE POWER & SWITCH LEG UNSWITCHED LEG FLOOR MOUNTED DATA RACK WALL MOUNTED DATA RACKM PROJECTOR PAN, CEILING MOUNTED WALL MOUNTED CAMERA, 2 GANG JUNCTION BOX, 3/4"CND TO ACCESSABLE CEILING, WP INDICATES WEATHERPROOF, COORDINATE MOUNTING HEIGHT WITH SECUIRITY VENDOR CEILING MOUNTED CAMERA, 2 GANG JUNCTION BOX, 3/4"CND TO ACCESSABLE CEILING WP WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR, PIR TECHNOLOGY OCCUPANCY SENSOR, LOW VOLTAGE (24VDC) 19mA DRAW, WATTSTOPPER CX100-1, LONG RANGE SENSOR. INSTALL WHERE FREE OF OBSTRUCTIONS. WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR, PIR TECHNOLOGY OCCUPANCY SENSOR, LOW VOLTAGE (24VDC) 19mA DRAW, WATTSTOPPER CX100-3, TWO SIDED AISLEWAY. INSTALL WHERE FREE OF OBSTRUCTIONS. WALL MOUNTED SPEAKER CEILING MOUNTED SPEAKER DESCRIPTIONSYMBOL CABLE TRAY, BASKET TYPE WALL MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR, DUAL BUTTON ON/OFF CONTROL WITH 0-10V DIMMING, 180° COVERAGE, MOUNTED AT 46" AFF UNLESS OTHERWISE NOTED. WATTSTOPPER DW-311 OR EQUAL. RECEPTACLE, DUPLEX, GROUND FAULT CIRCUIT INTERRUPTER TYPE, 120VAC, 20A, MOUNTED 24" AFF, UNLESS OTHERWISE NOTED. (SEE ELECTRICAL MOUNTING HEIGHT DETAIL) RECEPTACLE, DUPLEX, GROUND FAULT CIRCUIT INTERRUPTER TYPE, 120VAC, 20A, MOUNTED 6" ABOVE COUNTER TOP OR BACK SPLASH. RECEPTACLE, QUADPLEX, GROUND FAULT CIRCUIT INTERRUPTER TYPE, 120VAC, 20A MOUNTED 24"AFF UNLESS OTHERWISE NOTED (SEE ELECTRICAL MOUNTING HEIGHT DETAIL) RECEPTACLE, QUADPLEX, GROUND FAULT CIRCUIT INTERRUPTER TYPE, 120VAC, 20A, MOUNTED 6" ABOVE COUNTER TOP OR BACK SPLASH. **FOR ALL RECEPTACLE TYPES ABOVE: +XX"- INDICATES MOUNTING HEIGHT OF DEVICE IN INCHES AFF (IF GIVEN) (SEE ELECTRICAL MOUNTING HEIGHT DETAIL) WP - LISTED WEATHER-RESISTANT TYPE DEVICE WITH WEATHERPROOF IN USE COVER TR - TAMPER RESISTANT S - INDICATES THE TOP RECEPTACLE OF THE DEVICE IS CONTROLLED VIA WALL SWITCH H - DEVICE MOUNTED HORIZONTALLY U - USB IN-WALL CHARGER WALL CLNG DEMOLITION KEY NOTE SYMBOL KEY NOTE SYMBOL REVISION DELTA FB 4 GANG FLOOR BOX WITH DUPLEX RECEPTACLE AND DATA CAPABILITIES (CONFIRM WITH OWNER FOR REQUIREMENTS). PROVIDE METALLIC IN-USE COVER (HUBBELL CFB4G30CR OR EQUIVALENT). 2 HOUR RATED FIRE WALL - EXISTING 1 HOUR RATED FIRE WALL - EXISTING 3 HOUR RATED FIRE WALL - EXISTING HAND HOLE, IN GRADE, TIER RATING AS INDICATED ON DRAWING DOOR CONTACTS CARD READER, 2 GANG JUNCTION BOX, 3/4"CND TO ACCESSABLE CEILING, COORDINATE MOUNTING HEIGHT WITH SECUIRITY VENDOR ELECTRIC STRIKE MOTION DETECTOR (TYPE DENOTED) KEYPAD MAGNETIC LOCK WALL TELEPHONE OUTLET, MOUNTED 60" AFF UNLESS OTHERWISE NOTED. PROVIDE 11/4" CONDUIT TO ABOVE ACCESSIBLE GRID CEILING W/PULL STRING FOR OUTLETS LOCATED BELOW HARD (GYPBOARD) CEILINGS, ROUTE 11/4" CONDUIT TO TELEPHONE/DATA ROOM. WALL MOUNTED 120V EMERGENCY OFF PUSH BUTTON WITH RED MUSHROOM STYLE HEAD WITH MANUAL PULL REST, NORMALLY OPEN, WITH CLEAR PROTECTIVE COVER. MOUNTED AT 46" AFF UNLESS OTHERWISE NOTED. EPO 2 START/STOP PUSHBUTTON CONTROLLER 1 BUTTON CONTROLLER WALL MOUNTED PUSH PLATE MOUNTED AT 46" AFF UNLESS OTHERWISE NOTED. OVERHEAD PRIMARY CONDUCTORS OVERHEAD PRIMARY CONDUCTORS - EXISTING OVERHEAD SECONDARY CONDUCTORS OVERHEAD SECONDARY CONDUCTORS - EXISTING UNDERGROUND PRIMARY CONDUCTORS UNDERGROUND PRIMARY CONDUCTORS - EXISTING UNDERGROUND SECONDARY CONDUCTORS UNDERGROUND SECONDARY CONDUCTORS - EXISTING COPPER CLASS 1 CONDUCTOR ON ROOF CONTROL CABLE CONDUIT COPPER CLASS 1 CONDUCTOR BELOW GRADE "A" COPPER AIR TERMINAL IN BRONZE BASE ALUMINUM AIR TERMINAL IN ALUMINUM BASE 226V - STYLE THRU-ROOF CONNECTOR (TYPE T) 230V - STYLE THRU-ROOF CONNECTOR (TYPE T1) "B" ALUMINUM CLASS 1 CONDUCTOR ON ROOF LIGHTNING CONDUCTOR CABLE CONNECTOR"BM" GROUND ROD, COPPER, 3/4"DIA x 10'-0" LONG DESCRIPTIONSYMBOL **FOR ALL LIGHTING FIXTURE TYPES ABOVE: LETTER ADJACENT TO FIXTURE INDICATES FIXTURE TYPE, SEE LIGHTING FIXTURE SCHEDULE GROUNDING ELECTRODE CONDUCTOR, 10' COILED ABOVE GRADE T.S. TEACHERS STATION I.F.P. INTERACTIVE FLAT PANEL (X) OHP (X)OHP UGP (X)UGP OHS (X)OHS UGS (X)UGS G GA UGG C (X) (X) 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 E-001 ELECTRICAL SYMBOLS AND ABBREVIATIONS 2022075.00 11/22/2024 0 11/22/24 ISSUED FOR CONSTRUCTION 11/27/2024 GENERAL NOTES 1. ALL ELECTRICAL WORK SHALL BE IN FULL COMPLIANCE WITH NFPA 70 SPECIFICALLY INCLUDING ART. 500, 501, 513, THE NORTH CAROLINA STATE BUILDING CODE, ALL LOCAL CODES AND ORDINANCES AND IN ACCORDANCE WITH THE REQUIREMENTS OF THE LOCAL AUTHORITY HAVING JURISDICTION. 2. ALL EQUIPMENT PROVIDED BY THE CONTRACTOR SHALL BE LISTED AND LABELED BY A NATIONALLY-RECOGNIZED TESTING AGENCY, ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION, FOR THE CONDITIONS OF INSTALLATION. ALL MATERIAL, EQUIPMENT AND DEVICES SHALL BE NEW CURRENT PRODUCTS OF MANUFACTURERS REGULARLY ENGAGED IN THE PRODUCTION OF SUCH PRODUCTS. EQUIPMENT SHALL BE SUITABLE FOR ITS APPLICATION (E.G. WHEN INSTALLED OUTDOORS, IT SHALL BE WEATHERPROOF, ETC.) 3. THE CONTRACTOR SHALL REVIEW ALL DRAWINGS AND SPECIFICATIONS FOR WORK REQUIREMENTS, THE AMOUNT OF SPACE AVAILABLE FOR ELECTRICAL EQUIPMENT, AND LAYOUT HIS WORK IN A COMPATIBLE AND COMPLEMENTARY MANNER. 4. THE CONTRACTOR SHALL ALSO BE RESPONSIBLE FOR THOROUGHLY FAMILIARIZING HIMSELF WITH ANY CONTRACTUAL REQUIREMENTS AS MAY BE SET FORTH IN THE OTHER DIVISIONS OF THE PROJECT SPECIFICATIONS. 5. UNLESS SPECIFICALLY NOTED OTHERWISE, SYSTEMS PROVIDED OR INSTALLED BY THE ELECTRICAL CONTRACTOR SHALL BE COMPLETE AND FULLY-FUNCTIONING AFTER INSTALLATION. INCIDENTAL COMPONENTS MAY NOT BE SHOWN, AND ALL WORK WHICH MAY BE REASONABLY IMPLIED AS BEING INCIDENTAL TO THIS WORK, BUT REQUIRED FOR THE PROPER OPERATION OF THE EQUIPMENT OR SYSTEM, SHALL BE PROVIDED BY THE CONTRACTOR AND INCLUDED IN THE BID. ADDITIONAL CIRCUITS SHALL BE INSTALLED WHEREVER NEEDED TO CONFORM TO THE SPECIFIC REQUIREMENTS OF EQUIPMENT. 6. TEMPORARY POWER CONNECTIONS AS REQUIRED SHALL BE PROVIDED BY THE CONTRACTOR AND INCLUDED IN THE BID. ALL TEMPORARY EQUIPMENT WIRING SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. THE CONTRACTOR SHALL PROVIDE DETAILS, METHODS, MATERIALS, ETC. FOR REVIEW PRIOR TO MAKING TEMPORARY CONNECTIONS. FURNISH AND INSTALL ALL EQUIPMENT AND MATERIALS INCLUDING CONTROL EQUIPMENT, MOTOR STARTERS, BRANCH AND FEEDER CIRCUIT BREAKERS, PANELBOARDS, TRANSFORMERS, ETC. FOR TEMPORARY POWER. COORDINATE WITH THE ELECTRICAL UTILITY COMPANY AS REQUIRED. 7. THE WORK SHALL INCLUDE COMPLETE TESTING OF ALL EQUIPMENT AND WIRING AT THE COMPLETION OF WORK AND ANY MINOR CORRECTIONS, CHANGES OR ADJUSTMENTS NECESSARY FOR THE PROPER FUNCTIONING OF THE SYSTEM AND EQUIPMENT. 8. ALL EQUIPMENT SHOWN DOTTED OR DASHED IS BY OTHERS OR IS EXISTING, AS NOTED. 9. ALL ELECTRICAL EQUIPMENT SHALL, AT ALL TIMES DURING CONSTRUCTION, BE ADEQUATELY PROTECTED AGAINST MECHANICAL INJURY, OR DAMAGE BY WATER AND/OR THE ELEMENTS. ELECTRICAL EQUIPMENT SHALL NOT BE STORED OUT OF DOORS, BUT SHALL BE STORED IN DRY PERMANENT SHELTERS. IF AN APPARATUS HAS BEEN DAMAGED, OR HAS BEEN SUBJECT TO POSSIBLE INJURY BY WATER OR THE ELEMENTS, SUCH DAMAGE SHALL BE REPLACED AT NO ADDITIONAL COST. 10. DO NOT SCALE ELECTRICAL DRAWINGS. REFER TO THE ARCHITECTURAL DRAWINGS FOR DIMENSIONS. 11. CIRCUIT LAYOUTS ARE NOT INTENDED TO SHOW THE NUMBER OF FITTINGS, OR OTHER INSTALLATION DETAILS. UNLESS NOTED OTHERWISE, THE EXACT ROUTING OF FEEDER AND BRANCH CIRCUIT RACEWAYS AND CABLES IS THE RESPONSIBILITY OF THE CONTRACTOR. RISER AND GENERAL CIRCUIT ARRANGEMENTS ARE SHOWN SCHEMATICALLY/DIAGRAMMATICALLY ONLY. THE CONTRACTOR SHALL ROUTE CONDUITS AS REQUIRED BY THE CONDITIONS OF THE INSTALLATION. 12. UNLESS DIMENSIONED, DEVICE LOCATIONS SHOWN ON THE DRAWINGS ARE APPROXIMATE. ADJUST EXACT LOCATIONS AS REQUIRED TO SERVE THE INTENDED PURPOSE AND TO AVOID CONFLICTS AND INTERFERENCES WITH OTHER TRADES. EXACT DEVICE LOCATIONS SHALL BE AS INDICATED ON THE ARCHITECTURAL DRAWINGS OR AS DIMENSIONED. IF NOT SHOWN ON THE ARCHITECTURAL DRAWINGS OR DIMENSIONED ON THE ELECTRICAL DRAWINGS, VERIFY EXACT LOCATION WITH THE ARCHITECT/ENGINEER PRIOR TO ROUGH-IN. 13. CONDUIT TERMINATING IN PRESSED STEEL BOXES SHALL HAVE DOUBLE LOCKNUTS AND INSULATED BUSHINGS. CONDUITS TERMINATING IN GASKETED ENCLOSURES SHALL BE TERMINATED WITH GROUNDING TYPE CONDUIT HUBS. 14. DEVICE BOXES SHOWN BACK-TO-BACK SHALL BE OFFSET A MINIMUM OF TWELVE (12) INCHES TO REDUCE SOUND TRANSMISSION BETWEEN ROOMS. 15. BRANCH CIRCUIT HOMERUNS SHOWN ON DRAWINGS INDICATE PHASE CONDUCTORS, NEUTRAL, EQUIPMENT GROUND, ISOLATED GROUND CONDUCTORS AS REQUIRED. ADDITIONAL CONDUCTORS REQUIRED FOR CONTROL SHALL BE INCLUDED EVEN IF NOT EXPLICITLY SHOWN. 16. SEAL ALL CONDUIT OPENINGS THROUGH EXTERIOR BUILDING WALLS WATERTIGHT. 17. IN WET LOCATIONS AND EXTERIOR, ALL WIRING DEVICES SHALL BE WEATHER- RESISTANT LISTED WITH WEATHERPROOF WHILE IN USE COVER. LIGHTING FIXTURES SHALL BE APPROPRIATELY RATED AND LISTED FOR THE ENVIRONMENT. 18. RACEWAYS PENETRATING FLOORS, CEILINGS OR WALLS SHALL BE PROPERLY SEALED SMOKETIGHT. 19. RACEWAYS PENETRATING RATED FLOOR, CEILING OR WALL ASSEMBLIES SHALL BE PROPERLY SEALED IN ACCORDANCE WITH THE CORRESPONDING UNDERWRITERS LABORATORIES (OR OTHER APPROVED THIRD PARTY TESTING AGENCY) APPROVED AND LISTED FIRESTOPPING MATERIALS AND MANUFACTURER APPROVED INSTALLATION TECHNIQUES COMPLYING WITH ALL APPLICABLE CODES. SEE ARCHITECTURAL DRAWINGS FOR IDENTIFICATION OF RATED WALLS AND CEILINGS. 20. ALL RACEWAYS SHALL BE CONCEALED WHERE POSSIBLE. 21. INSTALL EXPOSED RACEWAYS PARALLEL TO OR AT RIGHT ANGLES TO NEARBY SURFACES OR STRUCTURAL MEMBERS, AND FOLLOW THE SURFACE CONTOURS AS MUCH AS POSSIBLE. NO DIAGONAL RUNS WILL BE ALLOWED. ALL CONDUITS SHALL BE RUN STRAIGHT AND TRUE. RUN PARALLEL OR BANKED RACEWAYS TOGETHER ON COMMON SUPPORTS WHERE PRACTICAL. MAKE BENDS IN PARALLEL OR BANKED RUNS FROM SAME CENTERLINE TO MAKE BENDS PARALLEL. 22. USE FLUSH MOUNTING OUTLET BOXES IN FINISHED AREAS AND FOR EXTERIOR DEVICES/LIGHT FIXTURES UNLESS NOTED OTHERWISE. 23. PROVIDE AND PLACE ALL SLEEVES FOR CONDUITS PENETRATING WALLS, FLOORS, PARTITIONS, ETC. LOCATE ALL NECESSARY SLOTS FOR ELECTRICAL WORK AND FORM BEFORE CONCRETE IS POURED. 24. PATCHING OF WATERPROOFED SURFACES SHALL RENDER THE AREA OF THE PATCHING COMPLETELY WATERPROOF. 25. ALL MOTORS, DRY TYPE TRANSFORMERS AND OTHER VIBRATING EQUIPMENT SHALL BE CONNECTED TO THE CONDUIT SYSTEM BY MEANS OF A SHORT SECTION (18 INCH MINIMUM) OF FLEXIBLE CONDUIT UNLESS OTHERWISE INDICATED. AN EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED INSIDE THE FLEXIBLE CONDUIT AND TERMINATE AT THE LOAD END WITH AN APPROVED GROUNDING CLAMP OR LUG. 26. SURFACE MOUNTED PANELBOARDS, JUNCTION, OUTLET AND PULL BOXES, RACEWAYS, ETC., INSTALLED ON EXTERIOR SURFACES OR INSIDE ON EXTERIOR WALLS SHALL BE SUPPORTED BY SPACERS TO PROVIDE A 1/4" MINIMUM CLEARANCE BETWEEN THE WALL AND EQUIPMENT. 27. CEILING MOUNTED DEVICES INSTALLED IN ACOUSTICAL TILE CEILING AREAS SHALL BE SUPPORTED FROM THE STRUCTURE ABOVE WITH RODS OF SUFFICIENT SIZE TO PREVENT VERTICAL MOVEMENT OF THE OUTLET BOX. BRIDGES ALONE ARE NOT ADEQUATE UNLESS SPECIFICALLY APPROVED. CEILING MOUNTED EXIT LIGHT FIXTURES SHALL BE INSTALLED LEVEL. DO NOT SUPPORT DEVICES FROM ACCOUSTICAL CEILING TILE. 28. EXCAVATION AND TRENCHING REQUIRED FOR THE INSTALLATION OF ELECTRICAL POWER AND TELECOMMUNICATIONS RACEWAYS SHALL BE PROVIDED BY THE CONTRACTOR IN ACCORDANCE WITH THE REQUIREMENTS OF DIVISION 26 OF THE PROJECT SPECIFICATIONS. 29. PRIOR TO TRENCHING IN ANY AREA, THE CONTRACTOR SHALL CONTACT ELECTRICAL, COMMUNICATIONS/DATA/FIBER, CABLE TELEVISION, GAS AND WATER UTILITY PROVIDERS AND HAVE ALL UTILITIES IN THE AREA IDENTIFIED. DAMAGE TO ANY UNDERGROUND UTILITIES OR STRUCTURES SHALL BE REPAIRED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE PROJECT. 30. ALL UNDERGROUND RACEWAYS SHALL BE IDENTIFIED BY UNDERGROUND LINE MARKING TAPE LOCATED DIRECTLY ABOVE THE RACEWAY AT 6 TO 8 INCHES BELOW FINISHED GRADE. SEE SPECIFICATIONS SECTION 260553. 31. PROVIDE ADHESIVE BACKED RECEPTACLE AND SWITCH/DIMMER/OCCUPANCY SENSOR DEVICE PLATE LABELS IDENTIFYING THE PANEL AND CIRCUIT FEEDING THE DEVICE. LABELS SHALL INDICATE PANEL AND CIRCUIT NUMBER. SEE SPECIFICATIONS SECTION 260553 FOR REQUIREMENTS. 32. FINAL TYPED PANELBOARD DIRECTORIES INSTALLED IN THE PANELBOARD DOOR POCKET SHALL INCLUDE FINAL ACTUAL ROOM NAMES AND NUMBERS IN ADDITION TO THE GENERAL DESCRIPTION SHOWN ON THE PANEL SCHEDULES ON THE DRAWINGS. 33. ALL EQUIPMENT, MATERIALS, AND INSTALLATION TECHNIQUES USED IN AREAS DESIGNATED AS HAZARDOUS ON THE DRAWINGS, SHALL BE IN STRICT ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE ARTICLES 500, 501 AND 513. ALL EQUIPMENT AND MATERIALS USED IN HAZARDOUS AREAS SHALL BE U.L. LISTED FOR THE APPROPRIATE HAZARDOUS AREA CLASSIFICATION. OBSERVE CLASSIFIED AREAS MOUNTING HEIGHT REQUIREMENTS AND PROVIDE CONDUIT SEALING FITTINGS AS REQUIRED BY NFPA 70. 34. CONDUCTOR SIZING IS BASED ON 75 DEGREE C. COPPER NEC RATINGS, UNLESS NOTED OTHERWISE. THE CONTRACTOR SHALL VERIFY, PRIOR TO INSTALLATION OF CONDUCTORS OR CONDUIT FEEDING ANY EQUIPMENT, THE ELECTRICAL EQUIPMENT IS RATED FOR USE WITH 75 DEGREE C. WIRING. IF ANY EQUIPMENT IS RATED FOR USE WITH LESS THAN 75 DEGREE C. CONDUCTORS, THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER IMMEDIATELY FOR EVALUATION/CORRECTION. 35. DO NOT PULL CONDUCTORS UNTIL THE CONDUIT SYSTEM IS COMPLETE IN EVERY DETAIL. IN THE CASE OF CONCEALED WORK, "COMPLETE" MEANS UNTIL ALL ROUGH PLASTERING OR MASONRY HAS BEEN COMPLETED. 36. WHERE SIZE IS NOT SHOWN ON THE DRAWINGS, BRANCH CIRCUITS SHALL CONSIST OF #12 OR #10 AWG MINIMUM PHASE, NEUTRAL AND EQUIPMENT GROUND CONDUCTORS IN 1/2" MINIMUM RACEWAY. 37. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS WITH A TOTAL INSTALLED LENGTH GREATER THAN 75 FEET AND/OR BRANCH CIRCUIT HOMERUNS LONGER THAN 50 FEET, I.E.; #12 AWG INCREASED TO #10 AWG FOR RECEPTACLE BRANCH CIRCUITS OVER 75 FEET TOTAL LENGTH (INCLUDING THE HOMERUN SEGMENT) AND HOMERUNS OVER 50 FEET. IF 277 VOLT CIRCUITS ARE SHOWN, USE #10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS WITH TOTAL INSTALLED LENGTH GREATER THAN 200 FEET AND/OR BRANCH CIRCUIT HOMERUNS LONGER THAN 125 FEET, I.E.; #12 AWG INCREASED TO #10 AWG FOR RECEPTACLE BRANCH CIRCUITS OVER 75 FEET TOTAL LENGTH (INCLUDING THE HOMERUN SEGMENT) AND HOMERUNS OVER 50 FEET. 38. COMMON NEUTRAL BRANCH CIRCUITS ARE NOT PERMITTED. PROVIDE SEPARATE, INDIVIDUAL NEUTRAL CONDUCTORS FOR ALL BRANCH CIRCUITS. 39. KEEP CONDUCTOR SPLICES TO A MINIMUM. INSTALL SPLICES AND TAPES THAT POSSESS EQUIVALENT OR BETTER MECHANICAL STRENGTH AND INSULATION RATINGS THAN CONDUCTORS BEING SPLICED. USE SPLICE AND TAP CONNECTORS COMPATIBLE WITH CONDUCTOR MATERIAL. INSTALL CONDUCTORS AT EACH OUTLET WITH AT LEAST 6 INCHES OF SLACK. CONNECT OUTLETS AND COMPONENTS TO WIRING AND TO GROUND AS INDICATED AND INSTRUCTED BY THE MANUFACTURER. 40. DO NOT SPLICE BRANCH CIRCUIT HOMERUNS WITHOUT THE PERMISSION OF THE ARCHITECT/ENGINEER. HOMERUNS SHALL BE CONTINUOUS FROM THE LAST OUTLET BOX TO THE SERVING PANELBOARD. 41. DO NOT COMBINE BRANCH CIRCUIT HOMERUNS UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS. 42. DO NOT CHANGE CIRCUITING SHOWN WITHOUT PERMISSION OF THE ARCHITECT/ENGINEER. 43. TROUGH TAPS SHALL BE AT SWITCH AMPACITY, UNLESS NOTED OTHERWISE. 44. INSTALL WIRING DEVICES AT HEIGHTS AS SHOWN ON THE DRAWINGS. ALSO COORDINATE MOUNTING HEIGHTS WITH THE ARCHITECTURAL DRAWINGS AND CASEWORK DETAILS. IF CONFLICTING, ARCHITECTURAL DRAWINGS AND DETAILS SHALL GOVERN. 45. PROVIDE GROUND FAULT CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL IN ACCORDANCE WITH THE NEC INCLUDING ALL ELECTRIC WATER COOLERS, EXTERIOR RECEPTACLES AND RECEPTACLES IN AREAS SUBJECT TO POSSIBLE WET CONDITIONS. ALL RECEPTACLES INSTALLED WITHIN 6 FEET OF A SINK SHALL BE GFI PROTECTED. ALL RECEPTACLES IN NON-RESIDENTIAL KITCHENS SHALL BE GFI PROTECTED. 46. IN AREAS IN WHICH DUAL LEVEL SWITCHING IS INDICATED (TYPICALLY BY 2 OR MORE ADJACENT, GANGED SWITCHES), PROVIDE THE APPROPRIATE NUMBER OF CONDUCTORS TO FACILITATE THIS FUNCTION (AS TYPICALLY SHOWN). 47. CONNECT BATTERY PACK TYPE EMERGENCY AND EXIT LIGHTING TO THE UNSWITCHED LIGHTING CIRCUIT SERVING THE SPACE LIGHTED BY THE EMERGENCY AND EXIT FIXTURES. THESE CONNECTIONS ARE INTENTIONALLY NOT SHOWN TO MAINTAIN DRAWING FOR CLARITY. 48. COORDINATE LIGHTING FIXTURE LOCATIONS WITH THE ARCHITECTURAL REFLECTED CEILING PLAN. IF CONFLICTS ARE NOTED, REQUEST CLARIFICATION FROM THE ARCHITECT/ENGINEER BEFORE PROCEDING. 49. ADJACENT SWITCHES SHALL BE GANGED. INSTALL BARRIERS BETWEEN UNLIKE VOLTAGE SECTIONS. 50. SEPARATE NEUTRALS ARE REQUIRED FOR ALL DIMMED LIGHTING CIRCUITS. 51. WHERE THE DRAWINGS INDICATE A LIGHTING FIXTURE IS TO BE PROVIDED WITH SPECIAL FEATURES/SWITCHING (DIMMING, EMERGENCY BATTERY BALLAST, MULTI- LEVEL, ETC), THE CONTRACTOR SHALL PROVIDE THESE FIXTURES WITH THE APPROPRIATE BALLASTING TO ACCOMMODATE THE SPECIAL FEATURE. THE CONTRACTOR SHALL PROVIDE THE FIXTURES AS INDICATED IN THE LIGHTING FIXTURE SCHEDULE WITH MODIFICATIONS AS REQUIRED BY DRAWING NOTES. 52. COORDINATE LOCATIONS OF PLUMBING, MECHANICAL, DATA AND TELEPHONE AND AUDIO/VISUAL EQUIPMENT AND OF OWNER-PROVIDED EQUIPMENT WITH THE RESPECTIVE CONTRACTORS AND VENDORS AND THE OWNER BEFORE ROUGH-IN. ADJUST LIGHTING FIXTURES, RECEPTACLES AND ELECTRICAL EQUIPMENT TO ACCOMMODATE THIS EQUIPMENT. ADVISE THE ARCHITECT/ENGINEER OF CONFLICTS BEFORE ROUGH-IN. 53. BEFORE COMMENCING WORK OR ORDERING MATERIALS, THE CONTRACTOR SHALL COORDINATE WITH OTHER TRADES AND VERIFY THE NAMEPLATE RATINGS OF ALL EQUIPMENT (MOTORS, HEATERS, COMPRESSORS, ETC.) AND ADJUST THE RATINGS OF THE ELECTRICAL EQUIPMENT (SWITCHES, FUSES, CIRCUIT BREAKERS, FEEDERS, ETC.) AS APPROPRIATE TO SERVE THIS EQUIPMENT. 54. ENERGIZE EQUIPMENT ONLY AFTER OBTAINING PERMISSION FROM THE CONTRACTOR PROVIDING THE EQUIPMENT. 55. UNLESS SPECIFICALLY NOTED OTHERWISE, THE ELECTRICAL CONTRACTOR SHALL MAKE FINAL CONNECTIONS TO ALL UTILIZATION EQUIPMENT SHOWN ON THE DRAWINGS. VERIFY THE TYPE OF FINAL CONNECTION AND PROVIDE APPROPRIATE WIRING METHOD. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL, PLUMBING AND GENERAL CONTRACTORS, PRIOR TO ORDERING OR INSTALLATION OF ANY EQUIPMENT, TO VERIFY MECHANICAL AND PLUMBING EQUIPMENT REQUIREMENTS ARE PROVIDED IN THE ELECTRICAL DESIGN. THE CONTRACTOR WILL NOT BE COMPENSATED FOR COSTS ASSOCIATED WITH CHANGING THE ELECTRICAL SYSTEMS TO MATCH UTILIZATION EQUIPMENT, EVEN IF THE ELECTRICAL WORK IS INSTALLED PER THE ELECTRICAL DRAWINGS. 56. THE MECHANICAL AND PLUMBING CONTRACTORS SHALL FURNISH ALL STARTERS AND CONTROLS FOR THEIR EQUIPMENT. THE ELECTRICAL CONTRACTOR SHALL MOUNT STARTERS FURNISHED BY THE MECHANICAL AND PLUMBING CONTRACTORS, THE ELECTRICAL CONTRACTOR PROVIDE ALL SAFETY SWITCHES, WIRING AND CONNECTIONS TO LINE SIDE AND LOAD SIDE OF STARTERS AND SAFETY SWITCHES COMPLETE TO MECHANICAL EQUIPMENT. FOR RESISTANCE TYPE LOADS WHERE STARTERS OR CONTACTORS ARE NOT REQUIRED, THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL POWER WIRING AND CONNECTIONS COMPLETE TO EQUIPMENT. THE MECHANICAL AND PLUMBING CONTRACTORS SHALL PROVIDE ALL CONTROL WIRING AND CONNECTIONS AND DEVICES FOR THEIR EQUIPMENT. 57. THE ELECTRICAL CONTRACTOR SHALL COORDINATE ALL EQUIPMENT TERMINATIONS, PLUGS AND CORDSETS WITH VENDOR EQUIPMENT AND VERIFY ALL DEVICE LOCATIONS FOR SPECIALITY EQUIPMENT WITH CASEWORK PRIOR TO ROUGH-IN. 58. THE LAYOUT AND PLACEMENT OF ELECTRICAL DISTRIBUTION EQUIPMENT IN ELECTRICAL AND MECHANICAL EQUIPMENT ROOMS IS BASED ON PUBLISHED EQUIPMENT SIZES AND SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE. DEVIATIONS FROM CONFIGURATIONS SHOWN IS THE RESPONSIBILITY OF THE CONTRACTOR. PROVIDE NATIONAL ELECTRIC CODE REQUIRED CLEARANCES FOR ALL ELECTRICAL EQUIPMENT, PANELBOARDS, TRANSFORMERS, SAFETY SWITCHES, SWITCHBOARDS, ETC. COORDINATE RESOLUTION OF CONFLICTS WITH OTHER TRADES. ADVISE THE ARCHITECT/ENGINEER OF CONFLICTS BEFORE ROUGH-IN. 59. LAYOUT AND PLACEMENT OF ELECTRICAL DISTRIBUTION EQUIPMENT IN ELECTRICAL AND MECHANICAL EQUIPMENT ROOMS IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR, IF ARRANGEMENT DIFERS FROM THAT SHOWN ON THE DRAWINGS. PROVIDE NATIONAL ELECTRICAL CODE REQUIRED CLEARANCES FOR ALL ELECTRICAL EQUIPMENT, PANELBOARDS, TRANSFORMERS, SAFETY SWITCHES, SWITCHBOARDS, ETC. COORDINATE RESOLUTION OF CONFLICTS WITH OTHER TRADES. 60. COORDINATION WITH THE UTILITY COMPANY FOR PLACEMENT OF THE UTILITY’S FACILITIES AND THE CONTRACTOR’S SERVICE ENTRANCE RACEWAYS AND CONNECTIONS TO THE CONTRACTOR’S SERVICE ENTRANCE CONDUCTORS IS THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR. 61. TELECOMMUNICATIONS AND DATA CABLES WILL BE PROVIDED AND INSTALLED BY THE CONTRACTOR OWNER. LEAVE PULL WIRES OR ROPES OF ADEQUATE TENSILE STRENGTH IN ALL EMPTY CONDUITS. 62. PROVIDE, FIBER AND DATA SERVICE ENTRANCE CONDUIT IN SIZES AND LOCATIONS AS SHOWN ON THE DRAWINGS AND AS REQUIRED BY THE OWNER AND THE SERVICE UTILITIES. UTILITY SERVICE ENTRANCE CABLES WILL BE PROVIDED AND INSTALLED BY THE OWNER'S SERVICE UTILITIES. LEAVE PULL WIRES OR ROPES OF ADEQUATE TENSILE STRENGTH IN ALL EMPTY CONDUITS. 63. EXACT SPACING OF SMOKE DETECTORS SHALL BE FOLLOWED AS CLOSELY AS POSSIBLE WITH POSITIONS SHOWN ON THE DRAWINGS. DETECTOR SPACING IS BASED UPON NFPA 72 INCLUDING APPENDIX A. SLIGHT ADJUSTMENTS MAY BE MADE IN SPACING IF REQUIRED BY FIELD CONDITIONS, BUT SPACING SHALL NOT EXCEED ADA, NFPA AND EQUIPMENT MANUFACTURERS SPACING CRITERIA. DO NOT INSTALL SMOKE DETECTORS WITHIN 3 FEET OF SUPPLY AIR DIFFUSERS OR RETURN GRILLES. PROVIDE FLEX CONDUIT CONNECTION TO SMOKE AND HEAT DETECTORS OF ADEQUATE LENGTH TO ALLOW HORIZONTAL ADJUSTMENT OF FOUR FEET FROM POSITION INDICATED ON DRAWINGS. 64. SHOP DRAWINGS MUST BE SUBMITTED BY THE FIRE ALARM CONTRACTOR COMPLYING WITH THE FIRE ALARM PLAN REVIEW REQUIREMENTS POLICY - JANUARY 2006 BEFORE PERMITTING BY THE WILMINGTON FIRE DEPARTMENT. THESE DRAWINGS DO NOT CONSTITUTE APPROVAL AND MAY CHANGE AFTER A FULL REVIEW BY THE WILMINGTON FIRE DEPARTMENT. A SEPARATE PERMIT MUST BE OBTAINED PRIOR TO INSTALLATION. 65. INSTALLATION INFORMATION PACKED WITH LIGHTING FIXTURES, DEVICES AND EQUIPMENT SHALL BE RETAINED FOR INCLUSION IN THE OPERATIONS AND MAINTENANCE MANUALS. 66. SAFETY: COMPLY WITH OSHA AND NEC ARC FLASH PROTECTION REQUIREMENTS. 67. ALL SWITCHES, RECEPTACLE AND LIGHTS SHALL COMPLY WITH ANSI 117.2 FOR ADA REQUIREMENTS. 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 E-002 GENERAL NOTES 2022075.00 11/22/2024 0 11/22/24 ISSUED FOR CONSTRUCTION 11/27/2024 MB ASPH PARK FLIGHTLINE ROAD CO WV WV FO WV WV WV T D D D D D D D D D PP JJ 2EP1-35 PIV E-100 2 PLAN NORTH TRUE NORTH NN PUSHPLATE AND LOW VOLTAGE CABLE PROVIDED AND INSTALLED BY SECURITY CONTRACTOR 3"DIA x 60" HIGH BOLLARD. BOLLARD MUST EXTEND MIN 36"ABOVE GRADE. PROVIDE SURFACE MOUNTED 2 GANG WEATHERPROOF BOX FOR GATE PUSH TO EXIT, BOLLARD AND WEATHERPROOF BOX PROVIDED BY ELECTRICAL CONTRACTOR 1 1/4"CND UNDERGROUND WITH NYLON PULL STRING DATA: PROVIDE 1 1/4"CND FROM ABOVE LAY-IN CEILING IN CONF RM [106] TO BELOW GRADE AND STUB UP 4" ABOVE GRADE AT GATE GATE POWER, 2 GANG WEATHERPROOF PROVIDED AND MOUNTED BY ELECTRICAL CONTRACTOR (TYP 2) GATE POWER 2EP2-35 GATE FENCE 2EP2-39 NOTE: ELECTRICAL CONTRACTOR MUST COORDINATE FINAL STUB-UP LOCATIONS OF POWER AND DATA CONDUITS, JUNCTION BOXES AND BOLLARD LOCATION WITH GENERAL CONTRACTOR AND OWNERS SECURITY CONTRACTOR PRIOR TO ROUGH-IN AND INSTALLATION. 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1820 FLightline Road Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 E-100 ELECTRICAL SITE PLAN 2022075.00 11/22/2024 3/32" = 1'-0"1 ELECTRICAL SITE PLAN GENERAL NOTES 1 ELECTRICAL CONTRACTOR MUST COORDINATE ALL INDERGROUND UTILITIES PRIOR TO TRENCHING FOR UNDERGROUND ELECTRICAL AND LOW VOLTAGE CONDUITS. 1 EXISTING UTILITY POLE (480V) 480V UNDERGROUND ELECTRICAL PROVIDED BY UTLILTY 480V ABOVE GROUND JUNCTION BOX PROVIDED BY UTLITY CT CABINET AND METER, SEE RISER DIAGRAM ON E-601 HOT BOX POWER D.S. 30A/1/3R, W/ 20AF PANEL 2EP2 PANEL 2EP1 PANEL 4EP1 FACP PROVIDE (2) 2"CND'S UNDERGROUND TO PROPERTY LINE, COORDINATE FINAL LOCATION WITH TELECOM UTILITY BFP TAMPER SW AND PIV SCALE : 3/32" = 1'-0" 0'10'10'5' TELECOM CABINET 1/4" = 1'-0"2 GATE POWER AND DATA PLAN 1 1 0 11/22/24 ISSUED FOR CONSTRUCITON 1 2025.01.31 GFO HANGAR PERMIT SET 01/31/2025 CR CR CR CR CR J J J PP PLAN NORTH TRUE NORTH NN 1 6 3 4 5 2 1.1 5.9 GF.9ABB.1 DC E F HANGAR 100 ENTRY/ LOBBY 101 CONFERENCE 106 PARTS STORAGE 116 ELEC/ IT 114 OPEN OFFICE 103 RISER 115 OFFICE 105 CORR 110 RESTROOM 107 RESTROOM 108 JAN 109 BREAK 111 CLOSET 112 CORR 102 HYDRAULIC DOOR #2 D.S. 60A/3/1, W/ 60AF HYDRAULIC DOOR #1 D.S. 60A/3/1, W/ 60AF 4EP1 T-2EP1 2EP1 EP401 1 EP401 2 WP WP WP WP WP HYD POWER UNIT (480V, 125A PIN & SLEEVE) AC PCU (480V, 100A PIN & SLEEVE) TUG CHARGER D.S. (480V, 100A PIN & SLEEVE) PORTABLE AC UNIT (208V, 60A PIN & SLEEVE) AC PCU (480V, 100A PIN & SLEEVE) PORTABLE AC UNIT (208V, 100A PIN & SLEEVE) AC PCU (480V, 100A PIN & SLEEVE) PORTABLE AC UNIT (60A PIN & SLEEVE) AC PCU (100A PIN & SLEEVE) 2EP2-1 2EP2 REFRIGERATED CABINET AGR 1002 ICE MAKER 8985 2EP2-8 2EP2-10 2EP2-3 WP 2EP1-23 2EP2-5 2EP2-12 4EP1-2,4,6 2EP2-7,9 3#4 & 1#8GND- 1"CND 2#6 & 1#8GND- 3/4"CND 4EP1-13,15,17 3#6 & 1#8GND- 1"CND 4EP1-8,10,12 3#6 & 1#8GND- 1"CND 2#6 & 1#8GND- 3/4"CND 2EP2-14,16 3#4 & 1#8GND- 1"CND 4EP1-19,21,23 2EP2-17,19 2#6 & 1#8GND- 3/4"CND 4EP1-14,16,18 3#4 & 1#8GND- 1"CND 4EP1-25,27,29 3#3 & 1#8GND- 1 1/4"CND 4EP1-20,22,24 4EP1-31,33,35 FIRST RESPONDERS CABINET 3#4 & 1#8GND- 1"CND 3#1 & 1#6GND- 1 1/4"CND FACP AC-01 D.S. 100A/3/1, W/ 70AF 2EP1-8,10,12 3#4 & 1#10GND- 1"CND CT CABINET METER SPDSPD HYD POWER UNIT D.S. 200A/3/3R, W/ 125AF HINGED TELECOM CABINET TELECOM BACKBOARD WAP CAM-1CAM-2 CAM-3 CAM-4 CAM-5 CAM-6 CAM-7 2EP1-39 SIGN VIA PHOTOCELL #3, SEE EL101 FOR LOCAITON SIGN VIA PHOTOCELL #4, SEE EL101 FOR LOCAITON 2EP1-43 SIGN 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1820 FLightline Road Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 EP101 ELECTRICAL FLOOR PLAN - POWER 2022075.00 11/22/2024 1 1/8" = 1'-0"1 FLOOR PLAN - POWER KEYNOTES 1 HYDRAULIC DOOR: THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR OBTAINING THE LATEST DRAWINGS FOR PURCHASED EQUIPMENT FROM THE HYDRAULIC DOOR PROVIDER. THE ELECTRICAL CONTRACTOR MUST COORDINATE ALL EQUIPMENT VOLTAGES, RECOMMENDED BREAKER RATINGS, MANUFACTURERS RECOMMENDED FUSE SIZES, DOOR CONTROLS, CONDUIT, CABLE AND CONDUCTOR INSTALLATION REQUIREMENTS FOR THIS PROJECT. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND INSTALLING ALL EQUIPMENT REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. NOTIFY THE ARCHITECT / ENGINEER IF PURCHASED EQUIPMENT DIFFERS FROM THE INFORMATION PROVIDED IN THIS DESIGN. 2 CONTRACTOR MUST COORDINATE ALL RECEPTACLE CONFIGURATIONS FOR AIRCRAFT SUPPORT EQUIPMENT WITH OWNER BEFORE ROUGH-IN AND PROCUREMENT OF DEVICES. CONTRACTOR MUST CONTACT ENGINEER FOR DIRECTION IF EQUIPMENT PURCHASED DOES NOT HAVE SAME ELECTRICAL CHARACTERISTICS AS DESIGNED. 0'8'4'8' SCALE : 1/8" = 1'-0" # 1 1. ALL RECEPTACLE OUTLETS LOCATED IN THE BAY AND OFFICE AREAS MUST BE MOUNTED AT 24" ABOVE FINISHED FLOOR TO THE BOTTOM OF THE OUTLET. RECEPTACLE NOTE 2 2 2 2 2 2 2 2 2 1 1 0 11/22/24 ISSUED FOR CONSTRUCITON 1 2025.01.31 GFO HANGAR PERMIT SET 01/31/2025 M M M M M M M M M M 1 6 3 4 5 2 1.1 5.9 GF.9ABB.1 DC E F GWH1 HP01 AH01 RH01 RH02 RH03 RH04 F01 F02 SF01 SF02 EF01 EF02 EUH01 DAH01 DHP01 HANGAR 100 ENTRY/ LOBBY 101 CONFERENCE 106 PARTS STORAGE 116 ELEC/ IT 114 OPEN OFFICE 103 RISER 115 OFFICE 105 CORR 110RESTROOM 107 RESTROOM 108 JAN 109 BREAK 111 CLOSET 112 CORR 102 2EP1 2EP24EP1 FACP 2EP1-31,33 HP01 D.S. 60/2/3R, W/ 60AF 2#6 & 1#10GND- 3/4"CND 2#12 & 1#12GND- 3/4"CND GWH1 D.S. 30/1/3R, W/ 15AF 2EP1-29 AH01 D.S. 60/3/1, W/ 50AF (ABOVE CEILING AT UNIT) 2#6 & 1#10GND- 3/4"CND 2EP2-20 2EP1-34,36,38 2EP1-40,42 DHP01 D.S. 60/2/1, W/ 35AF 2#8 & 1#10GND- 3/4"CND 2EP2-22 2#12 & 1#12GND- 3/4"CND ELECTRICAL CONTRACTOR MUST PROVIDE CONDUIT AND CONDUCTORS AS REQUIRED TO THE INDOOR UNIT PER MANUFACTURERS REQUIREMENTS 2EP2-13 2#12 & 1#12GND- 3/4"CND 2EP2-26 2EP2-30 SF01 D.S. SF02 D.S. EF01 D.S.EF02 D.S. 2EP2-15 RH02 D.S.RH04 D.S. RH01 D.S.RH03 D.S. F01 CONTROL SWITCH, PROVIDED BY MECHANICAL INSTALLED BY ELECTRICAL CONTRACTOR 2EP2-23,25,27 F02 CONTROL SWITCH, PROVIDED BY MECHANICAL INSTALLED BY ELECTRICAL CONTRACTOR 2EP2-29,31,33 3#12 & 1#12GND- 3/4"CND 3#12 & 1#12GND- 3/4"CND 2#12 & 1#12GND- 3/4"CND 2#12 & 1#12GND- 3/4"CND (ENTIRE CIRCUIT) 2#12 & 1#12GND- 3/4"CND 2#12 & 1#12GND- 3/4"CND PLAN NORTH TRUE NORTH NN 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 EP102 ELECTRICAL FLOOR PLAN - HVAC POWER 2022075.00 11/22/2024 1/8" = 1'-0"1 FLOOR PLAN - HVAC POWER 0 11/22/24 ISSUED FOR CONSTRUCTION 0'8'4'8' SCALE : 1/8" = 1'-0" 11/27/2024 1 6 3 4 5 2 1.1 5.9 GF.9A BB.1 DC E F CR CR CR CR CR 1 6 3 4 5 2 1.1 5.9 GF.9ABB.1 DC E F #4/0 BARE COPPER CONDUCTOR 36" BELOW GRADE MIN. (TYPICAL) AIRCRAFT STATIC GROUNDING RECEPTACLE (TYPICAL) #4/0 BARE COPPER CONDUCTOR 36" BELOW GRADE MIN. (TYPICAL) EXOTHERMIC CABLE TO CABLE CONNECTOR (TYPICAL) UGG UGG UGG UGG UGG UGG UGG UGG UGG UGG UGG U G G UGG UGG UGG UGGUGGUGGUGGUG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UG G UGG UGG UGG UGG UGG UGG UGG UGG UGGUGGUGGUGGUGGUGGUGG UGG UGG UGG UGG UGG UGG UGG UGG UGGUGGUGGUGGUGGUGGUGG UGG UGG UGG UGG UGG UGG UGG UGG UGGUGGUGGUGGUGGUGGUGG UGG UGG UGG UGG UGG UGG UGG UGG UGG UGG UGGUGGUGGUGGUGGUGGUGG U G GUGG5-0" (TYPICAL) 5' - 0 " ( T Y P I C A L ) E-502 6 TW TW E-502 8 E-502 6 EXOTHERMIC CABLE TO STRUCTURAL STEEL CONNECTION (TYPICAL) UG G UG G UG G E-502 10 PLAN NORTH TRUE NORTH NN 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 EP103 ELECTRICAL FLOOR PLAN - GROUNDING 2022075.00 11/22/2024 1/8" = 1'-0"1 FLOOR PLAN - GROUNDING 0 11/22/24 ISSUED FOR CONSTRUCTION 0'8'4'8' SCALE : 1/8" = 1'-0" 11/27/2024 1 6 3 4 5 2 1.1 5.9 GF.9A BB.1 DC E F CR CR CR CR CR LOWER ROOF STANDING SEAM METAL ROOF SYSTEM A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G G DOWN LEADER WITH #4/0 BARE COPPER CONDUCTOR TO GROUND LOOP 36" BELOW GRADE MIN. (TYPICAL) DOWN LEADER WITH #4/0 BARE COPPER CONDUCTOR TO GROUND LOOP 36" BELOW GRADE MIN. (TYPICAL) DOWN LEADER WITH #4/0 BARE COPPER CONDUCTOR TO GROUND LOOP 36" BELOW GRADE MIN. (TYPICAL) DOWN LEADER WITH #4/0 BARE COPPER CONDUCTOR TO GROUND LOOP 36" BELOW GRADE MIN. (TYPICAL) E-502 5 (TYP.) E-502 9(TYP.) PLAN NORTH TRUE NORTH NN 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 EP104 ELECTRICAL FLOOR PLAN - LIGHTNING PROTECTION 2022075.00 11/22/2024 1/8" = 1'-0"1 FLOOR PLAN - LIGHTNING PROTECTION 0 11/22/24 ISSUED FOR CONSTRUCTION 0'8'4'8' SCALE : 1/8" = 1'-0" 1. LIGHTNING PROJECTION SYSTEM MUST BE INSTALLED IN ACCORDANCE WITH NFP780. 2. COMPLETED SYSTEM MUST HAVE A UL MASTER LABEL. 3. IF DOWN CONDUCTORS ARE INSTALLED ON EXTERIOR OF BUILDING THEY MUST BE PROTECTED IN CONDUIT AND THE CONDUIT PAINTED TO MATCH BUILDING EXTERIOR AS CLOSELY AS POSSIBLE. LIGHTNING PROTECTION NOTES 11/27/2024 1 6 3 4 5 2 1.1 5.9 GF.9ABB.1 DC E F SEE NOTE 2 ABOVE SEE NOTE 3 ABOVE SEE NOTE 4 ABOVE SEE NOTE 4 ABOVE SEE NOTE 2 ABOVE SEE NOTE 3 ABOVE PLAN NORTH TRUE NORTH NN 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 EP105 ELECTRICAL FLOOR PLAN - HAZARDOUS LOCATION BOUNDRIES 2022075.00 11/22/2024 1/8" = 1'-0"1 FLOOR PLAN - HAZARDOUS LOCATION BOUNDRIES 0 11/22/24 ISSUED FOR CONSTRUCTION 0'8'4'8' SCALE : 1/8" = 1'-0" FLOOR PLAN SHEET NOTES 1. ALL WIRING MATERIALS AND METHODS SHALL BE IN COMPLIANCE WITH NEC ARTICLE 513, AIRCRAFT HANGERS. 2. ALL AREAS ABOVE GRADE WITHIN THIS BOUNDARY IS CLASS 1, DIVISION 2. THIS BOUNDARY EXTENDS VERTICALLY 5 FEET ABOVE HIGHEST ENGINE OR WING. 3. ALL AREAS ABOVE GRADE WITHIN THIS BOUNDARY IS CLASS 1, DIVISION 2 TO A HEIGHT OF 18". 4. ALL AREAS BELOW GRADE IS CLASS 1, DIVISION 1. 5. THE OFFICE AND PARTS STORAGE AREAS ARE DESIGNED TO BE VENTILATED AT MORE THAN FOUR AIR CHANGES PER HOUR AND ARE DESIGNED TO BE UNDER POSITVE PRESSURE. BASED ON THIS, THE HAZARDOUS AREA DOES NOT EXTEND INTO THE OFFICE AND PARTS STORAGE AREAS. 11/27/2024 48" 48" 78"44"44" 44" 44"44" 40" 60" 60" 60" 60" 40" 60" J PLAN NORTH TRUE NORTH NN 1 2 1.1 A BB.1 PARTS STORAGE 116 ELEC/ IT 114 RISER 115 CORR 110 RESTROOM 108 JAN 109 BREAK 111 CLOSET 112 2EP14EP1 T-2EP1 PLYWOOD TELEPHONE BACKBOARD REFRIG DISHCOFFEE MICRO 2EP1-1 2EP1-3 2EP1-5 2EP1-7 2EP1-9 2EP1-13 2EP1-15 2EP1-17 2EP1-19 2EP1-11 2EP1-14 2EP2 FIRST RESPONDERS CABINET (ABOVE) BATTERY CABINET (BELOW) 2EP1-25 2EP1-27 FACP 2EP1-32 SPD SPD SPD CT CABINET E-602 4 CONTINUED ON PLAN 2 THIS SHEETS HINGED TELECOM CABINETMETER 6 3 4 5 5.9 A BB.1 ENTRY/ LOBBY 101 CONFERENCE 106 OPEN OFFICE 103 OFFICE 105 CORR 110 RESTROOM 107 RESTROOM 108 JAN 109 CLOSET 112 CORR 102 FB 2EP1-16 2EP1-18 2EP1-20 2EP1-24 2EP1-22 2EP1-26 2EP1-28 2EP1-30 2EP1-21 E-502 11 WAP WAP E-502 12 E-502 12 WAP WAP 2EP1-37 SIGN, COORDINATE EXACT LOCATION OF SIGN WITH OWNER PRIOR TO ROUGH-IN AND INSTALLATION 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 EP401 ELECTRICAL ENLARGED PLANS -POWER 2022075.00 11/22/2024 1/4" = 1'-0"1 ENLARGED FLOOR PLAN - POWER 1 1/4" = 1'-0"2 ENLARGED FLOOR PLAN - POWER 2 CONTINUED ON PLAN 1 THIS SHEET SCALE : 3/32" = 1'-0" 0'10'10'5' 0 11/22/24 ISSUED FOR CONSTRUCTION 11/27/2024 OD O OS OS OS OS OD OF OS OF O D OD OD DD OD 3 3 ODOD D D PE PE T D D OF OS OS PE PE PE 1 6 3 4 5 2 1.1 5.9 GF.9ABB.1 DC E F HANGAR 100 ENTRY/ LOBBY 101 CONFERENCE 106 PARTS STORAGE 116 ELEC/ IT 114 OPEN OFFICE 103 RISER 115 OFFICE 105 CORR 110 RESTROOM 107 RESTROOM 108 JAN 109 BREAK 111 CLOSET 112 CORR 102 A BB B C CE C C C C C C C C B B B BB B B B B B A A A A A A A A A A A AA A A A A B A A A D D D D D D D H H H H H H H H H H H H H H H H B B EF04 EF03 2EP14EP1 2EP2 FACP 4EP1-26 4EP1-28 2EP2-32 F 2EP2-34 K K K K K 4EP1-37 4EP1-32 L L L L L L L L L L L L MOUNT PHOTOCELL #1 AS HIGH ON WALL AND BELOW EAVE AS POSSIBLE VIA PE #1 4EP1-30 MOUNT PHOTOCELL #2 AS HIGH ON WALL AND BELOW EAVE AS POSSIBLE VIA PE #2 X1 X2G X3 X3 X3 X3 E E E E E MOUNT FIXTURE ABOVE FIRE DOOR (~11'-0"AFF) E E E E E E E E E E E E E E E E E E J J J J J J J J J M MM M P P EF05 D TYPE D FIXTURE AND SWITCH MOUNTED IN ATTIC TYPE P FIXTURE MOUNTED ON ROOF, SEE ARCHITECTURAL PLAN/DETAILS FOR MOUNTING TYPE P FIXTURE MOUNTED ON ROOF, SEE ARCHITECTURAL PLAN/DETAILS FOR MOUNTING E D X1 X1 MOUNT PHOTOCELL #3 AS HIGH ON WALL AND BELOW CANOPY AS POSSIBLE VIA PE #3 MOUNT PHOTOCELL #3 AS HIGH ON WALL AND BELOW EAVE AS POSSIBLE MOUNT PHOTOCELL #4 AS HIGH ON WALL AND BELOW EAVE AS POSSIBLE PLAN NORTH TRUE NORTH NN 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1820 FLightline Road Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 EL101 ELECTRICAL FLOOR PLAN - LIGHTING 2022075.00 11/22/2024 1/8" = 1'-0"1 FLOOR PLAN - LIGHTING 0'8'4'8' SCALE : 1/8" = 1'-0" 1 0 11/22/24 ISSUED FOR CONSTRUCITON 1 2025.01.31 GFO HANGAR PERMIT SET 01/31/2025 SUSPENDED CEILING WALL DEDICATED SPACE CONTINUES THROUGH SUSPENDED CEILING PER N.E.C. ARTICLE 110-26 EXCLUSIVELY DEDICATED SPACE OF 6 FEET. ANY FOREIGN SYSTEMS TO THE ELECTRICAL EQUIPMENT SHALL NOT RUN WITHIN THE 6 FEET ABOVE THE ELECTRICAL EQUIPMENT LIGHT FIXTURE STRUCTURAL CEILING ELECTRICAL EQUIPMENT ELECTRICAL DEDICATED SPACE NOTE: THIS FIGURE ILLUSTRATES THE ADDITIONAL EXCLUSIVELY DEDICATED SPACE REQUIRED OVER AND UNDER THE ELECTRICAL EQUIPMENT FOR THE CABLES, RACEWAYS, ETC...TO AND FROM THE ELECTRICAL EQUIPMENT REQUIRED BY SECTION 110-26 OF THE NATIONAL ELECTRICAL CODE. "EQUIPMENT NAME" SOURCE: PANEL "###" SOURCE LOCATION "###" RATING: ### AMPS VOLTAGE: ### / ###V, #Ø, #W MACHINE SCREW WITH ACORN NUT AND LOCKWASHER, TYP. VOLTAGE & PHASE DESIGNATION 1/4" WHITE ENGRAVED LETTERS EQUIPMENT DESIGNATION 3/8" WHITE ENGRAVED LETTERS SOURCE DESIGNATION 1/4" WHITE ENGRAVED LETTERS RATING DESIGNATION 1/4" WHITE ENGRAVED LETTERS NOTE: SEE SPECS. SECTION 260553 FOR NAMEPLATE MATERIAL AND ENGRAVING COLORS. 2 3 / 4 " LENGTH AS REQUIRED SOURCE LOCATION DESIGNATION 1/4" WHITE ENGRAVED LETTERS PANEL: NAME SOURCE: PANEL "###" RATING: ### AMPS VOLTAGE:208/120V, 3Ø, 4W MAXIMUM FAULT CURRENT XX,XXX A RMS BASED ON DATA FROM UTILITY CO., MM-DD-2022 PANEL DESIGNATION 3/8" WHITE ENGRAVED LETTERS SOURCE DESIGNATION RATING DESIGNATION VOLTAGE & PHASE DESIGNATION NOTE: SEE SPECS. SECTION 260553 FOR NAMEPLATE MATERIAL AND ENGRAVING COLORS. MACHINE SCREW WITH ACORN NUT AND LOCKWASHER, TYP. 3 1 / 2 " M I N . O R HE I G H T A S RE Q U I R E D PROVIDE ACTUAL VALUE AND DATE WHEN AVAILABLE FROM THE UTILITY COMPANY **ALL LETTERS MUST BE 1/4" WHITE ENGRAVED UNLESS NOTED OTHERWISE** WARNING Arc Flash and Shock Hazard Appropriate PPE required 1 7 / 8 " M I N I M U M 4 1/2" MINIMUM BLACK LETTERS AND SYMBOL ON SAFETY ORANGE BACKGROUND LETTER COLORS, SEE SPECIFICATIONSNOTES: 1. LABEL SHOWN CAN BE SOURCED FROM SAFETYSIGN.COM, OTHER SUPPLIERS ARE COMPLIANTSIGNS.COM & SETON.COM 2. THIS WARNING LABEL MINIMALLY COMPLIES WITH NEC, HOWEVER IF ELECTRICAL EQUIPMENT IS LIKELY TO REQUIRE EXAMINATION OR MAINTENANCE WHILE ENERGIZED A DETAILED SHORT CIRCUIT AND ARC FLASH HAZARD ANALYSIS IS RECOMMENDED. TABLE 110.26(A)(1) - WORKING SPACES NOMINAL VOLTAGE TO GROUND CONDITION 1 MINIMUM CLEAR DISTANCE (FEET) 0 - 150 151 - 600 NOTE: WHERE THE "CONDITIONS" ARE AS FOLLOWS: CONDITION 1 - EXPOSED LIVE PARTS ON ONE SIDE OF WORKING SPACE AND NO LIVE OR GROUNDED PARTS ON THE OTHER SIDE OF THE WORKING SPACE, OR EXPOSED LIVE PARTS ON BOTH SIDES OF THE WORKING SPACE THAT ARE EFFECTIVELY GUARDED BY INSULATING MATERIALS. CONDITION 2 - EXPOSED LIVE PARTS ON ONE SIDE OF THE WORKING SPACE AND GROUNDED PARTS ON THE OTHER SIDE OF WORKING SPACE. CONCRETE BRICK, OR TILE WALLS SHALL BE CONSIDERED GROUNDED. CONDITION 3 - EXPOSED LIVE PARTS ON BOTH SIDES OF THE WORK SPACE 6' - 6 " M I N . 30" MIN. OR WIDTH OF EQUIP.S E E T A B L E "A " T H I S D I S T A N C E SUSPENDED CEILIN G W ALL CONDITION 2 CONDITION 3 601 - 1000 900mm (3 ft) 1.2 m (4 ft.) 1.5 m (5 ft.) 900mm (3 ft) 900mm (3 ft) 900mm (3 ft) 900mm (3 ft) 1.0m (3 ft 6 in.) 1.2 m (4 ft.) ELECTRICAL EQUIPMENT PLANE OF FRONT EDGE OF ELECTRICAL EQUIPMENT EXCLUSIVELY DEDICATED SPACE LIG HT FIXTURE STRUCTURAL CEILIN G SERVICE EQUIPMENT GROUND BAR TO FOOTING REINFORCING STEEL TO SERVICE EQUIPMENT ENCLOSURES-SIZE PER NEC 250-102(C)(1) SERVICE EQUIPMENT NEUTRAL BAR TO TELEPHONE BACKBOARDS TO DRY TYPE TRANSFORMERS T1 & T2 COLD WATER SERVICE ENTRANCE SUPPLY SIDE ALL GROUND CABLES SHALL BE SIZE 2/0 AWG (GREEN) UNLESS OTHERWISE SPECIFIED BUILDING STRUCT. STEEL EQUIPMENT GROUND CONDUCTORS SIZED PER NEC 250-122 GROUNDING BUSHING ON METALLIC CONDUITS, TYPICAL GROUND CLAMP UL APPROVED, TYPICALJUMPER VALVE, METER OR UNION EXOTHERMIC WELD OR APPROVED GROUND CLAMP3/4" X 10' GROUND ROD IN WELL W/ COVER. BRAZED CONNECTION JUMPER SIZED PER NEC TABLE 250-102(C)(1) 10'-0" MIN. #250kcmil GND SYSTEM GROUND "DO NOT REMOVE"#2/0 CU CONDUCTORS PER NEC OR AS SPECIFIED, WHICHEVER IS LARGER GROUNDING BUSHING FOR METALLIC RACEWAYS EACH END, TYPICAL SERVICE EQUIPMENT GROUND BAR 1/4"x2"x LENGTH AS REQUIRED (12" MIN.), COPPER BAR SUPPORTED BY HEAVY DUTY STANDOFF INSULATORS BOLTED TO WALL BOLT, NUT & BELLEVILLE WASHER, TYPICAL BLACK LAMICORE LABEL, WHITE CORE, TY-WRAPPED TO GROUND CONDUCTORS, TYPICAL CONDUCTORS PER NEC, TYP. CONDUIT GROUNDING BUSHING COMPRESSION LUG, TYPICAL 'NAME' 'WARNING' 'WORKING SPACE' E-501 2 E-501 3 E-501 4 DANGER AREA IN FRONT OF THIS ELECTRICAL PANEL MUST BE KEPT CLEAR FOR 36 INCHES OSHA - NEC REGULATIONS WHITE LETTERS ON RED BACKGROUND BLACK LETTERS ON WHITE BACKGROUND MODIFY CLEARANCE REQUIREMENT PER INSTALLATION UV INKS SCREEN PRINTED ON PRESSURE SENSITIVE POLYESTER, OVERLAMINATED WITH CLEAR POLYESTER 5" MINIMUM 3- 1 / 4 " M I N I M U M VOLTAGE & PHASE DESIGNATION 1/4" WHITE ENGRAVED LETTERS TRANSFORMER DESIGNATION 3/8" WHITE ENGRAVED LETTERS MACHINE SCREW WITH ACORN NUT AND LOCKWASHER, TYP. NOTE: SEE SPECS. SECTION 260553 FOR NAMEPLATE MATERIAL AND ENGRAVING COLORS. TRANSFORMER: "NAME" SOURCE:PANEL "###" SOURCE LOCATION "###" RATING:### AMPS VOLTAGE: 480/277V, 3 Ø, 4W 2 3 / 4 " LENGTH AS REQUIRED SOURCE LOCATION DESIGNATION 1/4" WHITE ENGRAVED LETTERS RATING DESIGNATION 1/4" WHITE ENGRAVED LETTERS SOURCE DESIGNATION 1/4" WHITE ENGRAVED LETTERS 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 E-501 ELECTRICAL DETAILS 2022075.00 11/22/2024 NO SCALE7 DEDICATED SPACE FOR ELECTRICAL EQUIPMENT N.E.C. ARTICAL 1101 NO SCALE5NAME PLATE - EQUIPMENT NO SCALE2NAME PLATE - PANELBOARD NO SCALE3NAME PLATE - WARNING NO SCALE8WORKING CLEARANCE FOR ELECTRICAL EQUIPMENT NO SCALE9GROUNDING DETAIL - SERVICE NO SCALE10EQUIPMENT GROUND BAR DETAIL (EGB) NO SCALE1 NAME PLATE - REQUIRED PANELBOARD NAMEPLATE AND LABELS DETAIL NO SCALE4NAME PLATE WORKING SPACE NO SCALE6NAME PLATE - TRANSFORMER 0 11/22/24 ISSUED FOR CONSTRUCTION 11/27/2024 SS SM S SDS SECTION A-A A A 1A 3 2 1B System No WL1054 1. WALL ASSEMBLY -- THE 1 OR 2 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300A OR U400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. STUDS -- WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY 4 IN. LUMBER SPACED 16 IN. OC. STEEL STUDS TO BE MIN 2-1/2 IN. WIDE AND SPACED MAX 24 IN. OC. WHEN STEEL STUDS ARE USED AND THE DIAM OF OPENING EXCEEDS THE WIDTH OF STUD CAVITY, THE OPENING SHALL BE FRAMED ON ALL SIDES USING LENGTHS OF STEEL STUD INSTALLED BETWEEN THE VERTICAL STUDS AND SCREW-ATTACHED TO THE STEEL STUDS AT EACH END. THE FRAMED OPENING IN THE WALL SHALL BE 4 TO 6 IN. WIDER AND 4 TO 6 IN. HIGHER THAN THE DIAM OF THE PENETRATING ITEM SUCH THAT, WHEN THE PENETRATING ITEM IS INSTALLED IN THE OPENING, A 2 TO 3 IN. CLEARANCE IS PRESENT BETWEEN THE PENETRATING ITEM AND THE FRAMING ON ALL FOUR SIDES. B. GYPSUM BOARD* -- 5/8 IN. THICK, 4 FT WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 32-1/4 IN. FOR STEEL STUD WALLS. MAX DIAM OF OPENING IS 14-1/2 IN. FOR WOOD STUD WALLS. THE F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE FIRE RATING OF THE WALL ASSEMBLY. 2. THROUGH-PENETRANTS -- ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE SHALL BE MIN 0 IN. TO MAX 2-1/4 IN. PIPE MAY BE INSTALLED WITH CONTINUOUS POINT CONTACT. PIPE, CONDUIT OR TUBING MAY BE INSTALLED AT AN ANGLE NOT GREATER THAN 45 DEGREES FROM PERPENDICULAR. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED: A. STEEL PIPE -- NOM 30 IN DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE. B. IRON PIPE -- NOM 30 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE. C. CONDUIT -- NOM 4 IN DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR 6 IN. DIAM STEEL CONDUIT. D. COPPER TUBING -- NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING. E. COPPER PIPE -- NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE. 3. FILL, VOID OR CAVITY MATERIAL* -- SEALANT -- MIN 5/8 IN. (16 MM) THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. AT THE POINT OR CONTINUOUS CONTACT LOCATIONS BETWEEN PIPE AND WALL, A MIN 1/2 IN. (13 MM) DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE PIPE WALL INTERFACE ON BOTH SURFACES OF WALL . HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- FS-ONE SEALANT *INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR CUL CERTIFICATION MARK FOR JURISDICTIONS EMPLOYING THE UL OR CUL CERTIFICATION (SUCH AS CANADA), RESPECTIVELY. F Ratings - 1 and 2 Hr (See Items 1 & 3) T Ratings - 0 Hr L Ratings at Ambient - Less Than 1 CFM / sq ft L Ratings at 400 F - Less Than 1 CFM / sq ft ANSI / UL1479 (ASTM E814) October 14, 2015 F Ratings - 1 and 2 Hr (See Items 1 & 3) FT Ratings - 0 Hr FH Ratings - 1and 2 HR (See Items 1 and 3) FTH Ratings - 0 Hr CAN / ULC S115 FTH Ratings - 0 Hr L Rating at Ambient - Less Than 1 CFM / sq ft L Ratings at 400 F - Less Than 1 CFM / sq ft PVC SLEEVE 10' GROUND ROD CONDUCTOR EXOTHERMIC CONNECTION 10'-0"MIN. ~~ EXIT EXIT EXIT 3 EQ.EQ.EQ. EQ.EQ.EQ. EQ.EQ.EQ. FINISHED CEILING FLOOR DOOR ABOVE COUNTER RECEPTACLE/DAT A 3" TV NOTE: DETAIL SHOWN FOR REFERENCE ONLY, NOT ALL DEVICES ARE INDICATED ON PLANS. BACK SPLASHSTRIKE SIDE HINGE SIDE COUNTER TOP LIGHT SWITCH /DIMMER CABLE, VOICE/DATA, DUPLEX & QUADRAPLEX RECEPTACLES GANG SWITCHING CABLE & TV OUTLET MECHANICAL CASSETTE CABLE & TV OUTLET RECEPTACLE FOR TV OUTLET CLOCK HANGER RECEPTACLE +##" +##" WALL MOUNTED EXIT SIGN ABOVE DOOR (MAX. MT. HT. OF 80" ABOVE TOP OF DOOR) WALL MOUNTED EXIT SIGN ABOVE DOOR (MAX. MT. HT. OF 80" ABOVE TOP OF DOOR) CEILING MOUNTED EXIT SIGN ABOVE DOOR SURFACE MTD 6"6" 24 " 46 " 72 " 84 " 80 " 46 " EQ . E Q . EQ . E Q . BRANCH CIRCUIT CONDUIT MAKE CIRCUIT JOINT WITH TWIST-ON CONNECTOR AND CONNECT TO DEVICE WITH SINGLE LEADS 1 #12 AWG SOLID COPPER GREEN INSULATED JUMPER TO BOX BONDING SCREW. 1 #12 AWG SOLID COPPER GREEN INSULATED JUMPER TO DEVICE GROUNDING SCREW. 4" SQUARE DEVICE BOX BOX DEVICE COVER WITH RAISED RING OF PROPER DEPTH AND TYPE FOR WALL CONSTRUCTION. RING TO FINISH FLUSH WITH WALL DUPLEX RECEPTACLES SHALL BE INSTALLED WITH GROUND PRONG UP DEVICE TRIM PLATE SERVICE GROUNDING DETAIL, SEE TRANSFORMER ON RISER FOR GROUND H2H1 H3 XO X1 X3X2 TRANSFORMER ENCLOSURE FACTORY BONDING JUMPER FEEDER TO LOAD BONDING BUSHING SYSTEM BONDING JUMPER 3 CONDUCTOR GROUNDING LUGBONDING JUMPER BONDING BUSHINGFEEDER FROM SOURCE TRANSFORMER COILS & SUPPORT TAPERED AIR TERMINAL ADHESIVE CABLE FASTENER EVERY 3' MAX. RIDGE SADDLE AIR TERMINAL BASE LIGHTNING PROTECTION CONDUCTOR ADHESIVE TYPE DEVICES ADHESIVE CABLE HOLDER ADHESIVE AIR TERMINAL BASE LIGHTNING PROTECTION CONDUCTOR AIR TERMINAL AIR TERMINAL SWIVAL AIR TERMINAL BASE LIGHTNING PROTECTION CONDUCTOR ADHESIVE CABLE HOLDER ADHESIVE AIR TERMINAL BASE LIGHTNING PROTECTION CONDUCTOR CABLE TO CABLE EXOTHERMIC CONNECTION GROUND CONDUCTOR CABLE TO STRUCTURAL STEEL AT LOWEST AVAILABLE LOCATION TINNED BARE COPPER GROUNDING CONDUCTOR PER NEC HDPE TWIST LOCK COVER WITH STAINLESS STEEL LOCKING BOLT AND "GROUND" EMBOSSED ON COVER 3/4" x 10 COPPER CLAD GROUND ROD, TYPICAL EXOTHERMIC GROUND CONNECTION, TYPICAL 9" DIAMETER x 10" DEEP HIGH DENSITY POLYMER WELL HOUSING CLASS 1 MAIN CONDUCTOR CLASS 1 MAIN CONDUCTOR THRU ROOF CONNECTOR FLANGE BONDING PLATE CONDUIT BELOW SLAB TO A/V WALL BOX 4-GANG ON-GRADE EPOXY COATED FLOOR BOX -WITH ROUND FLUSH ALUMINUM STYLE COVER -(SEE 4 GANG FLOOR BOX INFORMATION IN LEGEND ON SHEET E0.1 FOR POWER AND LV REQUIREMENTS) CONCRETE SLAB POWER CONDUIT BELOW SLAB FLUSH BOXES SHALL BE MOUNTED BEHIND TV, COORDINATE FINAL MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS & DETAILS CONCEALED 1 1/4"CND CONCEALED 3/4"CND WITH #12 CONDUCTORS TV PROVIDED BY OWNER, INSTALLED BY CONTRACTOR J-HOOKS ABOVE CEILING (TYPICAL) CAT 6 CABLES INSTALLED BY OTHERS CONCEALED 1 1/4"CND CAT 6A CAT 6A FLOORBOX LAY-IN CEILING CAST BRONZE COVER (FRICTION FIT) FINISHED FLOOR #10 BRASS BALL CHAIN CAST BRONZE HOUSING #4/0 BARE COPPER EXOTHERMIC TYPE WELD EXOTHERMIC TYPE WELD 3/4" x 10'-0" COPPER CLAD GROUND ROD 10 ' - 0 " M I N . 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 E-502 ELECTRICAL DETAILS 2022075.00 11/22/2024 NO SCALE2RECEPTACLE GROUNDING DETAIL NO SCALE7GROUND ROD DETAIL NO SCALE1ELECTRICAL DEVICES MOUNTING DETAIL NO SCALE4U.L. WL1054 NO SCALE3TRANSFORMER GROUNDING DETAIL NO SCALE5AIR TERMINAL DETAILS NO SCALE6EXOTHERMIC CONNECTION DETAILS NO SCALE8GROUND WELL INSPECTION DETAIL NO SCALE9ROOF TRANSITION DETAIL NO SCALE11FLOOR BOX DETAIL NO SCALE12TV POWER/DATA OUTLET DETAIL NO SCALE10AIRCRAFT STATIC GROUNDING RECEPTACLE 0 11/22/24 ISSUED FOR CONSTRUCTION 11/27/2024 LOAD SUMMARY VOLTAGE PHASE 480 3 1.732 LARGEST MOTOR APPROX. AMPS 91 AMPS LARGEST MOTOR APPROX. AMPS x .25 23 AMPS HVAC AH01 13,258 VA HP01 5,824 VA SFO'S (QTY 2)2,784 VA EF'S (QTY 4)3,030 VA RH'S (QTY 4)480 VA FO'S (QTY 2)4,381 VA DAH01 & DHP01 4,326 VA EUH01 750 VA SUB-TOTAL HVAC DEMAND 34,834 VA SUB-TOTAL HVAC DEMAND 42 AMPS EQUIPMENT HYDRAULIC DOORS (QTY 2)56,536 VA GWH1 200 VA AC-01 7,566 VA AC POWER CART 42,402 VA AIRCRAFT PORTABLE AC UNIT 4,014 VA TUG CHARGER 64,018 VA HYD POWER UNIT 75,658 VA FRENCH DR REFRIG 1,800 VA DISHWASHER 792 VA MICROWAVE 1,668 VA ICE MAKER 792 VA GATE POWER 360 VA COMMERCIAL DRINK REFRIG 1,200 VA SUB-TOTAL EQUIPMENT DEMAND 257,006 VA SUB-TOTAL EQUIPMENT DEMAND 309 AMPS ADD FOR LARGEST MOTOR 23 AMPS TOTAL EQUIPMENT DEMAND 332 AMPS LIGHTING LIGHTS (INTERIOR, BASED ON NEC 220.12)17,084 VA LIGHTS (EXTERIOR)1,761 VA SIGN (QTY 4)3,000 VA TOTAL LIGHTING LOAD 21,845 VA TOTAL DEMAND FOR LIGHTING 26 AMPS RECEPTACLES RECEPTACLES 19,984 VA FIRST 10000VA 10,000 VA REMAINDER @ 50%4,992 VA TOTAL DEMAND FOR RECEPTACLE/POWER PANELS 14,992 VA TOTAL DEMAND FOR RECEPTACLE/POWER PANELS 18 AMPS TOTAL DEMAND BUILDING AMPS 418 AMPS TOTAL DEMAND BUILDING VA 347,590 VA TOTAL BUILDING CONNECTED LOAD 333,669 VA AT PNL 4EP1: 52,032 AMPS AT PNL 2EP1: 5,828 AMPS AT PNL 2EP2: 5,775 AMPS NOTE: 1. SHORT CIRCUIT CALCULATION COMPLETED ON 11/26/2024. BASED ON A 300KVA POLE MOUNTED TRANSFORMER BANK @ 1.7% IMPEDANCE, AND 2.37 X/R. VERIFY ACTUAL PARAMETERS WITH UTILITY COMPANY AND EQUIPMENT CHARACTERISTICS PRIOR TO INSTALLATION. 2. SERVICE EQUIPMENT SHALL BE LEGIBLY MARKED WITH MAX. AVAILABLE FAULT CURRENT, INCLUDING THE DATE THE FAULT CURRENT CALCULATIONS WERE PERFORMED, PER NEC 110.24 AVAILABLE FAULT CURRENT GROUND PER NEC 250 DETAIL #2/0 BARE CU (2) 3" CONDUITS EACH CONTAINING 4-350kcmil CONDUCTORS SURGE PROTECTION DEVICE (SPD) SHALL BE MOUNTED TO KEEP LEADS AS SHORT AS POSSIBLE. SPD's ARE SHOWN WITH A 30A, 3 POLE BREAKER IN PANELBOARD BEING PROTECTED, MAKE CONNECTION WITH 4#10AWG CONDUCTORS, IF SPD MANUFACTURER RECOMMENDS LARGER BREAKER OR LEADS, PROVIDE AT NO ADDITIONAL COST TO OWNER. ELECTRICAL [110] SPD EGB PANEL "4EP1" 600A 480/277V, 3∅, 4W SERVICE EQUIPMENT LISTED 3#2/0 & 1#6GND- 2"CND E-501 10 E-501 9 "2EP1" 200A 208/120V, 3∅, 4W #2 BARE CU 4#3/0 & 1#6GND- 2"CND "T-2EP1 112.5KVA, 480-208/120V, 3ɸ, 4W GROUND PER NEC 250, SEE DETAIL 3/E-502 E-501 1TYP. 'NAME' 'WARNING' 'WORKING SPACE 'NAME' 'WARNING' 'WORKING SPACE E-501 6 'NAME''WARNING' E-501 3 SPD "2EP2" 200A 208/120V, 3∅, 4W 'NAME' 'WARNING' 'WORKING SPACE SPD NOTE (SURGE PROTECTION DEVICE) CT CABINET GRADE METERBASE AND METER 480V ABOVE GROUND JUNCTION BOX PROVIDED BY UTILITY, EC MUST COORDINATE LOCATION WITH UTILITY PRIOR TO TRENCHING AND INSTALLATION FOR SERVICE CONDUIT AND CONDUCTORS 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1820 FLightline Road Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 E-601 ELECTRICAL RISER DIAGRAM AND SCHEDULES 2022075.00 11/22/2024 Notes: Lighting 8420 VA 100.00% 8420 VA Total Est. Demand:76.6 A RCPT 21244 VA 73.54% 15622 VA Total Conn.:83.3 A Power 560 VA 100.00% 560 VA Total Est. Demand:63665 VA Other 3558 VA 100.00% 3558 VA Total Conn. Load:69287 VA HVAC 35515 VA 100.00% 35515 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Legend: Total Amps:422.4 A 394.7 A 396.8 A Total Load:116939 VA 109345 VA 109828 VA 41 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 42 39 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 40 37 LTS: EXTERIOR OVER BAY DOOR 20.0 A 1 915 VA 0 VA 1 20.0 A SPARE 38 35 14133 VA 0 VA 1 20.0 A SPARE 36 33 14133 VA 0 VA 1 20.0 A SPARE 34 31 AC PCU D.S.70.0 A 3 14133 VA 696 VA 1 20.0 A LTS: PERIMETER EXTERIOR 32 29 21615 VA 100 VA 1 20.0 A LTS: CANOPY AT MAIN ENTRY 30 27 21615 VA 2700 VA 1 20.0 A LTS: HANGAR 28 25 TUG CHARGER D.S.100.0 A 3 21615 VA 2700 VA 1 20.0 A LTS: HANGAR 26 23 0 VA 25495 VA 24 21 0 VA 25495 VA 22 19 AC PCU D.S.70.0 A 3 0 VA 25495 VA 3 125.0 A HYD POWER UNIT D.S. 20 17 9423 VA 0 VA 18 15 9423 VA 0 VA 16 13 HYDRAULIC DOOR #1 D.S.,60.0 A 3 9423 VA 0 VA 3 70.0 A AC PCU D.S. 14 11 29644 VA 9423 VA 12 9 26557 VA 9423 VA 10 7 XFMR T-2EP1 (PANEL 2EP1 & 2EP2)175.0 A 3 32541 VA 9423 VA 3 60.0 A HYDRAULIC DOOR #2 D.S., 8 5 0 VA 0 VA 6 3 0 VA 0 VA 4 1 SPD 30.0 A 3 0 VA 0 VA 3 70.0 A AC PCU D.S. 2 CKT Circuit Description Trip Pol es A B C Pol es Trip Circuit Description CKT Notes: Enclosure:NEMA 1 MCB Rating:600.0 A Mounting:SURFACE Wires:4 Mains Rating:600.0 A Supply From: Phases:3 Mains Type:MAIN CB Location:ELEC/ IT 114 Volts:480Y/277 A.I.C. Rating:65,000 AMPS SYMMETRICAL Branch Panel: 4EP1 1. PROVIDE GFCI BREAKER. Notes: Total Est. Demand:110.5 A RCPT 16012 VA 81.23% 13006 VA Total Conn.:118.8 A Power 560 VA 100.00% 560 VA Total Est. Demand:39807 VA Other 3000 VA 100.00% 3000 VA Total Conn. Load:42813 VA HVAC 23241 VA 100.00% 23241 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Legend: Total Amps:174.1 A 166.2 A 172.6 A Total Load:20787 VA 19945 VA 20613 VA 53 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 54 51 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 52 49 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 50 47 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 48 45 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 46 43 BLDG SIGNS 20.0 A 1 1200 VA 0 VA 1 20.0 A SPARE 44 41 SPARE 20.0 A 1 0 VA 2080 VA 42 39 BLDG SIGN 20.0 A 1 600 VA 2080 VA 2 35.0 A DHP01 D.S.40 37 SIGN 20.0 A 1 1200 VA 4419 VA 38 35 HOT BOX POWER 20.0 A 1 1500 VA 4419 VA 36 33 2912 VA 4419 VA 3 50.0 A AH01 D.S. 34 31 HP01 D.S.60.0 A 2 2912 VA 400 VA 1 20.0 A FACP ELECT/IT [114]32 29 GWH1 D.S.20.0 A 1 200 VA 720 VA 1 20.0 A RCPTS/FLR BOX: CONF [106]30 27 RCPT: FIRST RESPONDERS CABINET ELECT/IT [114]20.0 A 1 180 VA 900 VA 1 20.0 A RCPTS: CONF [106]28 25 RCPT: FIRST RESPONDERS CABINET ELECT/IT [114]20.0 A 1 180 VA 1080 VA 1 20.0 A RCPTS: OFFICE [105]26 23 RCPTS: EXTERIOR MAIN ENTRY 20.0 A 1 360 VA 720 VA 1 20.0 A RCPTS: OPEN OFFICE [103]24 21 RCPT: EWC (NOTE 1)20.0 A 1 430 VA 900 VA 1 20.0 A RCPTS: OPEN OFF [103]22 19 RCPT: DISHWASHER BREAK [111] (NOTE 1)20.0 A 1 792 VA 1080 VA 1 20.0 A RCPTS: ENTRY/LOBBY [101] & OPEN OFF [103]20 17 RCPT: MICROWAVE BREAK [111]20.0 A 1 1650 VA 900 VA 1 20.0 A RCPTS: ENTRY/LOBBY [101]18 15 RCPT: BREAK [111]20.0 A 1 360 VA 360 VA 1 20.0 A RCPTS: RESTROOMS [107] & [108]16 13 RCPT: COFFEE BREAK [111]20.0 A 1 180 VA 720 VA 1 20.0 A RCPTS: JAN [109], CORRIDORS [102] & [110]14 11 RCPT: RFRIG BREAK [111]20.0 A 1 1800 VA 5544 VA 12 9 RCPTS: BREAK [111]20.0 A 1 540 VA 5544 VA 10 7 RCPTS: PARTS STORAGE [116]20.0 A 1 720 VA 5544 VA 3 70.0 A AC-01 D.S. 8 5 RCPTS: PARTS STORAGE [116]20.0 A 1 720 VA 0 VA 6 3 RCPTS: TELE BACKBOARD ELECT/IT [114]20.0 A 1 720 VA 0 VA 4 1 RCPTS: ELECT/IT [114]20.0 A 1 360 VA 0 VA 3 30.0 A SPD 2 CKT Circuit Description Trip Pol es A B C Pol es Trip Circuit Description CKT Notes: Enclosure:NEMA 1 MCB Rating:200.0 A Mounting: Wires:4 Mains Rating:200.0 A Supply From:T-2EP1 Phases:3 Mains Type:MAIN CB Location:ELEC/ IT 114 Volts:208Y/120 A.I.C. Rating:10,000 AMPS SYMMETRICAL Branch Panel: 2EP1 1. PROVIDE GFCI BREAKER. Notes: Total Est. Demand:53.8 A Lighting 1367 VA 100.00% 1367 VA Total Conn.:53.8 A RCPT 5232 VA 100.00% 5232 VA Total Est. Demand:19371 VA Other 558 VA 100.00% 558 VA Total Conn. Load:19371 VA HVAC 12274 VA 100.00% 12274 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Legend: Total Amps:101.1 A 55.1 A 78.4 A Total Load:11757 VA 6612 VA 9031 VA 41 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 42 39 GATE POWER 20.0 A 1 180 VA 0 VA 1 20.0 A SPARE 40 37 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 38 35 GATE POWER 20.0 A 1 180 VA 0 VA 1 20.0 A SPARE 36 33 913 VA 636 VA 1 20.0 A LTS: OFFICE AREA 34 31 913 VA 942 VA 1 20.0 A LTS: OFFICE AREA 32 29 F02 15.0 A 3 913 VA 1392 VA 1 20.0 A EF02 D.S.30 27 913 VA 0 VA 1 20.0 A SPARE 28 25 913 VA 1392 VA 1 20.0 A EF01 D.S.26 23 F01 15.0 A 3 913 VA 0 VA 1 20.0 A SPARE 24 21 SPACE -- 1 -- 1392 VA 1 20.0 A SF01 D.S.22 19 4014 VA 750 VA 1 20.0 A EUH01 D.S.20 17 PORTABLE AC UNIT D.S.60.0 A 2 4014 VA -- 1 --SPACE 18 15 RH01, RH01, RH03, RH04 20.0 A 1 480 VA 0 VA 16 13 SF02 D.S.20.0 A 1 1392 VA 0 VA 2 60.0 A PORTABLE AC UNIT D.S. EXTERIOR 14 11 SPACE -- 1 -- 720 VA 1 20.0 A RCPTS: EAST WALL HANGAR [101] & EXT.12 9 0 VA 1200 VA 1 20.0 A RCPT: REFRIGERATED CABINET AGR 1002 HANGAR...10 7 PORTABLE AC UNIT D.S.60.0 A 2 0 VA 792 VA 1 20.0 A RCPT: ICE MAKER 8985 HANGAR [100]8 5 RCPTS: NORTH AND EAST WALLS HANGAR [100] & EXT.20.0 A 1 900 VA 0 VA 6 3 RCPTS: WEST AND NORTH WALL HANGAR [100] & EXT.20.0 A 1 900 VA 0 VA 4 1 RCPTS: WEST WALL HANGAR [100] & EXT.20.0 A 1 720 VA 0 VA 3 30.0 A SPD 2 CKT Circuit Description Trip Pol es A B C Pol es Trip Circuit Description CKT Notes: Enclosure:NEMA 1 MCB Rating:200.0 A Mounting: Wires:4 Mains Rating:200.0 A Supply From:T-2EP1 Phases:3 Mains Type:MAIN CB Location:ELEC/ IT 114 Volts:208Y/120 A.I.C. Rating:10,000 AMPS SYMMETRICAL Branch Panel: 2EP2 NO SCALE1RISER DIAGRAM 1 1 1 1 0 11/22/24 ISSUED FOR CONSTRUCITON 1 2025.01.31 GFO HANGAR PERMIT SET 01/31/2025 THE INSTALLER FIRST RESPONDERS PROJECT NOTES IN TESTING AND INSTALLATION SEQUENCING FIRST RESPONDERS INSTALLATION NOTES FIRST RESPONDERS GENERAL NOTE 1. A PRELIMINARY SITE SURVEY IS NEEDED TO DETERMINE THE EXISTING dBm SIGNAL STRENGTH. 2. A MORE DETAILED SURVEY WILL MAP THE BUILDING ONCE THE BUILDING IS SUBSTANTIALLY COMPLETED. 3. THE NEXT SIGNAL STRENGTH SURVEY WILL COMPLY WITH THE 2018 NCFC, 510.5.3 AND NFPA 72, 24.5.2.1 (2013 EDITION) - EACH FLOOR SHALL BE DIVIDED INTO 20 (APPROXIMATELY) EQUAL TEST AREAS, THE WORST CASE SIGNAL STRENGTH READING SHALL BE RECORDED. PROVIDE 90 PERCENT FLOOR AREA RADIO COVERAGE. - CRITICAL AREAS, IF PRESENT, SHALL BE SURVEYED SEPARATE FROM THE EQUAL TEST AREAS; --- EXIT STAIRS --- EXIT PASSAGEWAYS --- ELEVATOR LOBBIES --- AT STANDPIPE CABINETS --- SPRINKLER SECTIONAL VALVE LOCATIONS --- AHJ MAY REQUIRE ADDITIONAL LOCATIONS. -- CRITICAL AREAS SHALL BE PROVIDED WITH 99 PERCENT RADIO COVERAGE. 4. THE MINIMUM SIGNAL STRENGTH OF -95 dBm IS REQUIRED. 1. ALL WIRING SHALL BE IN ACCORDANCE WITH LOCAL AND NATIONAL CODES, INCLUDING NFPA 72 (2013 EDITION) AND NEC. 2. A FIRST RESPONDERS SYSTEM IS AN EMERGENCY RESPONDER RADIO ENHANCED SYSTEM IN COMPLIANCE WITH THE NC FIRE CODE, SECTION 510. 3. WHERE REQUIRED, WIRING SHALL BE RUN IN MINIMUM 3/4" CONDUIT. SURFACE METAL RACEWAY IS ACCEPTABLE. 4. PLENUM RATED COAXIAL CABLE WITHOUT CONDUIT, MAY BE ACCEPTABLE FOR HORIZONTAL RUNS IN AREAS OTHER THAN WHERE WATERPROOF DEVICES ARE REQUIRED. HOWEVER, CONDUIT SHALL BE USED TO PENETRATIONS IN RATED WALLS SHALL BE MADE IN CONDUIT PER APPROPRIATE U.L. SYSTEM. 5. MANUFACTURER'S 1/2" COAXIAL CABLE SHALL BE USED FOR THE FIRST RESPONDERS SYSTEM, DUE TO ITS LOW OHM LOSS PROPERTIES. 6. THE DIRECTIONAL DONOR ANTENNA ON THE ROOF SHALL BE TIED INTO THE BUILDING GROUNDING SYSTEM. 7. ALL CABLES USED FOR FIRST RESPONDERS SHALL BE GROUNDED TO THE BUILDING GROUNDING SYSTEM. 8. THE CABLE BETWEEN THE DONOR ANTENNA AND THE AMPLIFIER MAY BE RUN TO THE ROOF, BUT IT MUST BE IN CONDUIT. 9. A LIGHTNING ARRESTOR SHALL BE INSTALLED ON THE ANTENNA. 10. THE CABLE FROM THE DONOR ANTENNA TO THE AMPLIFIER SHALL BE SEPARATED FROM THE RISER CABLE FROM THE FIRST RESPONDERS SYSTEM TO THE INDOOR ANTENNA, THIS REQUIREMENT APPLIES TO THE RISER. - IF BOTH CABLES ARE NOT IN CONDUIT, THE MINIMUM SEPARATION SHALL BE SIX (6) FEET. - IF AT LEAST ONE CABLE IS IN CONDUIT, THE MINIMUM SEPARATION SHALL BE THREE (3) FEET. - THESE CABLES ARE ALLOWED TO CROSS A MAXIMUM OF ONE TIME. 11. THE FIRST RESPONDERS AMPLIFIER ENCLOSURE SHALL BE INSTALLED ON METAL STRUT CHANNEL (TO ALLOW AIRFLOW). SEE INSTALLATION DIAGRAM. 12. THE FIRST RESPONDERS AMPLIFIER AND BATTERY ENCLOSURES SHALL BE GROUNDED TO THE BUILDING GROUNDING SYSTEM UTILIZING A SHORT, DIRECT PATH WITH THE MINIMUM NUMBER OF BENDS (GROUNDING CABLES SHALL NOT REVERSE DIRECTION WHEN CONNECTING TO TERMINATION POINTS.) 13. A.C. WIRES SHALL BE RUN IN SEPARATE CONDUIT FROM D.C. WIRING, SUCH THAT A SYSTEM ALARM DOES NOT DE-ENERGIZE THE CONTROL PANEL, MINIMUM SIZE WIRE TO BE AWG 12 THHN. PROTECTION AGAINST VOLTAGE TRANSIENTS AND SURGES SHALL BE INSTALLED AT THE ELECTRICAL PANELBOARD AND INSTALLED BY THE ELECTRICAL CONTRACTOR. - PRIMARY AC POWER TO THE FIRST RESPONDERS AMPLIFIER SHALL BE DEDICATED CIRCUIT. - REDUNDANT AC POWER TO THE FIRST RESPONDERS AMPLIFIER SHALL BE A 120VAC CIRCUIT. (PROVIDING A SECOND (REDUNDANT) POWER CIRCUIT IS PER THE MANUFACTURERS RECOMMENDED PRACTICE.) - CIRCUIT DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED BY THE SYSTEM TYPE: i.e. "EMERGENCY COMMUNICATION SYSTEM" (ECS) 14. CONDUIT FOR THE DONOR (ROOF) ANTENNA AND FOR THE RISER COAXIAL CABLE SHALL BE PARALLEL TO THE FIRST RESPONDERS ENCLOSURE. THESE CONDUITS SHALL TERMINATE WITH A BUSHING WITHIN TWO (2) FEET OF THE BOTTOM OF THE ENCLOSURE. FIRST RESPONDERS SHALL MAKE THE CONNECTION PROVIDED, PRE-WIRED 1/4" FLEX CABLE FROM THE FIRST RESPONDERS SYSTEM. 15. INSTALLATION REQUIREMENTS TO COMPLY WITH NFPA 72, SECTION 24.3.6.8: - THE RISER COAXIAL CABLE SHALL BE INSTALLED IN A 2 HOUR RATED ENCLOSURE OR SHAFT. (2 HOUR RATED COAXIAL CABLE IS NOT AVAILABLE AT THE CORRECT LOW OHM LOSS RATING.) - THE SPLITTER CONNECTIONS BETWEEN THE RISER CABLE AND THE HORIZONTAL FEEDER CABLE SHALL ALSO BE MADE WITH A 2 HOUR RATED ENCLOSURE. THE FEEDER CABLE PASSAGE THROUGH THAT 2 HOUR ENCLOSURE SHALL BE FIRE STOPPED WITH THE APPROPRIATE U.L. SYSTEM. - ALL FEEDER CABLES SHALL BE PLENUM RATED AT A MINIMUM. (FEEDER CABLES ARE THE HORIZONTAL RUNS TO THE DAS.) 16. WHEN SPLITTER CONNECTIONS ARE IN CONDUIT, PROVIDE A MINIMUM 12 INCH x 12 INCH JUNCTION COX TO MAKE THE CONNECTION. 17. THE FIRST RESPONDERS ANNUNCIATOR SHALL BE INSTALLED NEAR THE FIRE ALARM CONTROL PANEL. 18. ALL FIELD WIRING SHALL BE CHECKED FOR SHORTS, OPENS, AND GROUNDS BEFORE MAKING CONNECTIONS. 19. SEE MANUFACTURERS SHEETS FOR MOUNTING DETAILS. 20. ALL JUNCTION BOX COVERS SHALL BE RED IN COLOR. THOSE IN FINISHED ARES ARE PERMITTED TO MATCH THE FINISH COLOR. 21. ALL PENETRATIONS THROUGH RATED WALLS SHALL BE SEALED USING APPROPRIATE U.L. SYSTEM. 1. NOT ALL COMPONENTS REQUIRED ARE INDICATED IN THE INFORMATION PROVIDED IN THE INSTALLATION NOTES, RISER AND FLOOR PLAN(S). THE CONTRACTOR MUST PROVIDE A FULLY FUNCTIONAL AND OPERATIONAL SYSTEM AS PART OF THIS PROJECTS CONTRACT. LIGHTING FIXTURE SCHEDULE MARK DESCRIPTION MANUFACTURER/SERIES NOM. SIZE SOURCE / TEMP(oK) / DELIVERED LUMENS VOLTS WATTS LENS COLOR/ MATERIAL MOUNTING HEIGHT DRIVER/ DIMMING REMARKS A LAY-IN VOLUMETRIC FIXTURE LITHONIA: STAKS 24"L LEDs / MVOLT 41 ACRYLIC WHITE/ RECESSED LED DRIVER 1 STAKS-2X2-AL03-SWW-7 24"W 3500K /ALUMINUM 0-10V HIGH LUMEN 4"H 5000 LUMENS DIMMING B RECESSED CAN GOTHAM: EVO 6"DIA LEDs / MVOLT 15 WHITE RECESSED LED DRIVER 1 EVO6-35/15/AR/MD/LSS 3500K / GYP 0-10V 1500 LUMENS DIMMING C RECESSED CAN GOTHAM: EVO 6"DIA LEDs / MVOLT 10 WHITE RECESSED LED DRIVER 3 EVO6-40/10/AR/MD/LSS 4000K / GYP 1000 LUMENS CE RECESSED CAN GOTHAM: EVO 6"DIA LEDs / MVOLT 10 WHITE RECESSED LED DRIVER 3,8 EVO6-40/10/AR/MD/LSS/4000K / GYP ELSD 1000 LUMENS D 4' STRIP LITHONIA: CSS 48"L LEDs / MVOLT 38 WHITE SURFACE LED DRIVER CSS-L48-4000LM-UVOLT- 4000K / CEILING 40K-80CRI 4000 LUMENS E 2-HEAD EMERGENCY EELP: OEM LED SD 12"W LED MVOLT 10 WHITE WALL LED DRIVER 8 6"H 7'-6" AFF 6"D F LINEAR SUSPENSION FIXTURE VISUAL COMFORT: 55.9"L LEDs / 120V 82 BLACK SUSPENDED LED DRIVER WIT 5 LINEAR SUSPENDED 3.9"W 3000K / 5-GLASS 12" STEM 700LSWIT5 3.9"H 3638 LUMENS G LARGE STAGGERED ARM VISUAL COMFORT:36"DIA LEDs /120V 36 ALABASTER SURFACE LED DRIVER PENDANT W/ 8 ROUND PEDRA LARGE STAGGER 6"H 3000K / BRONZE CEILING LIGHT SOURCES ARM FLUSH 4300 LUMENS KW 4622BZ-ALB H HI-BAY FIXTURE W/ GLARE LITHONIA: LEDs / MVOLT 325 ALUMINUM SUSPENDED LED DRIVER 2 CONTROL LENS, MEDIUM DIST. COMPACT PRO HIGHBAY 5000K / BOTTOM WITH INTERGRAL OCC. SENSOR CPHB-48000LM-SEF-GCL-WD- 48000 LUMENS OF FIXTURE 50K-80CRI-NLTAIR2-RLSXR6 30'AFF J UNDER COUNTER LIGHT JUNO: UNDER CABINET 14"L LEDs /120V 6 WHITE SURFACE LED DRIVER UPLD-14-3500K 3500K / UNDERSIDE CABINET K LED AREA OVER BAY DOOR LITHONIA: D-SERIES, SIZE 1 LEDs /MVOLT 183 BRONZE WALL LED DRIVER 3,6 LED-P7-40K-80CRI-T3M-EG K 4000K MOUNTED 22,000 LUMENS 30'-0"AFF L WALL MOUNTED AREA LIGHT LITHONIA: ARC2-LED-P3-40K LEDs / MVOLT 23 BRONZE WALL LED DRIVER 3,6 4000K MOUNTED 3206 LUMENS 13'-0"AFF M EXIT EGRESS LITHONIA: AFF SERIES 6.5"W LEDs / MVOLT 13 BRONZE WALL LED DRIVER 3,8 AFF-PEL-DDBTXD-UVOLT-10.2"H MOUNTED LTP-SDRT-WT-CW 3.3"D 10'-0"AFF P BEACON LIGHT FEC-HELIPORTS HP2040,LED 120V 90 RED MOUNTED ON LED DRIVER 3 RED BEACON ROOF X1 EXIT SIGN SINGLE FACE EMERGILITE: LXN1NRC-A-D LED MVOLT 10 6" WHITE CEILING LED DRIVER 8 EDGELIT RED MOUNTED LETTERS X2 EXIT SIGN DOUBLE FACE EMERGILITE: LXN1NRC-A-D LED MVOLT 10 6"WHITE CEILING LED DRIVER 8 EDGELIT RED MOUNTED LETTERS X3 EXIT SIGN SINGLE FACE EMERGILITE: LXN1NRC-A-D LED MVOLT 10 6" WHITE WALL LED DRIVER 8 EDGELIT RED 7'-6"AFF LETTERS REMARKS: 1. 0-10V DIMMING TO 1% 4. WIREGUARD 7. FINAL COLOR SELECTION BY ARCHITECT 2. 0-10V DIMMING 5. LED REQUIRED SURGE PROTECTION 8. INTEGRAL BATTERY BACKUP - 90MIN. 3. WET LOCATION 6. VERIFY FINAL MOUNTING HEIGHT WITH ARCHITECT 9. REMOTE BATTERY BACKUP - 90MIN. GENERAL NOTES: A.THE CONTRACTOR MUST VERIFY THE LEAD TIME OF ALL PRODUCTS SPECIFIED IN THIS SCHEDULE AT THE TIME OF PACKAGE QUOTE. B.DURING THE BID PROCESS, THE CONTRACTOR MUST NOTIFY THE ARCHITECT/ENGINEER OF ANY DELIVERY/SCHEDULING ISSUES. C. NO SUBSTITUTIONS WILL BE ALLOWED DUE TO THE LACK OF COORDINATION OF DELIVERY DATES AND CONSTRUCTION SCHEDULE AFTER BID. D.ALL EXPEDITED EXPENSES MUST BE THE RESPONSIBILITY OF THE CONTRACTORS. E.THE ELECTRICAL CONTRACTOR MUST RECEIVE APPROVAL FOR ALL LIGHTING FIXTURES FROM THE ARCHITECT/OWNER PRIOR TO PURCHASE AND ROUGH-IN. F.FIXTURES INSTALLED IN CEILINGS INDICATED ON THE ARCHITECTURAL PLANS AS HAVING INSULATION IN CONTACT WITH THE CEILING SURFACE MUST BE MANUFACTURER RATED "IC".. G. LED MODULES MUST BE REPLACEABLE. H.ACRYLIC PRISMATIC LENSES MUST BE 0.125" NOMINAL MINIMUM THICKNESS. I.ALL EXIT AND EMERGENCY FIXTURES MUST COMPLY WITH NCSBC STANDARDS AND HAVE AUTOMATIC TESTING DEVICES. J.LED EMERGENCY BATTERY MUST PROVIDE FULL RATED FIXTURE A MINIMUM OF 100% OF RATED FIXTURE OUTPUT FOR 90 MINUTES MINIMUM. K.SEE SPECIFICATIONS SECTIONS 265100 AND 265200 FOR ADDITIONAL REQUIREMENTS. L.THE FIRST FIXTURE NAMED IN THE MANUFACTURER COLUMN IS THE BASIS OF DESIGN. OTHER FIXTURES ARE SIMILAR IN THE OPINION OF THE ARCHITECT AND ENGINEER. IF THE CONTRACTOR ELECTS TO SUBMIT A FIXTURE OTHER THAN THE BASIS OF DESIGN FIXTURE, INCLUDING ONE OF THE TWO SIMILAR FIXTURES, REQUIREMENTS OF NOTES O. AND P. APPLY. [THE ABOVE FIXTURE TYPES ARE LISTED AS THE DESIGN BASIS. THE ACTUAL FIXTURES SUBMITTED MUST BE MANUFACTURED IN THE UNITED STATES.] M.SUBSTITUTIONS MAY BE APPROVED BY THE ARCHITECT AND ENGINEER IF THEY ARE JUDGED TO BE EQUAL TO THE SPECIFIED FIXTURES. “EQUAL” MAY INCLUDE, AT THE SOLE DISCRETION OF THE ARCHITECT AND ENGINEER, LENS MATERIAL AND CHARACTERISTICS, COLORS, REFLECTORS, HOUSING MATERIAL AND CONFIGURATION, FINISHES, PHOTOMETRICS, EFFICIENCY, OPTIONS, FUNCTIONALITY, ETC. 2018 APPENDIX B BUILDING CODE SUMMARY ELECTRICAL SUMMARY ELECTRICAL SYSTEMS AND EQUIPMENT METHOD OF COMPLIANCE: ENERGY CODE: PRESCRIPTIVE PERFORMANCE ASHRAE 90.1: PRESCRIPTIVE PERFORMANCE LIGHTING SCHEDULE (EACH FIXTURE TYPE) LAMP TYPE REQUIRED IN FIXTURE: SEE FIXTURE SCHEDULE NUMBER OF LAMPS IN FIXTURE: SEE FIXTURE SCHEDULE BALLAST TYPE USED IN THE FIXTURE: SEE FIXTURE SCHEDULE NUMBER OF BALLASTS IN FIXTURE: SEE FIXTURE SCHEDULE TOTAL WATTAGE PER FIXTURE: SEE FIXTURE SCHEDULE TOTAL INTERIOR WATTAGE: (WHOLE BUILDING OR SPACE BY SPACE) ALLOWED =12,316 WATTS ADDITIONAL 10% =11,084 WATTS SPECIFIED =8,420 WATTS EXTERIOR ALLOWANCE: (TRADEABLE SURFACES) ALLOWED =3,606 WATTS SPECIFIED =1,761 WATTS (NON-TRADEABLE SURFACES:) ALLOWED = N/A WATTS SPECIFIED = N/A WATTS ADDITIONAL PRESCRIPTIVE COMPLIANCE C406.2 MORE EFFICIENT HVAC EQUIPMENT PERFORMANCE C406.3 REDUCED LIGHTING POWER DENSITY C406.4 ENHANCED DIGITAL LIGHTING CONTROLS C406.5 ON-SITE RENEWABLE ENERGY C406.6 DEDICATED OUTSIDE AIR SYSTEM C406.7 REDUCED ENERGY USE IN SERVICE WATER HEATING 48 " FLOOR 3/4"x24'x24' FIRE RETARDANT PLYWOOD BACKBOARD CEILING QUADRAPLEX RECEPTACLE FIBER EQUIPMENT PROVIDE (2) 2"CND'S TO PROPERTY LINE (2) 2"CND'S FROM UTILITY 1 1/4" CONDUIT. GROUNDING BAR "EGB" NOTES: TYPICAL DATA/TELEPHONE OUTLET. REFER TO PLANS FOR QUANTITIES AND LOCATIONS. REFER TO DETAILS FOR OUTLET CONFIGURATION. WAP 1.OWNERS VOICE/DATA CONTRACTOR SHALL PROVIDE AND INSTALL DATA CABLE. 2. RISER DIAGRAM IS DEPICTIVE (FUNCTIONAL) ONLY. 3. ALL DEVICES ARE NOT SHOWN ALL TELECOM SLEEVES AND RACEWAYS SHALL BE BUSHED, REAMED AND BE PROVIDED WITH INSULATED BONDING BUSHINGS. PROVIDE PULL STRING IN ALL SLEEVES AND RACEWAY. WALL MOUNTED DATA RACK PROVIDE (1) 6 STRAND MULTIMODE FIBER OPTIC CABLE 1 1/4"CND 24"x24"x8" HINGED TELECOM CABINET, NEMA 3R RATED WALL NOTE: ALL OUTLET BOXES SHALL BE 2-GANG WITH ADAPTORS TO SINGLE-GANG FACEPLATES. 1 1/4" CONDUIT TYPICAL (UNLESS OTHERWISE NOTED) 4x4 WALL BOX INSTALL SINGLE GANG PLASTIC RING CL P11 - 161/ 2 " DEVICE IDENTIFICATION LABEL, CLEAR "RHINO" TAPE WITH BLACK LETTERING P11-INDICATES PANEL 16-INDICATES BRANCH CIRCUIT BREAKER NUMBER DONOR ANTENNA ROOF 1ST FLOOR BDA CABINET MUST BE IN 2 HOUR RATED ROOM OR SHAFT BDA BATTERY CABINET MUST BE IN 2 HOUR RATED ROOM OR SHAFT SPLITTER MUST BE IN 2 HOUR RATED SHAFT (TYPICAL) DAS, INDOOR ANTENNA (TYPICAL) 2 HOUR RATED ROOM OR SHAFT HORIZONTAL CABLING PLENUM RATED LIGHTNING ARRESTOR 2"CND VERTICAL CABLING MUST BE IN 2 HOUR RATED SHAFT NOTE: ALL VERTICAL ITEMS MUST BE MADE WITH-IN 2 HOUR RATED ENCLOSURE (CABLE, CONNECTORS ETS..) FACP ANNUNCIATOR PANEL BDA ANNUNCIATOR PANEL MUST BE LCOATED ADJACENT TO FACP ANNUNCIATOR PANEL NO SCALE3LABELING DETAIL NO SCALE2OUTLET PATHWAY DETAIL NO SCALE1TELECOM RISER 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 E-602 ELECTRICAL TELECOM RISER, DETAILS & FIRST RESPONDERS INFORMATION 2022075.00 11/22/2024 NO SCALE4FIRST RESPONDERS RADIO RISER DIAGRAM 0 11/22/24 ISSUED FOR CONSTRUCTION 11/27/2024 FIRE ALARM SYSTEM NOTES 1. PROVIDE AN NFPA 72 COMPLIANT FIRE DETECTION AND ALARM SYSTEM. THE SYSTEM SHALL BE A CLASS “B” TWO WIRE ADDRESSABLE TYPE, WITH A 24VDC NOMINAL OPERATING VOLTAGE, SMOKE DETECTORS, DOUBLE ACTION TYPE MANUAL STATIONS, A SOLID STATE, MICROPROCESSOR CONTROLLED FIRE ALARM CONTROL PANEL WITH INTEGRAL LCD ANNUNCIATOR, AND RECHARGING BATTERY SUPPLY. THE SYSTEM SHALL PROVIDE LOCAL ANNUNCIATION VIA ALARM INDICATING APPLIANCES AND REMOTE ANNUNCIATION VIA TELEPHONE LINES OR CELLULAR MODEM. PROVIDE A DEDICATED 120 VAC BRANCH CIRCUIT WITH BREAKER LOCKING MEANS FOR THE FACP. PROVIDE A DUAL LINE UNIVERSAL DIGITAL ALARM COMMUNICATOR (UDACT) AND CONNECT TO TELEPHONE LINES OR CELLULAR MODEM. ALL INDICATING APPLIANCE WIRING SHALL BE #14 AWG MINIMUM. INITIATING DEVICE CIRCUITS SHALL BE SIZED AS REQUIRED BY THE SYSTEM MANUFACTURER. 2. THE CONTRACTOR SHALL FURNISH ALL PARTS, MATERIALS, LABOR, ACCESSORIES, CONNECTIONS, EQUIPMENT, PROGRAMMING, ETC. CUSTOMARILY REQUIRED OR PROVIDED FOR A COMPLETE AND OPERATING CODE-COMPLIANT SYSTEM IN ACCORDANCE WITH ALL APPLICABLE REQUIREMENTS, EVEN IF EACH NEEDED ITEM IS NOT SPECIFICALLY SHOWN OR DESCRIBED ON THE CONTRACT DRAWINGS OR SPECIFICATIONS. ALL SYSTEM COMPONENTS SPECIFIED HEREIN, AS WELL AS THEIR INSTALLATION, SHALL COMPLY WITH APPLICABLE STANDARDS OF THE NATIONAL ELECTRICAL CODE, NATIONAL FIRE PROTECTION ASSOCIATION, AND LOCAL CODES. ALL EQUIPMENT SHALL BE UL LISTED FOR FIRE ALARM SYSTEM USE. 3. THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND SHALL BE INSTALLED AND CONNECTED UNDER THE DIRECTION AND SUPERVISION OF A MANUFACTURER'S REPRESENTATIVE. ALL FIRE ALARM EQUIPMENT AND DEVICES SHALL BE INSTALLED AND TERMINATED BY A NICET LEVEL 2 FIRE ALARM TECHNICIAN. THE MANUFACTURER'S AUTHORIZED REPRESENTATIVE SHALL PROVIDE SUPERVISION OF FINAL SYSTEM CONNECTIONS, MAKE REQUIRED ADJUSTMENTS, PERFORM A COMPLETE FUNCTIONAL TEST OF THE SYSTEM, PROVIDE ALL DOCUMENTATION, TESTING AND CERTIFICATION SERVICES AS REQUIRED BY ALL PERTINENT CODES AND THE AUTHORITY HAVING JURISDICTION (AHJ) AND CERTIFY IN WRITING THAT THE SYSTEM IS PROPERLY INSTALLED AND FUNCTIONS AS SPECIFIED. THE REPRESENTATIVE SHALL ALSO PROVIDE A WRITTEN REPORT ATTESTING TO THE PROPER OPERATION OF THE COMPLETED SYSTEM. 4. ALL CONDUCTORS AND CABLE SHALL BE INSTALLED CONCEALED UNO. ALL WIRING SHALL BE UL LISTED FIRE RATED CABLE AND COLOR CODED TO ALLOW EASE OF IDENTIFICATION OF THE DIFFERENT CIRCUITRY REQUIRED FOR THE SYSTEM. NO CIRCUIT SHALL CHANGE COLOR AT ANY POINT END TO END. 5. ALL WORK SHALL BE IN COMPLIANCE WITH NFPA 70 AND 72 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. ALL EQUIPMENT SUPPLIED SHALL BE LISTED FOR THE PURPOSE FOR WHICH IT IS USED AND INSTALLED IN ACCORDANCE WITH INSTRUCTIONS INCLUDED IN ITS LISTING. IT SHALL ALSO BE NEW, WITH A FULL WARRANTY (PARTS AND LABOR) OF AT LEAST ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE. FURNISH SERVICE AND MAINTENANCE OF THE SYSTEM FOR ONE YEAR FROM DATE OF FINAL ACCEPTANCE. 6. ALL WORK PERFORMED AND ALL MATERIAL FURNISHED UNDER THIS CONTRACT SHALL BE FREE FROM DEFECTS AND SHALL REMAIN SO FOR A PERIOD OF AT LEAST ONE YEAR FROM THE DATE OF ACCEPTANCE. THE CONTRACTOR SHALL PROVIDE A ONE YEAR WARRANTY FOR THE ALARM SYSTEM, ALONG WITH OTHER FORMS OR CERTIFICATE REQUIRED BY THE LOCAL JURISDICTION. 7. EQUIPMENT SHALL CONSIST OF THE FOLLOWING: 7.1 FIRE ALARM CONTROL PANEL WITH BATTERY BACK-UP. BATTERY SUPPLY CAPACITY SHALL PROVIDE FOR 60 HOURS IN STANDBY FOLLOWED BY 15 MINUTES WITH ALL DEVICES IN ALARM. 7.2 MANUAL STATION: MANUAL STATIONS SHALL BE CONSTRUCTED OF HIGH IMPACT, RED LEXAN WITH RAISED LETTERING. MANUAL STATIONS SHALL BE LOCATED NOT MORE THAN FOUR FEET ABOVE THE FINISHED FLOOR TO THE CENTER OF THE BOX. STATIONS SHALL BE LOCATED NOT MORE THEN FIVE FEET FROM EACH DESIGNATED EXIT-WAY AND THE TRAVEL DISTANCE SHALL NOT EXCEED 200 FEET. 7.3 SMOKE DETECTOR: NFPA 72, SOLID STATE ADDRESSABLE PHOTOELECTRIC TYPE WITH TWO WIRE OPERATION AND 360" SMOKE ENTRY. PROVIDE STAND ALONE IONIZATION TYPE WITH HORN AND BATTERY BACKUP FOR EACH UNIT. 7.4 REMOTE LCD ALPHANUMERIC ANNUNCIATOR, FLUSH MOUNTED. 8. SYSTEM OPERATION 8.1 WHEN A FIRE ALARM CONDITION IS DETECTED AND REPORTED BY ONE OF THE SYSTEM INITIATING DEVICES OR APPLIANCES, THE FOLLOWING FUNCTIONS SHALL IMMEDIATELY OCCUR: a. THE SYSTEM ALARM LED SHALL FLASH. b. A LOCAL PIEZO-ELECTRIC SIGNAL IN THE CONTROL PANEL SHALL SOUND. c. THE FACP DISPLAY SHALL INDICATE ALL INFORMATION ASSOCIATED WITH THE FIRE ALARM CONDITION, INCLUDING THE TYPE OF ALARM POINT AND ITS LOCATION WITHIN THE PROTECTED PREMISES. d. ALL SYSTEM OUTPUT PROGRAMS ASSIGNED VIA CONTROL-BY-EVENT EQUATIONS TO BE ACTIVATED BY THE PARTICULAR POINT IN ALARM SHALL BE EXECUTED, AND THE ASSOCIATED SYSTEM OUTPUTS (ALARM NOTIFICATION APPLIANCES AND/OR RELAYS) SHALL BE ACTIVATED. EXACT PROGRAMMING SHALL BE PROVIDED BY THE CONTRACTOR TO MEET THE OWNER'S REQUIREMENTS. e. ACTIVATE ALL FIRE ALARM NOTIFICATION APPLIANCES IN THE BUILDING, SOUNDING CONTINUOUSLY UNTIL THE INITIATING DEVICE AND CONTROL UNIT HAVE BEEN RESET TO NORMAL CONDITION. f. ACTIVATE DIGITAL ALARM COMMUNICATOR. g. DEACTIVATE CONTROL RELAYS TO CAUSE A GLOBAL SHUT DOWN OF ALL HVAC AIR HANDLING UNITS. 8.2 THE DEVICE FROM WHICH THE ALARM ORIGINATED SHALL BE INDICATED AT THE CONTROL PANEL, BOTH AUDIBLY AND VISUALLY, AND AT THE REMOTE ANNUNCIATOR(S). THE INIATING DEVICE LED SHALL PULSE AND SHALL BE ILLUMINATED CONTINUOUSLY AFTER IT HAS BE ACKNOWLEDGED AT THE CONTROL PANEL. 8.3 IN THE EVENT OF A SPRINKLER SYSTEM VALVE CLOSURE THAT ACTIVATES A TAMPER SWITCH, THE SUPERVISORY SIGNALS (BOTH AUDIBLE AND VISUAL) SHALL ACTIVATE AT THE CONTROL PANEL. IT SHALL BE POSSIBLE TO TEMPORARILY SILENCE THE AUDIBLE ALARM BY MEANS OF A SILENCING SWITCH. THE AUDIBLE ALARM SHALL REACTIVATE AUTOMATICALLY ON A PERIODIC BASIS UNTIL THE SYSTEM IS CORRECTED. IT SHALL NOT BE POSSIBLE TO EXTINGUISH THE SUPERVISORY LIGHT UNTIL THE SYSTEM IS CORRECTED. 9. SLEEVE AND SEAL ALL PENETRATIONS THROUGH RATED WALLS AND FLOORS. 10. NOTIFICATION APPLIANCE CIRCUITS SHALL BE A MINIMUM OF NO. 14 AWG UNLESS OTHERWISE NOTED. 11. IN SPACES WHERE MORE THAN TWO VISIBLE NOTIFICATION APPLIANCES ARE IN ANY FIELD OF VIEW, THEY SHALL FLASH IN SYNCHRONIZATION. 12. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR FIRE ALAM MODULES TO SHUTDOWN HVAC EQUIPMENT DURING AN ALARM CONDITION. 13. PROVIDE A 1” MINIMUM RACEWAY FOR A DEDICATED PHONE LINE FOR THE FACP DIALER AND BACKUP LINE FROM EXTERIOR CABINET TO FACP. 14. SHOP DRAWINGS MUST BE SUBMITTED BY THE FIRE ALARM CONTRACTOR COMPLYING WITH THE FIRE ALARM PLAN REVIEW REQUIREMENTS POLICY - JANUARY 2006 BEFORE PERMITTING BY THE WILMINGTON FIRE DEPARTMENT. THESE DRAWINGS DO NOT CONSTITUTE APPROVAL AND MAY CHANGE AFTER A FULL REVIEW BY THE WILMINGTON FIRE DEPARTMENT. A SEPARATE PERMIT MUST BE OBTAINED PRIOR TO INSTALLATION. PIV M M M MM F F F F FF F F M M TB (SYMBOLS SHOWN FOR REFERENCE ONLY AND MAY NOT IMPLY CONTRACTUAL REQUIREMENTS) F M M I C C F F FIRE ALARM LEGEND SYMBOL DESCRIPTION FACP 15cd FIRE ALARM MANUAL STATION, 48" AFF FIRE ALARM HORN/STROBE DEVICE, 80" AFF, "15cd" INDICATES CANDELA RATING SMOKE DETECTOR, CEILING MOUNTED ISOLATION MODULE FIRE ALARM CONTROL PANEL (FACP) FA REMOTE ANN FIRE ALARM REMOTE ANNUNCIATOR PANEL HEAT DETECTOR, CEILING MOUNTED SPRINKLER TAMPER SWITCH SPRINKLER FLOW SWITCH FIRE WATER FLOW ALARM, 80" AFF CONTROL MODULE CONTROL MODULE, WALL MOUNTED MONITOR MODULE MONITOR MODULE, WALL MOUNTED WP TERMINAL BOX NOTE: DETAIL SHOWN FOR REFERENCE ONLY, NOT ALL DEVICES ARE INDICATED ON PLANS. EXIT (3 ' - 6 " M I N I M U M , 4'- 0 " M A X I M U M ) FINISHED FLOOR CL CL NEVER HERE HORN OR SPEAKER SMOKE/ HEAT DETECTOR STROBEHORN / STROBE OR SPEAKER / STROBE CONTROL PANEL SMOKE/ HEAT DETECTOR MANUAL PULL STATION INSTALL PER NATIONAL ELECTRIC CODE STRIKE SIDE HINGE SIDE DOOR 5'-0" MAXIMUM CL 3' - 8 " 5' - 6 " 80 " M I N I M U M BO T T O M O F DE V I C E 96 " M A X I M U M TO P O F D E V I C E CONDUIT AIR SUPPLY DIFFUSER OR RETURN AIR OPENING MOUNT AUDIBLE & VISUAL DEVICES ON APPROVED BOXES 0'-4" MIN 1'- 0 " M A X . 0' - 4 " MI N . 3'-0" MINIMUM 0'-4" MINIMUM MOUNT ON AN APPROVED BOX 0'- 6 " MI N . FIRE ALARM CONTROL PANEL LOCATED INSIDE HE I G H T A S R E Q ' D LENGTH AS REQUIRED RED LAMICORE PLACARD WITH 3/4" WHITE ENGRAVED LETTERS MACHINE SCREW WITH ACORN NUT AND LOCKWASHER, TYP. HVAC SHUTDOWN FIRE ALARM CONTROL PANEL FIRE ALARM REMOTE ANNUNCIATORAPPROVED CELLULAR/ INTERNET COMMUNICATOR INTEGRAL BATTERYPANEL 2EP1-32 NOTE: RISER DIAGRAM IS DEPICTIVE (FUNCTIONAL) ONLY. ALL DEVICES ARE NOT SHOWN FIRST RESPONDERS: PROVIDE MODULES FOR THE FOLLOWING ALARMS: 1.AC FAIL 2. LOW BATTERY 3.CHARGER FAIL 4. BOOSTER FAIL 5.ANTENNA MALFUNCTION 6. SYSTEM COMPONENT FAIL COORDINATE EXACT LOCATIONAND QUANTITIES WITH FIRE PROTECTION PLANS WP INLINE SURGE PROTECTION,TYP FIRST FLOORGRADE BACKFLOW PREVENTER FIRE DOOR SHUTTER FIRST RESPONDERS (SEE NOTES ABOVE) 2 # 12 GND- 3/4" CND ELECTRIC BELL (ON EXTERIOR OF BUILDING) GRADE FIRE DOOR SHUTTER HLV FANS PROVIDE SMOKE DETECTOR AT FACP JUNCTION ABOVE CEILING (PAINTED RED) METALLIC CONDUIT FLEX METALLIC CONDUIT (6" MIN.) STEEL "T-BAR" SUPPORTED EACH END BY CEILING GRID CHANNEL FIXTURE BOX MTS. TO "T-BAR" CEILING GRID CHANNEL CEILING GRID CHANNELSMOKE DETECTOR NOTES: SECURELY MOUNT TRANSIENT ARRESTOR IN ACCESSIBLE JUNCTION BOX OR PROPER METAL ENCLOSURE ADJACENT TO THE PANELBOARD. PROVIDE ENGRAVED LABEL INDICATING ITS LOCATION ARRESTOR TO PANELBOARD NEUTRAL OR GROUND BAR AS INDICATED BY INSTALLATION INSTRUCTIONS TO PANELBOARD CIRCUIT WITH CLIP LOCK 120VAC BRANCH CIRCUIT HOT (BLACK) CONDUCTOR TO FIRE ALARM CONTROL COIL, 5 TO 10, ABOUT 1" DIAMETER, TIE WRAPPED FIRE ALARM SYSTEM CONTROL MATRIX SYSTEM OUTPUTS SYSTEM INPUTS NOTE ACTUATE COMMON ALARM SIGNAL INDICATOR ACTUATE NOTIFICATION APPLIANCES (NOTE 6) ACTUATE SLEEPING ROOM SOUNDER BASE ONLY ACTUATE EXTERIOR ELECTRIC BELL ACTUATE COMMON TROUBLE SIGNAL INDICATOR ACTUATE COMMON SUPERVISORY SIGNAL INDICATOR ALARM SIGNAL TO MONITORING SERVICE SUPERVISORY SIGNAL TO MONITORING SERVICE TROUBLE SIGNAL TO MONITORING SERVICE DISPLAY/PRINT CHANGE OF STATUS RECALL ELEVATOR TO PRIMARY RECALL FLOOR RECALL ELEVATOR TO ALTERNATE RECALL FLOOR ACTIVATE FIRE HAT SIGNAL SHUNT TRIP ELEVATOR CONTROLLER FEEDER CIRCUIT BREAKER START FIRE PUMP SHUTDOWN HLV FAN RECORD EVENTS IN SYSTEM MEMORY SIGNAL HVAC CONTROL SYSTEM A B C D E F G H I J K L M N O P Q R 1 INITIATING DEVICES 2 SMOKE DETECTORS X X X X X 3 MANUAL PULL STATIONS X X X X X 4 TROUBLE INPUTS 5 SYSTEM TROUBLE CONDITION X X X 6 LOSS OF FACU AC POWER 1 X X X 7 FACP LOW BATTERY X X X 8 SHORT CIRCUIT X X X 9 NAC POWER SUPPLY LOW BATTERY X X X 10 GROUND FAULT X X X 11 OPEN CIRCUIT X X X 12 AHU SHUTDOWN X X X 13 FIRE SUPPRESSION SYSTEM 14 SPRINKLER SYSTEM FLOW SWITCH 2 X X X X X X X 15 SPRINKLER SYSTEM TAMPER SWITCH 2 X X X 16 SPRINKLER PRESSURE SWITCH 2,3 X X X 17 POST INDICATOR VALVE TAMPER SWITCH 2 X X X 18 RPZ TAMPER SWITCHES 2 X X X 19 FIRST RESPONDERS CABINET 20 AC FAIL X X X 21 CHARGER FAIL X X X 22 ANTENNA MALFUNCTION X X X 23 LOW BATTERY X X X 24 BOOSTER FAIL X X X 25 SYSTEM COMPONENT FAIL X X X NOTES: 1 ONLY AFTER LOSS OF POWER FOR > 3 HOURS. 2. 3. TYPICAL, QUANTITIES OF DEVICES ARE NOT SHOWN, REFER TO FIRE PROTECTION SYSTEM RECORD DRAWINGS FOR QUANTITIES AND LOCATIONS. IF INSTALLED. ACTIVATE FIRE DOOR SHUTTER S X X X LEVEL WITH BOTTOM OF SUSPENDED LIGHT EMT CONDUIT, HORN/STROBE EMT CONDUIT CEILING SURFACE MOUNTED JUNCTION BOX 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1820 FLightline Road Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 F-001 FIRE ALARM LEGEND, NOTES, RISER AND DETAILS 2022075.00 11/22/2024 NO SCALE1FIRE ALARM RISER NO SCALE2FIRE ALARM DEVICES MOUNTING HEIGHTS NO SCALE3FA PLACARD DETAIL NOT TO SCALE4 TYPICAL CEILING MOUNTED DETECTOR MOUNTING DETAIL NO SCALE5TRANSIENT ARRESTOR INSTALLATION DETAIL NO SCALE7TYPICAL SYSPENDED DEVICE DETAIL 1 1 0 11/22/24 ISSUED FOR CONSTRUCITON 1 2025.01.31 GFO HANGAR PERMIT SET 01/31/2025 F F FF F F F F F F F F F F F F F F F 1 6 3 4 5 2 1.1 5.9 GF.9ABB.1 DC E F 4EP1 2EP1 FACP 2EP2 COORDINATE EXACT LOCATION AND QUANTITIES WITH FIRE PROTECTION PLANS (TYPICAL ALL) FIRE ALARM ANNUNCIATOR PANEL PROVIDE A PLACARD INDICATING "FIRE ALARM CONTROL PANEL INSIDE" SEE DETAIL 3/F-001 HANGAR 100 ENTRY/ LOBBY 101 CONFERENCE 106 PARTS STORAGE 116 ELEC/ IT 114 OPEN OFFICE 103 RISER 115 OFFICE 105 CORR 110 RESTROOM 107 RESTROOM 108 JAN 109 BREAK 111 CLOSET 112 CORR 102 WATER FLOW ALARM WP M FIRST RESPONDERS: PROVIDE MODULES FOR THE FOLLOWING ALARMS TO FACP: 1.AC FAIL 2.2. LOW BATTERY 3.CHARGER FAIL 4.4. BOOSTER FAIL 5.ANTENNA MALFUNCTION 6.SYSTEM COMPONENT FAIL 30CD 30CD 177CD 30CD 30CD 30CD 30CD 30CD 30CD 30CD 30CD 177CD PENDANT MOUNTED AT 30'AFF (TYP OF 4) 177CD 177CD M FA MODULE FOR FIRE DOOR SHUTTER M FA MODULE FOR F01 M FA MODULE FOR F01 F01 F02 DETECTOR WALL MOUNTED ABOVE FIRE DOOR SHUTTER PLAN NORTH TRUE NORTH NN 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 F-101 FIRE ALARM FLOOR PLAN 2022075.00 11/22/2024 1/8" = 1'-0"1 FIRST FLOOR PLAN - BASE BID - FIRE ALARM 0'8'4'8' SCALE : 1/8" = 1'-0" 0 11/22/24 ISSUED FOR CONSTRUCTION 11/27/2024 CD HWR HWS G (E) 16"x8" 16"/8" (E) F S M B D C 16"Ø E/A O/A T/A L/A R/A S/A CONDENSATE DRAINAGE HEATING WATER RETURN HEATING WATER SUPPLY NATURAL GAS EXHAUST AIR OUTSIDE AIR RELIEF AIR RETURN AIR SUPPLY AIR TRANSFER AIR REF-L REF-S REFRIGERANT-LIQUID REFRIGERANT-SUCTION 2" CAP PLUG 2" 4" 4"4" REF-HG REFRIGERANT-HOT GAS PIPING SYMBOLS KEYNOTE CONTINUATION SYMBOL EXISTING DUCT TAG OVAL DUCT SIZE TAG (WIDTH / HEIGHT) SQUARE DUCT SIZE TAG (WIDTH x HEIGHT) NUMBER OF SHEET WHERE DETAIL APPEARS NUMBER OF DETAIL ON SHEET REVISION NUMBER -SHOWN ON PLANS GENERAL MECHANICAL SYMBOLS ROOM NAME AND NUMBER POINT WHERE NEW CONNECTS TO EXISTING HVAC SYMBOLS MECHANICAL EQUIPMENT TAG EXISTING MECHANICAL EQUIPMENT TAG (TYPICAL FOR ALL EXISTING TAGS) &AND Ø ROUND A AIR AB ABOVE BASE ABV ABOVE AC AIR CONDITIONING ACOUS ACOUSTICAL AD AREA DRAIN ADD ADDENDUM ADDL ADDITIONAL AFF ABOVE FINISHED FLOOR AFUE ANNUAL FUEL UTILIZATION EFFICIENCY AG ABOVE GROUND ALT ALTERNATE ALUM ALUMINUM AP ACCESS PANEL APPROX APPROXIMATE ARCH ARCHITECT/ARCHITECTURAL AV ACID RESISTANT VENT AW ACID RESISTANT WASTE AUTO AUTOMATIC BFF BELOW FINISHED FLOOR BLDG BUILDING BLW BELOW BM BEAM BO BY OTHER BOT BOTTOM BSMT BASEMENT BTU BRITISH THERMAL UNITS BTUH BRITISH THERMAL UNITS PER HOUR BTWN BETWEEN CAP CAPACITY CB CATCH BASIN CCW COUNTER CLOCKWISE CFCV CONSTANT FLOW CONTROL VALVE CFM CUBIC FEET PER MINUTE CHW CIRCULATING HOT WATER CI CAST IRON CLG CEILING CLG COOLING CO CLEAN OUT COL COLUMN COMB COMBINATION CONC CONCRETE COND CONDENSATE CONF CONFERENCE CONN CONNECT CONST CONSTRUCTION CONT CONTINUE/CONTINUATION CONTR CONTRACT/CONTRACTOR COORD COORDINATE CTR CENTER CUFT CUBIC FEET CV CHECK VALVE CW COLD WATER CW CLOCKWISE D DEGREE DB DRY BULB DET DETAIL DIA DIAMETER DIAG DIAGONAL DISCH DISCHARGE DIV DIVISION DI DEIONIZED WATER DMPR DAMPER DN DOWN DWG DRAWING DW DISTILLED WATER EA EACH EAT ENTERING AIR TEMPERATURE EL ELBOW ELEC ELECTRICAL ELEV ELEVATION EP EXPLOSION PROOF EQ EQUAL EQUIP EQUIPMENT EWC ELECTRIC WATER COOLER EWT ENTERING WATER TEMPERATURE E/A EXHAUST AIR EAH EXHAUST HOOD EXIST EXISTING EXP EXPANSION EXPJT EXPANSION JOINT EXT EXTERIOR F DEGREES FAHRENHEIT FCO FLOOR CLEAN OUT FD FLOOR DRAIN FD FIRE DAMPER FDV FIRE DEPARTMENT VALVE FHC FIRE HOSE CABINET FL FLOOR FLEX FLEXIBLE FLG FLANGE FO FUEL OIL FOV FUEL OIL VENT FOR FUEL OIL RETURN FOS FUEL OIL SUPPLY FPM FEET PER MINUTE FRP FIBERGLASS REINFORCED PIPE FS FULL SIZE FS FLOOR SINK FT FOOT/FEET FTG FOOTING FTR FIN TUBE RADIATION FUT FUTURE GA GAGE/GAUGE GAL GALLON GALV GALVANIZED GC GENERAL CONTRACTOR GEN GENERATOR GENL GENERAL GPH GALLONS PER MINUTE GR GRADE GW GREASE WASTE HB HOSE BIB HD HEAD HORZ HORIZONTAL HP HORSE POWER HP HIGH PRESSURE HTG HEATING HTR HEATER HW HOT WATER HYD HYDRANT ID INDIRECT IN INCH INL INLET INSUL INSULATION INT INTERIOR INV INVERT INWG INCHES WATER GAUGE JST SPC JOIST SPACE JT JOINT LAB LABORATORY LB POUND LB/HR POUNDS PER HOUR LAT LEAVING AIR TEMPERATURE LF LINEAL FOOT LOC LOCATION LP LOW PRESSURE LPG LIQUEFIED PETROLEUM GAS LR LIQUID REFRIGERANT LS LAWN SPRINKLER L LOUVER LWT LEAVING WATER TEMPERATURE M/A MIXED AIR MAN MANUAL MATL MATERIAL MAV MANUAL AIR VENT MAX MAXIMUM MBD MOTORIZED BYPASS DAMPER MBH ONE THOUSAND BTU PER HOUR MCF ONE THOUSAND CUBIC FEET MCW MAKE-UP COLD WATER MD MOTORIZED DAMPER MECH MECHANICAL MFR MANUFACTURER MH MANHOLE MIN MINIMUM MISC MISCELLANEOUS MTR MOTOR MU/A MAKE-UP/AIR N NECK NC NOISE CRITERIA NC NORMALLY CLOSED NIC NOT IN CONTRACT NO NUMBER NO NORMALLY OPEN NOM NOMINAL NTS NOT TO SCALE O OXYGEN O/A OUTSIDE AIR OC ON CENTER OF OVERFLOW OPNG OPENING ORD OVERFLOW ROOF DRAIN PD PRESSURE DROP PIV POST INDICATOR VALVE PLBG PLUMBING PR PAIR PREL PRELIMINARY PRESS PRESSURE PRIM PRIMARY PRV PRESSURE REDUCING VALVE PSI POUNDS PER SQUARE INCH PSIG POUNDS PER SQUARE INCH GAUGE PW POTABLE WATER PWR POWER R DUCT RISER R/A RETURN AIR RCP RADIANT CEILING PANEL RD ROOF DRAIN REC RECESSED RED REDUCER REFR REFRIGERATION RH RELATIVE HUMIDITY REQD REQUIRED REV REVERSE RL/A RELIEF AIR RM ROOM RPM REVOLUTIONS PER MINUTE RW RAIN WATER SF SQUARE FOOT S/A SUPPLY AIR SAN SANITARY SCHED SCHEDULE SECT SECTION SF SQUARE FOOT SD SMOKE DAMPER SHT SHEET SIM SIMILAR SLV SLEEVE SM SURFACE MOUNT SP STANDPIPE SP STATIC PRESSURE SPEC SPECIFICATION SPS STATIC PRESSURE STATION SQ SQUARE SR SUCTION REFRIGERANT SSD SOIL SUBDRAIN SS STAINLESS STEEL STD STANDARD STM STEAM STRUCT STRUCTURAL SUCT SUCTION SUSP SUSPENDED T THERMOSTAT TCP TEMPERATURE CONTROL PANEL TD TEMPERATURE DROP TDR TRENCH DRAIN TEFC TOTALLY ENCLOSED FAN COOLED TEMP TEMPERATURE TYP TYPICAL UFD UNDER FLOOR DUCT UG UNDERGROUND VAC VACUUM V VENT VAV VARIABLE AIR VOLUME VEL VELOCITY VENT VENTILATION VERT VERTICAL VOL VOLUME VTR VENT THROUGH ROOF W WASTE WB WET BULB WCO WALL CLEAN OUT WH WALL HYDRANT ABBREVIATIONS FIRE DAMPER SMOKE DAMPER MOTORIZED DAMPER MANUAL BALANCING DAMPER BACKDRAFT DAMPER COMBINATION FIRE/SMOKE DAMPER RECTANGULAR SUPPLY/OUTSIDE AIR DUCT RISE RECTANGULAR RETURN/TRANSFER AIR DUCT RISE MECHANICAL EQUIPMENT ROUND DUCT SIZE TAG (DIAMETER) EXISTING PIPE TAG DOMESTIC WATER METER FLOW MEASURING AND BALANCING DEVICE BALL VALVE CHECK VALVE ITEM TO BE DEMOLISHED AREA NOT IN CONTRACT AC AIR CONDITIONING UNIT ACC AIR COOLED CONDENSER ACCU AIR COOLING CONDENSING UNIT AFMS AIR FLOW MEASURING STATION AHU AIR HANDLING UNIT AS AIR SEPARATOR B BOILER CF CABINET FAN CF CHEMICAL FEEDER CFP CHEMICAL FEEDER PUMP CH CHILLER CRU CONDENSATE RETURN UNIT CT COOLING TOWER CUH CABINET UNIT HEATER CWP CONDENSER WATER PUMP CHWP CHILLED WATER PUMP DAH DUCTLESS AIR HANDLER DHP DUCTLESS HEAT PUMP DCP DOMESTIC WATER CIRCULATING PUMP EUH ELECTRIC UNIT HEATER EDC ELECTRIC DUCT COIL ET EXPANSION TANK EWH ELECTRIC WATER HEATER FCU FAN COIL UNIT FP FIRE PUMP GI GREASE INTERCEPTOR GRV GRAVITY ROOF VENTILATOR H HUMIDIFIER HWP HEATING WATER PUMP HX HEAT EXCHANGER HPU HEAT PUMP UNIT HRU HEAT RECOVERY UNIT ILC INLINE CENTRIFUGAL PF PROPELLER FAN PV POWER VENTILATOR PWF POWER WALL FAN RE RETURN/EXHAUST FAN RTU ROOFTOP UNIT SA SHOCK ABSORBER SAT SOUND ATTENUATOR SEP SEWAGE EJECTOR PUMP SF SUPPLY FAN SP SUMP PUMP UH UNIT HEATER US UTILITY SET UV UNIT VENTILATOR VAV VARIABLE AIR VOLUME WH WATER HEATER EQUIPMENT ABBREVIATIONS DUCT BEING DEMOLISHED PIPING BEING DEMOLISHED THREE WAY VALVE BUTTERFLY VALVE ROUND SUPPLY/OUTSIDE AIR DUCT RISE ROUND RETURN/TRANSFER AIR DUCT RISE RECTANGULAR EXHAUST/RELIEF AIR DUCT RISE ROUND EXHAUST/RELIEF AIR DUCT RISE ABOVE GROUND PIPING PIPE SIZE TAG (DIAMETER) DROP DROP DROP DROP DROP DROP EXISTING MECHANICAL EQUIPMENT PIPE RISE PIPE DROP PIPE TEE REDUCING 45 DEGREE TEE 45 DEGREE TEE 1 - --- BELOW GROUND PIPING PIPE INVERT ELEVATION TAG PIPE SLOPE TAG GE/A GREASE EXHAUST AIR SE/A SMOKE EXHAUST AIR MECHANICAL EQUIPMENT TAG (REFER TO OTHER DISCIPLINE FOR ADDITIONAL INFORMATION) MECHANICAL EQUIPMENT FOR REFERENCE PG PROPANE GAS MOTORIZED CONTROL VALVE PRESSURE REDUCING VALVE SOLENOID VALVE THREE WAY MOTORIZED CONTROL VALVE Room 1 INVERT: -10' -1" 1/8" / 12" SLOPE FLUE EXHAUST GAS FLUE C/A COMBUSTION AIR S-O/A SUPPLY AIR (100% OUTSIDE AIR) VAV-XX (X)VAV-XX VAV-XX GRILLES, REGISTERS, AND DIFFUSERS TAG CFM SUPPLY OUTLET RETURN/EXHAUST INLET LINEAR DIFFUSER LINEAR DIFFUSER TAG CFM TYPE (SEE SCHEDULE) TYPE (SEE SCHEDULE) SECTORIZING BAFFLE OR BLANKOFF PANEL S2 0 S6 0 CARBON DIOXIDE SENSOR DUCT SMOKE DETECTOR E-STOP HUMIDITY SENSOR TEMPERATURE SENSORT CO2 H E D 1 FIRE WALL LEGEND 2-HR FIRE WALL 23551 E A H R D N O P TR HM.DVI A NGIN REE NH NOFO A N SEAL A L I OACR SES L I SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 M-001 MECHANICAL ABBREVIATIONS, LEGEND, SUMMARIES & UL DETAIL 2022075.00 11/22/2024 SLAB HEATED:NO HORIZONTAL/VERTICAL...N/A R-VALUE OF INSULATION:N/A U-VALUE OF TOTAL ASSEMBLY: 0.9 BTU/HR/SF/F DESCRIPTION OF ASSEMBLY: 6" CONCRETE SLAB FLOORS SLAB ON GRADE R-VALUE OF INSULATION:N/A U-VALUE OF TOTAL ASSEMBLY: N/A DESCRIPTION OF ASSEMBLY:N/A FLOORS OVER UNCONDITIONED... R-VALUE OF INSULATION:N/A U-VALUE OF TOTAL ASSEMBLY: N/A DESCRIPTION OF ASSEMBLY:N/A WALLS BELOW GRADE (EACH... DOOR R-VALUES: 0.37 (HR-SF-F)/BTU PROJECTION FACTOR:<0.5 SHADING COEFFICIENT:0.25 U-VALUE OF TOTAL ASSEMBLY 0.3 BTU/HR/SF/F OPENINGS (WINDOWS OR DOORS... R-VALUE OF INSULATION: R-13 + R-6 (HR-SF-F)/BTU U-VALUE OF TOTAL ASSEMBLY: 0.067 BTU/HR/SF/F DESCRIPTION OF ASSEMBLY: INSIDE SURFACE RESISTANCE, 5/8" GYPSUM BOARD, R-13 BATT, R-6 CONTINUOUS INSULATION, SINGLE LAYER MINERAL FIBER COMPRESSED AT METAL WALL GIRTS, METAL SIDING, OUTSIDE SURFACE RESISTANCE EXTERIOR WALLS (EACH ASSEMBLY) TOTAL SQ.FT OF SKYLIGHTS IN EA.... - U-VALUE OF SKYLIGHT:- SKYLIGHTS IN EACH ASSEMBLY:- R-VALUE OF INSULATION: R-30 (HR-SF-F)/BTU U-VALUE OF TOTAL ASSEMBLY: 0.04 BTU/HR/SF/F DESCRIPTION OF ASSEMBLY: INSIDE SURFACE RESISTANCE, EXPOSED VINYL FACED REINFORCED INSULATION WITH THERMALBLOCKS (R-30 MINIMUM) ON METAL ROOF PURLINS, OUTSIDE SURFACE RESISTANCE ROOF CEILING ASSEMBLY (EACH ASSEMBLY) THERMAL ENVELOPE PERFORMANCE (ASHRAE 90.1) PRESCRIPTIVE (ASHRAE 90.1) PERFORMANCE (([ 2018 NCECC ][ ENERGY CODE ])) X PRESCRIPTIVE ([ 2018 NCECC ][ ENERGY CODE ]) METHOD OF COMPLIANCE: CLIMATE ZONE:3 THE FOLLOWING DATA SHALL BE CONSIDERED MINIMUM AND ANY SPECIAL ATTRIBUTE REQUIRED TO MEET THE ENERGY CODE SHALL ALSO BE PROVIDED. EACH DESIGNER SHALL FURNISH THE REQUIRED PORTIONS OF THE PROJECT INFORMATION FOR THE PLAN DATA SHEET. IF PERFORMANCE METHOD, STATE THE ANNUAL ENERGY COST FOR THE STANDARD REFERENCE DESIGN VS ANNUAL ENERGY COST FOR THE PROPOSED DESIGN. ENERGY REQUIREMENTS: ENERGY SUMMARY LIST EQUIPMENT EFFICIENCIES: SEE SCHEDULES SIZE CATEGORY, IF OVERSIZED STATE... N... CHILLER SIZE CATEGORY, IF OVERSIZED STATE... N... BOILER SIZE CATEGORY OF UNIT: SEE SCHEDULES COOLING EFFICIENCY: SEE SCHEDULES HEATING EFFICIENCY: SEE SCHEDULES DESCRIPTION OF UNIT: SEE SCHEDULES UNITARY MECHANICAL SPACING CONDITIONING SYSTEM HANGAR HEATING LOAD: 742 ... OFFICE COOLING LOAD: 60.8 MBH OFFICE HEATING LOAD: 51.2 ... *DESIGN- NOT CONTROLLED RELATIVE HUMIDITY 60% RH* SUMMER DRY BULB 75 °F WINTER DRY BULB 70 °F INTERIOR DESIGN CONDITIONS SUMMER DRY BULB 93 °F WINTER DRY BULB:23 °F CLIMATE ZONE 3A - WARM/HUMID MECHANICAL SYSTEMS, SERVICE SYSTEMS AND EQUIPMENT MECHANICAL SUMMARY 0 11/22/24 ISSUED FOR CONSTRUCTION PLAN NORTH TRUE NORTH NN 1 1.1 2 3 4 5 5.9 6 A B B.1 C D E F F.9 G MH401 1 MH401 2 RH01 RH02 RH03 RH04 F01 F02 SF01 SF02 EF01 EF02 HANGAR 100 4"Ø VENT DUCT, TYP. 4"Ø INTAKE DUCT, TYP.CONCENTRIC VENT, TYP. 23551 E A H R D N O P TR HM.DVI A NGIN REE NH NOFO A N SEAL A L I OACR SES L I SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 MH101 MECHANICAL FLOOR PLAN - HVAC 2022075.00 11/22/2024 KEYNOTES 1 COORDINATE MOUNTING HEIGHT WITH G.C. AND MANUFACTURERS INSTALLATION INSTRUCTIONS. 2 COORDINATE MOUNTING HEIGHT WITH ARCHITECT AND MANUFACTURERS INSTALLATION INSTRUCTIONS. 1 1/8" = 1'-0"1 FLOOR PLAN - HVAC 0 11/22/24 ISSUED FOR CONSTRUCTION 1 1 1 2 2 22 2 2 FLOOR PLAN SHEET NOTES 1. MAINTAIN MANUFACTURER'S CLEARANCE REQUIREMENTS FOR INDOOR EQUIPMENT. 2. MECHANICAL CONTRACTOR TO COORDINATE WITH OTHER TRADES PRIOR TO BEGINNING WORK. 3. REFER TO ARCHITECTURAL DRAWINGS FOR RATED ASSEMBLY UL NUMBERS (WALLS, FLOOR / CEILINGS, ETC.. 4. COORDINATED CONDENSATE PIPE ROUTING WITH GENERAL CONTRACTOR AND OWNER, TYPICAL. 5. CONCERNING DIFFUSER LAYOUT AND CEILING TYPE, REFER TO ARCHITECTURAL PLANS FOR FURTHER INFORMATION. 1 1.1 2 3 4 5 5.9 6 A B B.1 C D E F F.9 G MH402 1 MH402 2 HANGAR 100 RH01 RH02 RH03 RH04 F01 F02 SF01 SF02 EF01 EF02 T T PLAN NORTH TRUE NORTH NN 23551 E A H R D N O P TR HM.DVI A NGIN REE NH NOFO A N SEAL A L I OACR SES L I SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 MH102 MECHANICAL RCP & T-STAT LOCATION FLOOR PLAN -HVAC 2022075.00 11/22/2024 1/8" = 1'-0"1 RCP & T-STAT LOC. FLOOR PLAN - HVAC 0 11/22/24 ISSUED FOR CONSTRUCTION PLAN NORTH TRUE NORTH NN 1 1.1 2 3 A B B.1 PARTS STORAGE 116 ELEC/ IT 114 RISER 115 CORR 110 RESTROOM 107 RESTROOM 108 JAN 109 BREAK 111 CLOSET 112 AH 0 1 EF03 EF04 EUH01 S5 190 EF 0 5 L01 220 L02 260 S2 145 S5 25 S5 50 S5 50 S1 55 22 " x 1 6 " 10 " x 1 0 " 22 " x 1 6 " 10"x10" 10 " x 1 0 " 6"Ø 6"Ø 8" Ø 10 " Ø R3 - 8" Ø R1 - 6"Ø 18 " x 1 4 " MANUAL VOUME DAMPER, TYP. HP01 4 5 5.9 6 A B B.1 DA H 0 1 DHP01 ENTRY/ LOBBY 101 CONFERENCE 106 OPEN OFFICE 103 OFFICE 105 CORR 102 S2 155 S2 155 S3 250 S3 250 S2 200 S4 125 S4 125 S4 125 R1 - S1 90 R1 - R1 - 18 " x 1 4 " 22 " x 1 6 " 18 " x 1 4 " 22 " x 1 6 " 14 " x 1 2 " 12 " x 1 2 " 10 " x 1 0 " 8"Ø 8"Ø 8"Ø 8"x8" 12"x12" 12"x12" R2 - R2 - R2 - 23551 E A H R D N O P TR HM.DVI A NGIN REE NH NOFO A N SEAL A L I OACR SES L I SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 MH401 MECHANICAL ENLARGED PLANS -HVAC 2022075.00 11/22/2024 1/4" = 1'-0"1 ENLARGED OFFICE PLAN 2 1/4" = 1'-0"2 ENLARGED OFFICE PLAN 1 0 11/22/24 ISSUED FOR CONSTRUCTION FLOOR PLAN SHEET NOTES 1. MAINTAIN MANUFACTURER'S CLEARANCE REQUIREMENTS FOR INDOOR EQUIPMENT. 2. MECHANICAL CONTRACTOR TO COORDINATE WITH OTHER TRADES PRIOR TO BEGINNING WORK. 3. REFER TO ARCHITECTURAL DRAWINGS FOR RATED ASSEMBLY UL NUMBERS (WALLS, FLOOR / CEILINGS, ETC.. 4. COORDINATED CONDENSATE PIPE ROUTING WITH GENERAL CONTRACTOR AND OWNER, TYPICAL. 5. CONCERNING DIFFUSER LAYOUT AND CEILING TYPE, REFER TO ARCHITECTURAL PLANS FOR FURTHER INFORMATION. KEYNOTES 1 PROVIDE MOTORIZED DAMPER AND OA DAMPER IN OUTSIDE AIR DUCT AS SHOWN. 2 PROVIDE 3/4" INSULATED, TRAPPED CONDENSATE PIPING. ROUTE DOWN INSIDE OF EXTERIOR WALL, PENETRATE APPROXIMATELY 8" ABOVE GRADE, PENETRATE SIDE OF DOWNSPOUT AS SHOWN. 3 PROVIDE RERIGERANT PIPING LINE-SET ROUTED ABOVE CEILING. 1 2 2 3 3 1 1.1 2 3 A B B.1 AH 0 1 EF04 EF03 PARTS STORAGE 116 ELEC/ IT 114 RISER 115 CORR 110 RESTROOM 107 RESTROOM 108 JAN 109 BREAK 111 CLOSET 112 4 5 5.9 6 A B B.1 ENTRY/ LOBBY 101 CONFERENCE 106 OPEN OFFICE 103 OFFICE 105 CORR 102 T AH01 T DAH01 PLAN NORTH TRUE NORTH NN 23551 E A H R D N O P TR HM.DVI A NGIN REE NH NOFO A N SEAL A L I OACR SES L I SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 MH402 MECHANICAL ENLARGED RCP FLOOR PLANS - HVAC 2022075.00 11/22/2024 1/4" = 1'-0"1 ENLARGED RCP FLOOR PLAN 2 - HVAC 1/4" = 1'-0"2 ENLARGED RCP FLOOR PLAN 1 - HVAC 0 11/22/24 ISSUED FOR CONSTRUCTION FLOOR PLAN SHEET NOTES 1. MAINTAIN MANUFACTURER'S CLEARANCE REQUIREMENTS FOR INDOOR EQUIPMENT. 2. MECHANICAL CONTRACTOR TO COORDINATE WITH OTHER TRADES PRIOR TO BEGINNING WORK. 3. REFER TO ARCHITECTURAL DRAWINGS FOR RATED ASSEMBLY UL NUMBERS (WALLS, FLOOR / CEILINGS, ETC.. 4. COORDINATED CONDENSATE PIPE ROUTING WITH GENERAL CONTRACTOR AND OWNER, TYPICAL. 5. CONCERNING DIFFUSER LAYOUT AND CEILING TYPE, REFER TO ARCHITECTURAL PLANS FOR FURTHER INFORMATION. ~ AUXILIARY DRAIN PAN FLOAT SWITCH. INTERLOCK TO SHUT DOWN SYSTEM DRAIN PAN FLEXIBLE CONNECTION, TYP. S/A DUCT -- SEE MECHANICAL PLAN FOR SIZES AIR HANDLER M MOTORIZED DAMPER MANUAL DAMPER; BALANCE TO AIRFLOW SHOWN IN SPLIT SYSTEM SCHEDULE O/A DUCT -- SEE MECHANICAL PLAN FOR SIZES R/A DUCT -- SEE MECHANICAL PLAN FOR SIZES ELEVATE A MINIMUM OF 4" VIBRATION ISOLATOR (EACH CORNER) PRIMARY CONDENSATE DRAIN WITH TRAP. EXTEND AS SHOWN ON PLANS 2x4 TREATED WOOD SUPPORT, TYP. OF 2 MEZZANINE FLOOR NOTES: 1. TRAPEZE HANGERS SHALL BE PROVIDED FOR ALL DUCT WORK. TRAPEZE HANGERS CANNOT BE USED FOR BRANCH DUCT WORK 12" IN WIDTH AND SHORTER REFER TO STRAP HANGER DETAIL. 2. SUPPORTS SHALL BE SPACED AND SIZED AS PER SPECIFICATIONS. 3. RIGID INSULATION SHALL EXTEND MINIMUM OF 3" BEYOND STRUT ON BOTH SIDES. MAINTAIN VAPOR BARRIER ACROSS STRUT. TRAPEZE HANGER DETAIL STRAP HANGER DETAIL UNISTRUT DUCT INSULATION & VAPOR BARRIER HANGER STRAP 1" 6" M I N . MAX 12" THREADED HANGER ROD SIZE AND MATERIAL PER SPECIFICATION MIN .9 lb/cft DENSITY RIGID INSULATION AT SHIELD DIVERGING FLOW RADIUS ELBOW 20° MAXIMUM AIR FLOW W W R=1.5 W CONVERGING FLOW RECTANGULAR ELBOW 30° MAXIMUM AIR FLOW TURNING VANES DOUBLE THICKNESS W W (BRANCH FLOW LESS THAN 25% OF MAIN FLOW) 45° (4" MINIMUM) W BRANCH BRANCH TAKE-OFFS L MAIN L=1/4 W DUCT OFFSETS (R = W) WHERE POSSIBLE FULL RADIUS ELBOWS W R R W TC2R = TWO TAPS V = 1.414(C+D)+9.66 Q = A/2+.707C+2.414 H = .707A+.5C+2" DIE-STAMPED 45° AND 90° DIMENSIONS: CR = 1.5A S = 2" R A L S BA 1" C CONICAL LATERAL H 4"S 1"LC2 = TWO TAPS V = 1.414C+4.83 1" * REDUCING CONICAL TEE A S V Q 5-1/4" S C X S = 2" LC = ONE TAP DIMENSIONS: V = C+4" TCR = ONE TAP V = C+D+8" S * DIMENSIONS: 1" CONICAL TEE S V 5-1/4" S C A S = 2" DIMENSIONS: A-B(12" MAX) V = C+4" V = C+D+8" TC = ONE TAP TC2 = TWO TAPS S = 2" * V S L = A/2+1" DIMENSIONS: M = .207A Z = SPECIFY OFFSET V = 2A UNLESS SPECIFIED OFFSET S V A DIMENSIONS: Z S = 2" A Y-BRANCH 90° 1"S A M L A S S = 2" DIMENSIONS: (4" MINIMUM & 12" MAXIMUM) ECCENTRIC S REDUCERS CONCENTRIC A S Z A B A-B S B S S = 2" A-B (12" MAXIMUM) BRANCHY VD MAIN Y W 15° MAXIMUM BOTH SIDES (BRANCH FLOW GREATER THAN 25% OF MAIN FLOW) TAKE-OFF STANDARD RECTANGULAR BRANCH 4" MINIMUM L = 1/4 W OR L WVOLUME FLOW AIR STANDARD RECTANGULAR DUCT BRANCH TAKE-OFF (BRANCH FLOW LESS THAN 25% OF MAIN FLOW) (BRANCH FLOW LESS THEN 25% OF MAIN FLOW) DUCT BRANCH CONNECTIONS ALTERNATE RECTANGULAR TO ROUND BELL MOUTH CONNECTION WHERE HEIGHT OF MAIN DUCT PERMITS CONNECTION TO ROUND BOOT 90° RECTANGULAR CONNECTION TO ROUND BOOT 45° RECTANGULAR TO ROUND TRANSITION BOOT WITH RECTANGULAR STANDARD RECTANGULAR FLOW AIR 45° 45°ELBOW WITH DOUBLE THICKNESS TURNING VANES AIR FLOW VOLUME DAMPER VOLUME DAMPER DAMPER ADJUSTABLE HANGER WITH ROLLER LOCKING NUT SUPPORT NUT INSULATION PIPE PIPE COVERING PROTECTION 16 GA SADDLE GALVANIZED INSULATION SHIELD 12"LONG. NOTES: CLEVIS HANGER (FOR 1/2" UP TO HEAVY DUTY & INCL. 2" PIPE) (FOR 2" TO 6" PIPE & FOR HVAC HOT WATER PIPING ALL SIZES) 1. THIS DETAIL SHALL BE USED AS A GUIDE. ALL HANGERS SHALL MEET THE REQUIREMENTS OF THE SPECIFICATIONS. 2. PIPE 6" AND LARGER SHALL HAVE ROLLER SUPPORTED WITH DUAL RODS. 3. FOR CHW SERVICE OVER 3" REPLACE SADDLE WITH 12" LONG 14 GA SHIELD WITH RIGID INSULATION BETWEEN PIPE AND SHIELD. 4. WHERE TRAPEZE HANGERS ARE USED FOR HEATING HOT WATER PROVIDE ROLLERS. SEE SPECIFICATIONS FOR BUILDING ATTACHMENT REQUIREMENTS PIPE SIZE 2 1/2" 1/2" - 2" LOAD SCHEDULE 5" 4" 3" 14' 10' 14' 5/8"∅ 5/8"∅ 5/8"∅ 8' 10'5/8"∅ 1/2"∅ ROD SIZEMAXIMUM SPACING HIGH DENSITY INSULATED STRUCTURAL INSERT (600 PSI MINIMUM COMPRESSIVE STRENGTH) AT SHEILD DN 24" W/ 2" RIGID BOARD INSULATION) INCLUDING ANY UNUSED LOUVER (INSULATE ALL EXPOSED PARTS & 12" UP SIDE JOINTS PITCH TO OUTSIDE SHOWN OTHERWISE ON PLANS) DUCT, 12" X 12" MIN (UNLESS ACCESS DOOR HALF HEIGHT OF SOLDER BOTTOM JOINTS SEAL AND CAULK ALL AROUND LOUVER PLENUM 1/2" BIRDSCREEN STORM- PROOF LOUVER CAULK ALL AROUND ACCESS DOOR ON SIDE OF DUCT (APPLIES TO INTAKE LOUVER ONLY) ROUGHEN SURFACE ANCHOR BOLT; SIZE PER EQUIPMENT MANUFACTURER. 1 LAYER OF MAT; 6X6-W2.9 X W2.9 WWF 1/2"DIA. EPOXY GROUT ANCHOR NOT MORE THAN 3' ON CTR. NOTE: 1.MESH SHALL BE FURNISHED IN SHEETS. 2.ALL PAD EDGES SHALL BE CHAMFERED. 3.CONCRETE COMPRESSIVE STRENGTH SHALL BE 3,000 PSI AT 28 DAYS 4.ONLY ANCHOR EQUIPMENT WITH MANUFACTURER SUPPLIED ANCHOR MOUNTS 4" MIN. 6" 3" 2" RIGID ROUND DUCT NYLON CLAMP OVER FLEX DUCT (2) WRAPS "B" TAPE AND NYLON CLAMP OVER INSULATION INSULATION FLEX DUCT #10 x 3/4" SELF TAPPING CADMIUM PLATED SHEET METAL SCREWS . NO POP RIVETS ALLOWED HANGER STRAPS 45º EXPANDED THROAT TAKE-OFF BALANCE DAMPER WITH LOCKING QUADRANT WIRE HANGER TO STRUCTURE FLEXIBLE DUCT (U.L.181 "B" ENCLOSURE SYSTEM) LIMIT RUN TO 5'-0" MAX. ROUNF TO SQUARE OR RECTANGULAR ADAPTER CEILING RIGID ROUND DUCT. SEE PLANS FOR SIZE. WRAP WITH EXTERNAL INSULATION12" WIDE 24 GA. SHIELD 2" x 24" GA. STRAPS PIPE FULL SIZE OF EQUIPMENT DRAIN CONNECTION THREADED CAP (TYP.)PIPE FULL SIZE OF EQUIPMENT DRAIN CONNECTION THREADED CAP (TYP.) SEE NOTE 3 SEE NOTE 4 FLOW DRAW THRU DRAIN UNION (TYP.) "2 SEE NOTE 2 BLOW THRU DRAIN 1. LOCATE TRAPS SO AS TO BE ACCESSIBLE FOR CLEANING. 2. HEIGHT SHALL BE EQUAL TO UNIT MAXIMUM TOTAL STATIC PRESSURE PLUS 1/2". 3. HEIGHT SHALL BE EQUAL TO UNIT MAXIMUM NEGATIVE STATIC PRESSURE PLUS 1". 4. HEIGHT SHALL BE 1/2" OF HEIGHT INSTALLED ON NOTE 3. 5. PIPE TO NEAREST DRAIN. 6. TRAP SHALL NOT BLOCK ACCESS TO EQUIPMENT. 7. PROVIDE UNIONS AT INLET AND OUTLET OF TRAP. NOTES: 23551 E A H R D N O P TR HM.DVI A NGIN REE NH NOFO A N SEAL A L I OACR SES L I SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 M-501 MECHANICAL DETAILS 2022075.00 11/22/2024 NO SCALE1RECTANGULAR DUCT FITTING DETAILS NO SCALE2ROUND DUCT FITTING DETAILS NO SCALE3ROUND/RECT. DUCT TAKE-OFF FITTING DETAILS NO SCALE5PIPE HANGER SUPPORT DETAIL NO SCALE4LOUVER PLENUM DETAIL NO SCALE6EQUIPMENT HOUSEKEEPING PAD DETAIL NO SCALE8TYPICAL DIFFUSER CONNECTION DETAIL NO SCALE9TYPICAL AIR HANDLER ON PLATFORM DETAIL 12" = 1'-0"7 TYPICAL EQUIPMENT CONDENSATE DRAIN DETAIL NO SCALE10TYPICAL DUCT SUPPORT DETAIL 0 11/22/24 ISSUED FOR CONSTRUCTION 23551 E A H R D N O P TR HM.DVI A NGIN REE NH NOFO A N SEAL A L I OACR SES L I SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 M-601 MECHANICAL SCHEDULES 2022075.00 11/22/2024 I WARRANTY: 3 YEARS ON ALL PARTS AND 10 YEARS ON TUBES, REFLECTORS AND BURNER CABINET H HANGING CHAIN SETS (CHAIN, KARABINER CLIPS, BEAM CLAMPS, EYE BOLTS) G 4" FITTED OUTSIDE COMBUSTION AIR COLLAR WITH KIT (FLEX HOSE AND CLAMPS) F 4" VENT ADAPTER E TOTALLY ENCLOSED BURNER CABINET, FAN CANNOT BE OUTSIDE OF BURNER BOX D 24V BMS DIGITAL TOUCH SCREEN 2-STAGE 7-DAY PROGAMMABLE THERMOSTAT WITH 24V TRANSFORMER MOUNTED INSIDE BURNER CABINETS WITH REMOTE BLACK BULB SENSORS C POLISHED ALUMINUM REFLECTORS AND END CAPS (NO GAPS) - HIGH EFFICIENT - 100% REFELCTION B 4", 16GA. HEAT TREATED ALUMINIZED STEEL COMBUSTION CHAMBERS AND RADIANT TUBING ACCESSORIES: A 3/4" BALL VALVE AND 3/4" STAINLESS STEEL FLEX GAS CONNECTOR 3 REFER TO MANUFACTURERS INSTALLATION INSTRUCTIONS FOR MOUNTINGLOCATION REQUIREMENTS AND RECOMMENDATIONS. 2 VENT IN ACCORDANCE WITH BUILDING CODE AND MANUFACTURER'S INSTRUCTIONS. NOTES: 1 REFER TO SPECIFICATIONS FOR FURTHER INFORMATION. RH04 ADVANCED RADIANT SYSTEMS DU220-U60 NATURAL GAS 220 165 32'-10" 75 14 4 4 120/1/60 1.0 1,2,3 A THRU I RH03 ADVANCED RADIANT SYSTEMS DU220-U60 NATURAL GAS 220 165 32'-10" 75 14 4 4 120/1/60 1.0 1,2,3 A THRU I RH02 ADVANCED RADIANT SYSTEMS DU220-U60 NATURAL GAS 220 165 32'-10" 75 14 4 4 120/1/60 1.0 1,2,3 A THRU I RH01 ADVANCED RADIANT SYSTEMS DU220-U60 NATURAL GAS 220 165 32'-10" 75 14 4 4 120/1/60 1.0 1,2,3 A THRU I HIGH FIRE (MBH) LOW FIRE (MBH) LENGTH EFF.(%) MAX. INLET PRESS (IN WC) OUTLET (IN) INLET (IN) (V/PH/HZ) (A) DRAWING CODE BASIS OF DESIGN MANUFACTURER BASIS OF DESIGN MODEL FUEL GAS FLUE COMBUSTION VOLTAGE FLA NOTES ACCESSORIES GAS-FIRED RADIANT HEATER SCHEDULE E FACTORY INSTALLED DISCONNECT SWITCH D BUILT-IN TAMPER PROOF THERMOSTAT C AUTOMATIC RESET THERMAL LIMIT B AUTOMATIC FAN DELAY CIRCUIT ACCESSORIES: A SEMI-RECESS MOUNTING ADAPTER 2 HEATER MUST BE LISTED BY ETL. NOTES: 1 REFER TO SPECIFICATIONS FOR FURTHER INFORMATION. EUH01 MARKEL E3321TD-RP QMARK, INDEECO WALL HEATER 175 HORIZONTAL 0.75 1 2,560 120/1/60 6.3 30 3'-0" A.F.F. 1,2 A,B,C,D,E TYPE FAN DISCHARGE CAPACITY (KW) STEPS BTU'S POWER (V/PH/HZ) FLA (A) DRAWING CODE BASIS OF DESIGN MANUFACTURER BASIS OF DESIGN MODEL ALTERNATE APPROVED MANUFACTURERS DESCRIPTION ELECTRIC COIL ELECTRICAL WEIGHT (LBS) MOUNTING HEIGHT (FT) NOTES ACCESSORIES ELECTRIC HEATER SCHEDULE G TWO-STAGE HEAT PUMP F FILTER RACK E PROVIDE TRANE TCONT830AS52DA PIVOT COMMERCIAL THERMOSTAT OR APPROVED EQUAL D SINGLE POINT POWER CONNECTION C LOW AMBIENT COOLING OPERATION TO 40F B ODU COIL SEACOAST PROTECTION ACCESSORIES: A ELECTRIC HEATER AS SCHEDULED 2 IF AN ALTERNATE... NOTES: 1 REFER TO... AH01 / HP01 TRANE GAM5B0C60/4TWR60 DAIKIN, YORK HEAT PUMP 57.2 46.0 93.0 77.5 64.7 SEER 17.5 36.2 23.0 63.9 COP 4.1 2,000 220 0.50 10.8 208/3/60 46.0 50 208/1/60 35.0 60 R-454B 60 60 170 300 1,2 A,B,C,D,E,F,G (V/PH/HZ) (MCA) (MOCP) (V/PH/HZ) (MCA) (MOCP) NET TOTAL (MBH) NET SENSIBLE (MBH) AMBIENT ( °F) EDB ( °F) EWB ( °F) EFFICIENCY (AHRI) TOTAL (MBH) AMBIENT ( °F) EDB ( °F) EFFICIENCY SUPPLY AIRFLOW (CFM) OUTSIDE AIRFLOW (CFM) ESP (IN. WG.) AUX HEAT CAP (KW) INDOOR UNIT OUTDOOR UNIT TYPE MAXIMUM LENGTH (FT.) MAXIMUM HEIGHT DIFFERENTIAL (FT.) INDOOR UNIT OUTDOOR UNIT DRAWING CODE (IDU/ODU) BASIS OF DESIGN MANUFACTURER BASIS OF DESIGN MODEL (IDU/ODU) ALTERNATE APPROVED MANUFACTURERS SYSTEM TYPE COOLING PERFORMANCE HEATING PERFORMANCE - HEAT PUMP INDOOR UNIT ELECTRICAL REFRIGERANT PIPING WEIGHT (LBS.) NOTES ACCESSORIES SPLIT SYSTEM SCHEDULE N ISOLATOR KIT M INTEGRAL BACKDRAFT DAMPER L WHITE PLASTIC GRILLE K FAN SPEED CONTROLLER 5 AMP 120V J WALL COLLAR I WEATHERHOOD-STL 45D H WIREGUARD-MOTOR SIDE G GRAVITY SHUTTER (STD) -27 F WEATHERHOOD 90 DEGREE E END SAFETY SCREEN D LONG WALL COLLAR C MOTORIZED CENTER PIVOT (HEAVY DUTY) -27 115V B DISCONNECT NEMA 1-PRE-WIRED ACCESSORIES: A FAN MOUNTED SPEED CONTROL 3 CONTROLLED VIA ON/OFF/AUTO SWITCH WITH THERMOSTAT. 2 CONTROLLED VIA OCCUPANCY SENSOR. REFER TO ELECTRICAL PLANS. NOTES: 1 REFER TO SPECIFICATIONS FOR FURTHER INFORMATION. EF05 COOK GC-186 GREENHECK, TWIN CITY CEILING-MOUNTED VENTILATORS EXHAUST DIRECT BACKDRAFT - - 120 0.50 847 - ECM 63 -120/1/60 0.8 - - 2.5 20 1,2 K,L,M,N EF04 COOK GC-186 GREENHECK, TWIN CITY CEILING-MOUNTED VENTILATORS EXHAUST DIRECT BACKDRAFT - - 120 0.50 847 - ECM 63 -120/1/60 0.8 - - 2.5 20 1,2 K,L,M,N EF03 COOK GC-148 GREENHECK, TWIN CITY CEILING-MOUNTED VENTILATORS EXHAUST DIRECT BACKDRAFT - - 70 0.50 902 - ECM 36 - 120/1/60 0.4 - - 2.0 20 1,2 K,L,M,N EF02 COOK 24XW28D17 GREENHECK, TWIN CITY CENTRIFUGAL VENTILATORS - WALL EXHAUST DIRECT GRAVITY OPEN - EC 1.25 6,500 0.125 1,276 1,725 ECM - 0.839 120/1/60 11.6 - - 18.5 190 1,3 A,B,G,H,I,J EF01 COOK 24XW28D17 GREENHECK, TWIN CITY CENTRIFUGAL VENTILATORS - WALL EXHAUST DIRECT GRAVITY OPEN - EC 1.25 6,500 0.125 1,276 1,725 ECM - 0.839 120/1/60 11.6 - - 18.5 190 1,3 A,B,G,H,I,J SF02 COOK 24XWS28D17 GREENHECK, TWIN CITY CENTRIFUGAL VENTILATORS - WALL SUPPLY DIRECT GRAVITY OPEN - EC 1.25 6,500 0.125 1,276 1,725 ECM - 0.839 120/1/60 11.6 - - 18.5 310 1,3 A,B,C,D,E,F SF01 COOK 24XWS28D17 GREENHECK, TWIN CITY CENTRIFUGAL VENTILATORS - WALL SUPPLY DIRECT GRAVITY OPEN - EC 1.25 6,500 0.125 1,276 1,725 ECM - 0.839 120/1/60 11.6 - - 18.5 310 1,3 A,B,C,D,E,F AIRFLOW (CFM) ESP (IN. WG.) FAN RPM MOTOR RPM MOTOR TYPE MOTOR SIZE (W) MOTOR SIZE (HP) V/PH/HZ FLA (A) MCA (A) MOCP (A) DRAWING CODE BASIS OF DESIGN MANUFACTURER BASIS OF DESIGN MODEL ALTERNATE APPROVED MANUFACTURERS FAN TYPE SERVICE DRIVE TYPE DAMPER MOTOR ENCLOSURE FAN ENERGY INDEX (FEI) CAPACITIES ELECTRICAL SONES WEIGHT (LBS.) NOTES ACCESSORIES POWER VENTILATOR SCHEDULE ACCESSORIES: A BIRD SCREENING (MATERIAL TO MATCH LOUVER MATERIAL) 4 AMCA 550 LISTED (WATER PENETRATION) 3 AMCA 540 LISTED (IMPACT RESISTANCE) 2 FINISH AS SELECTED BY ARCHITECT FROM MANUFACTURER'S FULL RANGE OF COLOR AND GLOSS. NOTES: 1 REFER TO SPECIFICATIONS FOR FURTHER INFORMATION. L02 RUSKIN HZ700MD VENT PRODUCTS, POTTORFF FIXED EXTERIOR FLANGE HORIZONTAL, DRAINABLE-BLADE ALUMINUM 7 16 X 16 EXHAUST 260 0.63 0.05 - 1,2,3,4 A L01 RUSKIN HZ700MD VENT PRODUCTS, POTTORFF FIXED EXTERIOR FLANGE HORIZONTAL, DRAINABLE-BLADE ALUMINUM 7 16 x 16 INTAKE 220 0.63 0.04 - 1,2,3,4 A FREE AREA (SF) S.P. LOSS (IN. H20) WATER PENETRATION (OZ./SF) DRAWING CODE BASIS OF DESIGN MANUFACTURER BASIS OF DESIGN MODEL ALTERNATE APPROVED MANUFACTURERS TYPE FRAME DESCRIPTION MATERIAL LOUVER DEPTH (IN.) SIZE (W x H) (IN.) SERVICE AIRFLOW (CFM) PERFORMANCE RATINGS NOTES ACCESSORIES LOUVER SCHEDULE C 24" DOWN ROD AND ASSOCIATED MOUNTING HARDWARE B STANDARD WALL MOUNT VARIABLE SPEED CONTROLLER (REFER TO ELECTIRCAL PLANS FOR LOCATION) ACCESSORIES: A DIRECT DRIVE MOTOR, INTEGRAL VFD AND AIRFOIL BLADES 5 REFER TO ARCHITECTURAL DRAWINGS FOR COLOR AND FINISH. 4 FAN AND MOTOR TO BE IP-66 RATED, SUITABLE FOR INDOOR AND OUTDOOR USE. 3 FAN TO INCLUDE 3-YEAR WARRANTY (ALL COMPONENTS). 2 FAN TO BE ETL/INTERTEK-CERTIFIED TO ANSI/UL 507 AND CSA 22.2. NOTES: 1 REFER TO SPECIFICATIONS FOR FURTHER INFORMATION. F02 BIG ASS FANS POWERFOIL D HUNTER, GREENHECK CIRCULATION DIRECT HVLS DOWNFLOW 6 16 108 1.5 208/3/60 7.6 250 1 THRU 5 A,B,C F01 BIG ASS FANS POWERFOIL D HUNTER, GREENHECK CIRCULATION DIRECT HVLS DOWNFLOW 6 16 108 1.5 208/3/60 7.6 250 1 THRU 5 A,B,C TYPE NUMBER OF BLADES DIAMETER (FT) MAX SPEED (RPM) MOTOR SIZE (HP) V/PH/HZ FLA (A) DRAWING CODE BASIS OF DESIGN MANUFACTURER BASIS OF DESIGN MODEL ALTERNATE APPROVED MANUFACTURERS SERVICE DRIVE FAN ELECTRICAL WEIGHT (LBS) NOTES ACCESSORIES HIGH-VOLUME, LOW-SPEED FAN SCHEDULE C INTEGRATED CONDENSATE PUMP B WIRED WALL-MOUNTED REMOTE CONTROLLER ACCESSORIES: A WALL MOUNTING BRACKET FOR OUTDOOR UNIT. REFER TO PLANS FOR ADDITIONAL INFORMATION. 5 SYSTEM MUST MEET CODE MINIMUM FOR ENERGY EFFICIENCY. 4 MECHANICAL CONTRACTOR MUST INSTALL SYSTEM REFRIGERANT PIPING PER MANUFACTURERS INSTALLATION REQUIREMENTS. 3 MOUNT INDOOR UNIT AT MAXIMUM ALLOWED HEIGHT WHILE MAINTAINING MANUFACTURERS RECOMMENDED CLEARANCES. 2 ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT AND CONDUCTOR FROM OUTDOOR UNIT TO INDOOR UNIT. NOTES: 1 REFER TO SPECIFICATIONS FOR FURTHER INFORMATION. DAH01 / DHP01 MITSUBISHI SLZ-AF18NL / SUZ-AA18NL DAIKIN, LG CEILING CASSETTE - 4 WAY HEAT PUMP 18.0 - 20.0 300-475 208/1/60 1.0 31 208/1/60 25.0 42 133 R-454B 1,2,3,4,5 A,B,C TOTAL (MBH) MIN (MBH) TOTAL (MBH) SA MIN-MAX (CFM) VOLTAGE (V/PH/HZ) MCA (A) VOLTAGE (V/PH/HZ) MCA (A) MOCP (A) FAN ELECTRICAL WEIGHT (LBS) ELECTRICAL WEIGHT (LBS) TYPE DRAWING CODE (IDU / ODU) BASIS OF DESIGN MANUFACTURER BASIS OF DESIGN MODEL (IDU / ODU) ALTERNATE APPROVED MANUFACTURERS INDOOR UNIT CONFIGURATION SYSTEM TYPE ARI COOLING 80/67/95 ARI HEATING 70/47 INDOOR UNIT OUTDOOR UNIT REFRIGERANT NOTES ACCESSORIES MINI-SPLIT SYSTEM SCHEDULE B INSULATED PLENUM BOX ACCESSORIES: A VOLUME DAMPER 3 PAINT ALL VISIBLE DUCTWORK THROUGH GRILLES AND REGISTERS FLAT BLACK. 2 DUCT BRANCH CONNECTION SIZE TO BE EQUAL TO THE NECK SIZE OF DIFFUSER UNLESS NOTED OTHERWISE ON PLANS. NOTES: 1 REFER TO SPECIFICATIONS FOR FURTHER INFORMATION. R3 PRICE 630 METALAIRE, TITUS FIXED FACE GRILLE RETURN 12 X 6 - ALUMINUM WHITE WALL SURFACE 1,2,3 - R2 PRICE LBG - 16B METALAIRE, TITUS LINEAR BAR GRILLE RETURN 24 X 4 - ALUMINUM WHITE CEILING SURFACE 1,2,3 - R1 PRICE 630 METALAIRE, TITUS FIXED FACE GRILLE RETURN 20 X 20 24 X 24 ALUMINUM WHITE T-BAR 1,2,3 B S5 PRICE LBG - 16B METALAIRE, TITUS LINEAR BAR DIFFUSER SUPPLY 24 X 4 - ALUMINUM WHITE CEILING SURFACE 1,2,3 A S4 PRICE 620 METALAIRE, TITUS LOUVER FACE DIFFUSER SUPPLY 12 X 6 - ALUMINUM WHITE CEILING/WALL SURFACE 1,2,3 A S3 PRICE ASCD METALAIRE, TITUS SQUARE CEILING DIFFUSER SUPPLY 10%%C 24 X 24 ALUMINUM WHITE T-BAR 1,2,3 A S2 PRICE ASCD METALAIRE, TITUS SQUARE CEILING DIFFUSER SUPPLY 8%%C 24 X 24 ALUMINUM WHITE T-BAR 1,2,3 A S1 PRICE ASCD METALAIRE, TITUS SQUARE CEILING DIFFUSER SUPPLY 6%%C 24 X 24 ALUMINUM WHITE T-BAR 1,2,3 A DRAWING CODE BASIS OF DESIGN MANUFACTURER BASIS OF DESIGN MODEL ALTERNATE APPROVED MANUFACTURERS TYPE SERVICE NECK SIZE (IN.) BRANCH CONN. SIZE (IN.) MODULE SIZE (IN.) MATERIAL FINISH MOUNTING NOTES ACCESSORIES DIFFUSERS, REGISTERS AND GRILLES SCHEDULE 0 11/22/24 ISSUED FOR CONSTRUCTION PLUMBING LEGEND FLOOR CLEANOUT WALL CLEANOUT HAMMER ARRESTOR CIRCUIT SETTER BALL VALVE COMBINATION 1/8 BEND DOUBLE SANITARY TEE 1/8 BEND LONG SWEEP 1/4 BEND 1/4 BEND SANITARY TEE WYE HOSE BIBB PRESSURE REGULATOR TRAP PRIMER VALVE CHECK VALVE FLOOR DRAIN FLOOR SINK 23551 E A H R D N O P TR HM.DVI A NGIN REE NH NOFO A N SEAL A L I OACR SES L I SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 P-001 PLUMBING NOTES, ABBREVIATIONS, LEGEND, SCHEDULES 2022075.00 11/22/2024 PLUMBING SUMMARY WORKSHEET FIXTURE OCCUPANCY TYPE OF CONTROL QUANTITY DOMESTIC WATER SYSTEM (W.S.F.U.)WASTE & VENT SYSTEM INDIVIDUAL FIXTURE UNITS TOTAL FIXTURE UNITS (D.F.U.) COLD HOT TOTAL COLD HOT TOTAL EACH TOTAL BATHROOM GROUP PRIVATE FLUSH TANK 1 2.7 1.5 3.6 2.7 1.5 3.6 5.0 5.0 DISHWASHING MACHINE PRIVATE AUTOMATIC 1 0.0 1.4 1.4 0.0 1.4 1.4 2.0 2.0 DRINKING FOUNTAIN OFFICES, ETC.3/8" VALVE 1 0.25 0.0 0.25 0.3 0.0 0.3 0.5 0.5 KITCHEN SINK PRIVATE FAUCET 1 1.0 1.0 1.4 1.0 1.0 1.4 2.0 2.0 LAVATORY PUBLIC FAUCET 1 1.5 1.5 2.0 1.5 1.5 2.0 1.0 1.0 SERVICE SINK OFFICES, ETC. FAUCET 2 2.25 2.25 3.00 4.5 4.5 6.0 2.0 4.0 WATER CLOSET PUBLIC FLUSH TANK 1 5.00 0.00 5.00 5.0 0.0 5.0 4.0 4.0 TOTALS 15.0 9.9 19.7 18.5 BASED ON AN ESTIMATED DEMAND OF 19.7 W.S.F.U.(19.5 GPM), PROVIDE A 1-1/4" INCOMING WATER LINE. BASED ON A WASTE COUNT OF 18.5 D.F.U., PROVIDE A 4" OUTGOING WASTE LINE. PLUMBING GENERAL NOTES: 1. SCOPE OF WORK: THESE DRAWINGS AND ACCOMPANYING SPECIFICATIONS DESCRIBE SCOPE OF WORK REQUIRED FOR PLUMBING SYSTEMS. LABOR AND MATERIAL SHALL BE PROVIDED AS REQUIRED FOR A COMPLETE, WORKMANLIKE INSTALLATION OF ALL SYSTEMS SHOWN ON DIAGRAMMATIC DRAWINGS AND/OR AS SPECIFIED HEREIN. 2. CONTRACTOR: THE WORD "CONTRACTOR", “PLUMBING CONTRACTOR”, AND "P.C." AS USED HEREIN SHALL MEAN THE PLUMBING INSTALLER UNLESS OTHERWISE QUALIFIED. 3. DRAWINGS: DRAWINGS ARE DIAGRAMMATIC AND MAY NOT COMPLETELY DESCRIBE EVERY DETAIL OF THE INSTALLATION. HOWEVER, CONTRACTOR IS RESPONSIBLE FOR FURNISHING COMPLETE SYSTEMS INCLUDING ALL REQUIRED EQUIPMENT AND ACCESSORIES TO OBTAIN FULLY FUNCTIONING PLUMBING SYSTEMS. 4. CODE COMPLIANCE: COMPLY WITH THE LATEST EDITIONS OF THE FOLLOWING STANDARDS AND CODES, INSOFAR AS THEY APPLY: NORTH CAROLINA STATE BUILDING CODE (CODE), LATEST EDITION AND REVISIONS. LOCAL JURISDICTION REQUIREMENTS. 5. PERMITS AND INSPECTIONS: OBTAIN ALL PERMITS, LICENSES, INSPECTIONS, ETC., REQUIRED FOR THE WORK AND PAY FOR SAME. FURNISH A FINAL CERTIFICATE OF INSPECTION AND APPROVAL FROM THE AUTHORITY HAVING JURISDICTION PRIOR TO ACCEPTANCE OF THE WORK. 6. SUPERVISION: PROVIDE SKILLED SUPERINTENDENTS TO SUPERVISE THE WORK FROM THE BEGINNING TO COMPLETION AND FINAL INSPECTION. 7. PROGRESS OF WORK: PERFORM WORK IN ACCORDANCE WITH SCHEDULE AND REQUIREMENTS OF THE GENERAL CONTRACTOR. UNDER NO CIRCUMSTANCES SHALL THIS CONTRACTOR DELAY THE OVERALL PROJECT SCHEDULE. 8. COORDINATION: COORDINATE PLUMBING WORK WITH THE WORK OF OTHER TRADES. LOCATIONS SHOWN ON THE DRAWINGS ARE APPROXIMATE UNLESS SPECIFICALLY DIMENSIONED. ARRANGE PLUMBING SO AS NOT TO INTERFERE WITH THE WORK OF OTHER TRADES. VERIFY ACTUAL BUILDING STRUCTURE PRIOR TO DUCT FABRICATION AND ADJUST LAYOUT AS REQUIRED. INCLUDE ALL OFFSETS IN DUCTS, FITTINGS, PIPING, ETC. AS REQUIRED TO PROPERLY INSTALL EQUIPMENT. 9. EQUIPMENT LOCATIONS: DETERMINE EXACT EQUIPMENT AND MATERIALS LOCATIONS TO PROVIDE BEST ARRANGEMENT AND TO FACILITATE PROPER MAINTENANCE AND SERVICING OF EQUIPMENT. 10. LISTING AND LABELING: ALL EQUIPMENT SHALL BE LABELED OR LISTED BY UL OR OTHER APPROVED TESTING AGENCY WHERE REQUIRED. 11. STORAGE SPACE: CONSULT WITH THE GENERAL CONTRACTOR REGARDING JOB SITE STORAGE FOR PLUMBING MATERIALS TO BE INSTALLED UNDER THIS PROJECT. STORAGE SPACE MUST BE SECURED AND CONTRACTOR'S REPRESENTATIVE MUST BE ON JOB BEFORE ANY MATERIAL MAY BE RECEIVED. 12. CLEANUP: REMOVE ALL DEBRIS GENERATED IN THE ACCOMPLISHMENT OF WORK UNDER THIS PROJECT. CLEAN, REPLACE OR REPAIR ALL SURFACES SOILED OR DAMAGED DURING THE COURSE OF THE WORK. REMOVE DEBRIS DAILY SO TO MAINTAIN SAFE WORKING CONDITIONS. 13. RECORD DRAWINGS: MAINTAIN ONE SET OF "RED-LINED" RECORD DRAWINGS ON SITE AT ALL TIMES AND PROVIDE DRAWINGS TO ARCHITECT/ENGINEER PRIOR TO FINAL INSPECTION. AIR COMPRESSOR SCHEDULE DRAWING CODE LOCATION MANUFACTURER/MODEL OR APPROVED EQUAL MODEL AIRFLOW @ 119 PSIG (ACFM) MOTOR HP POWER (V/PH/HZ)NOTES AC-01 ELEC/IT 114 INGERSOLL RAND UP6-15CTAS-125 55 15 208/3/60 1-4 NOTES:1 REFER TO SPECIFICATIONS FOR FURTHER INFORMATION. 2 PROVIDE WITH 120 GAL. RECEIVER, 3 PROVIDE WITH TOTAL AIR SYSTEM WHICH INCLUDES COOLER, DRYER, MOISTURE SEPARATORS, DRAIN PORTS AND FILTERS IN ONE COMPLETE PACKAGE 4 SET DISCHARGE PRESSURE AT 120 PSIG. GAS LOAD SCHEDULE FIXTURE TAG DESCRIPTION BTUH RATING QUANTITY TOTAL GWH1 TANKLESS WATER HEATER 199,900 1 199,900 RH01-RH04 INFARED UNIT HEATER 220,000 4 880,000 TOTAL LOAD 1,079,900 BUILDING SERVICE GAS PRESSURE 2 psi GAS-FIRED TANKLESS WATER HEATER DRAWING CODE DESCRIPTION MANUFACTURER - MODEL PIPE SIZE FLOW RATE @ 45°F RISE NAT GAS.ELECTRICAL NOTES DCW DHW (GPM) BTU/H WATTS VOLTAGE PHASE Hz.AMPS GWH1 TANKLESS NAVIEN - NPE240A2 3/4" 3/4" 8.7 199,990 200 120 1 60 2 1,2 NOTES: 1. PROVIDE WITH OUTDOOR VENT KIT. 2. PROVIDE WITH CONDENSATE NEUTRALIZATION KIT. PLUMBING ABBREVIATIONS (X) EXISTING AAV AIR ADMITTANCE VALVE A.F.F.ABOVE FINISHED FLOOR A.R.C.I. ACID RESISTANT CAST IRON ADA AMERICANS WITH DISABILITIES ACT B.F.F. BELOW FINISHED FLOOR BRZ.BRONZE BT BATHTUB C.I.CAST IRON CO CLEANOUT CONC. CONCRETE DCW DOMESTIC COLD WATER DHW DOMESTIC HOT WATER DIA.DIAMETER E.C.I.ENAMELED CAST IRON EC ELECTRICAL CONTRACTOR EWC ELECTRIC WATER COOLER EWH ELECTRIC WATER HEATER FCO FLOOR CLEANOUT FD FLOOR DRAIN FS FLOOR SINK GA. GAUGE GAL. GALLON GC GENERAL CONTRACTOR GCO GRADE CLEANOUT GPF GALLONS PER FLUSH GPH GALLONS PER HOUR GPM GALLONS PER MINUTE GWH GAS-FIRED WATER HEATER HB HOSE BIBB INCL. INCLUDED KS KITCHEN SINK LAV LAVATORY LP LIQUID PROPANE MS MOP SERVICE BASIN NAT. NATURAL GAS NKL. NICKEL NON SIMULT. NON SIMULTANEOUS O.F.L.C. OPEN FRONT LESS COVER OB OUTLET BOX OC ON CENTER ORDL OVERFLOW ROOF DRAIN LEADER PC PLUMBING CONTRACTOR PRESS. BAL. PRESSURE BALANCED RCVY. RECOVERY RDL ROOF DRAIN LEADER SA WATER HAMMER ARRESTOR SH SHOWER SK SINK SLD.SLIDE SS STAINLESS STEEL TDH TOTAL DYNAMIC HEAD TP TRAP PRIMER UR URINAL V VENT VB VACUUM BREAKER VC VITREOUS CHINA VR VANDAL RESISTANT VTR VENT THROUGH ROOF W WASTE WC WATER CLOSET WCO WALL CLEANOUT WH WALL HYDRANT NOTE: ALL ABBREVIATIONS MAY NOT BE USED IN PROJECT. PLUMBING FIXTURE SCHEDULE DRAWING CODE FIXTURE DESCRIPTION MANUFACTURER MODEL NOTES PIPE SIZE DCW DHW WASTE VENT WC1 TANK TYPE WATER CLOSET, FLOOR MTD, 1.6GPF, ADA BOWL SELECTED BY INTERIOR DESIGNER, INSTALLED BY P.C --6,9 1/2" -4" 2"SEAT LAV1 COUNTERTOP LAVATORY,0.5GPM, ADA BOWL SELECTED BY INTERIOR DESIGNER, INSTALLED BY P.C --2,4,5,9, 1/2" 1/2" 2" 2" FAUCET DRAIN MIXING VALVE LEAD FREE THERMOSTATIC MIXING VALVE - SETPOINT = 105%%DF INSTALL ON HOT WATER SUPPLY, ASSE 1070 CASH ACME HG-135 SK1 1-COMPARTMENT COUNTERTOP SINK, 10" DEEP BOWL SELECTED BY INTERIOR DESIGNER, INSTALLED BY P.C --2,4,5,9, 1/2" 1/2" 2" 2"FAUCET DRAIN MS1 MOP SINK BASIN 24"x24"x10" MOLDED STONE w/ STAINLESS STEEL DRAIN FIAT MSB-2424 1/2" 1/2" 3" 2" FAUCET BRASS CONSTRUCTION, ROUGH CHROME FINISH, INTEGRAL VACUUM BREAKER, INTEGRAL CHECK STOPS, 3/4"THREADED SPOUT, SERVICE STOPS, WALL MOUNT, VANDAL RESISTANT, LEVER HANDLES MOEN 8124 ACCESSORIES STAINLESS STEEL, THREE STATION MOP/BROOM HOLDER MOEN 8198 ACCESSORIES STAINLESS STEEL, HOSE BRACKET WITH 30" HEAVY DUTY RUBBER HOSE, GHT THREADED CONNECTION MOEN 8199 SS1 FLOOR MOUNT LAUNDRY SINK SINK SELECTED BY INTERIOR DESIGNER, INSTALLED BY P.C --9,10 1/2" 1/2" 2" 2"FAUCET SH1 PREFAB TRANSFER SHOWER, ADA ENCLOSURE SELECTED BY INTERIOR DESIGNER, INSTALLED BY P.C --1/2" 1/2" 2" 2"VALVE DRAIN EW1 EYE/FACE WASH FIXT PEDESTAL MOUNTED, STAINLESS STEEL BOWL WITH COVER, HAND AND FOOT CONTROL, THERMOSTATIC MIXING VALVE GUARDIAN G1760 1/2" 1/2" - - EWC1 WALL HUNG WATER COOLER, ADA FIXT SPLIT LEVEL, S.S. TOP, LIGHT GREY BODY, BOTTLE FILLING STATION, 8 GPH @ 50/80/90, 120V/1PH WITH FILTER ELKAY LZSTL8WSLK 1,11 1/2" - 2" 2" FCO FLOOR CLEANOUT FIXT 4"SCH. 40 HUB, PVC BASE ADAPTER, ROUND NICKEL-BRONZE COVER, VANDAL RESISTANT SCREWS SIOUX CHIEF 834-4PNRV - - MATCH - GCO GRADE CLEANOUT FIXT 4"SCH. 40 HUB, PVC BASE ADAPTER, ROUND NICKEL-BRONZE COVER, VANDAL RESISTANT SCREWS SIOUX CHIEF 851-44NV - - MATCH - WCO WALL CLEANOUT FIXT ROUND S/S ACCESS COVER & SCREW, RECESS BRONZE THRD. PLUG SIOUX CHIEF 870 - - MATCH - FD1 FLOOR DRAIN FIXT FINISHLINE ADJUSTABLE, SCH. 40 HUB CONNECTION, ABS/PVC BASE ADAPTER, SQUARE NICKEL BRONZE STRAINER SIOUX CHIEF 832 7 - - MATCH - FS1 FLOOR SINK FIXT 8x8x6 A.R.C.I. RECEPTOR, MEMBRANE CLAMP, DOME STRAINER, 1/2 GRATE SIOUX CHIEF 861 - - MATCH - HB1 INTERIOR HOSE BIBB FIXT POLISHED CHROME, VACUUM BREAKER, WHEEL HANDLE, 3/4" HOSE THREAD WOODFORD 24 1/2" - - - WH1 WALL HYDRANT FIXT CHROME PLATED BRASS, ANTI-SIPHON, VACUUM BREAKER, REMOVABLE TEE HANDLE, 3/4" HOSE THREAD WOODFORD 65 3/4" - - - OB1 ICE MAKER BOX FIXT ABS HOUSING, 1/4 TURN BALL VALVE, CHROME PLATED BRASS, SHOCK ARRESTORS SIOUX CHIEF 696 1/2" - - - OS1 OIL SEPARATOR FIXT POLYPROPELENE, 100 GPM WITH COALESCING MEDIA STRIEM OS-100 4" 2" TD1 TRENCH DRAIN FIXT 6" DUCTILE IRON FRAME, CLASS "F" LOAD CLASSIFICATION, DUCTILE IRON GRATING, 24x24x24 CATCH BASIN WATTS DEAD LEVEL 3 - - 4" - NOTES 1. PROVIDE MATCHING WALL HANGER. COORDINATE WITH G.C. FOR WALL REINFORCING. 2. PROVIDE BRASS 1-1/2" TAILPIECE, CAST BRASS SLIP JOINT P-TRAP WITH CLEANOUT; PROVIDE ADA OFFSET ARRANGEMENT WHERE REQUIRED. 3. REFER TO ARCHITECTURAL DRAWINGS FOR TOTAL LENGTH OF TRENCH. 4. COORDINATE WITH MILLWORK. 5. COORDINATE ADA MILLWORK ENCLOSURE FOR WATER AND DRAIN PIPING UNDER SINK. 6. TRIP LEVER OR FLUSH HANDLE TO BE LOCATED ON WIDE SIDE OF STALL OR TOILET ROOM. 7. PROVIDE TRAP PRIMER. NOT ALL TRAP PRIMERS WILL BE UTILIZED, SEE PLANS. 8. NOT USED. 9. PROVIDE 1/2" IPS X 3/8" OD ANGLE BRASS STOP(S) WITH RIGID COPPER RISERS. ALL EXPOSED PIPING SHALL BE CHROME PLATED. 10. PROVIDE INLINE CHECK VALVES FOR WATER SUPPLY LINES. 11. PROVIDE 1/2"IPS x 3/8" O.D. BRASS STOP CONCEALED BEHIND CABINET. 0 11/22/24 ISSUED FOR CONSTRUCTION PLAN NORTH TRUE NORTH NN P-401 1 4" W 4" FD1 4" FD1 4" W 4" W 2" V 4" W 2" V GCO 4" W 4" W 2" V 2" V 4" W 4" W 2" V 4" W 2" V 1 2 INV. EL. = (-)2.25' B.F.F INV. EL. = (-)3.75' B.F.F. INV. EL. = -3.0' B.F.F. 1 3 3 4 4 OS1 HANGAR 100 ENTRY/ LOBBY 101 CONFERENCE 106 PARTS STORAGE 116 ELEC/ IT 114 OPEN OFFICE 103 RISER 115 OFFICE 105 CORR 102 FCO FCO INV. EL. = (-)3.5' B.F.F. INV. EL. = (-)2.42' B.F.F. INV. EL. = (-)2.46' B.F.F. TD1TD1 TD1 TD1 4" W4" WGCO GCO GCO 2"VTR 23551 E A H R D N O P TR HM.DVI A NGIN REE NH NOFO A N SEAL A L I OACR SES L I SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 PS101 FIRST LEVEL WASTE-VENT PLAN 2022075.00 11/22/2024 8'16'4'01/8" = 1'-0"1 PLUMBING FIRST LEVEL WASTE-VENT PLAN KEYNOTES THIS SHEET 1 TO SANITARY SEWER. REFER TO SITE UTILITY PLAN FOR CONTINUATION 2 1/2" FROM TRAP PRIMER TO TRAP PRIMER CONNECTION ON DRAIN. 3 VENT TO BE ROUTED UNDERSLAB IN ACCORDANCE WITH SECTION 905.4 OF THE 2018 NCPC 4 PC MUST INSTALL WALL CLEANOUT IN VENT LINE IN ACCORDANCE WITH SECTION 904.5 OF THE 2018 NCPC # 0 11/22/24 ISSUED FOR CONSTRUCTION PLAN NORTH TRUE NORTH NN 1 WH1 P-401 2 1 1/4" CW 1 1 / 4 " C W 3/ 4 " C W HB1 WH1 3/ 4 " C W 2 3 3 HB1 4 SHUTOFF VALVE ABOVE CEILING 23551 E A H R D N O P TR HM.DVI A NGIN REE NH NOFO A N SEAL A L I OACR SES L I SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 PW101 FIRST LEVEL DOMESTIC WATER PLAN 2022075.00 11/22/2024 KEYNOTES THIS SHEET 1 INSTALL MAIN SHUTOFF VALVE INSIDE OF WALL MOUNTED VALVE ACCESS BOX. 2 1-1/4" DCW SERVICE. SEE SITE UTILITY PLAN FOR CONTINUATION 3 PIPING ROUTED ABOVE CEILING 4 INSTALL PRESSURE TYPE TRAP PRIMER WITH DISTRIBUTION HUB. CONNECT TO FLOOR DRAIN TRAP PRIMER CONNECTIONS IN RISER ROOM AND AT AIR COMPRESSOR 0'4'2'4' SCALE : 1/4" = 1'-0"1/8" = 1'-0"1 FIRST LEVEL DOMESTIC WATER PLAN # 0 11/22/24 ISSUED FOR CONSTRUCTION 3/4" NG 3/ 4 " N G 3/ 4 " C A 3/ 4 " N G 3/ 4 " C A 3/4" NG 3/4" NG 3/4" CA3/4" CA 3/4" NG 3/4" CA3/4" CA 3/4" CA 3/4" NG 3/ 4 " N G 3/ 4 " C A 3/4" CA 1 1/4" NG 3/ 4 " N G 3/ 4 " N G 3/ 4 " C A 3/4" NG 3/ 4 " C A 3/ 4 " N G 3/4" NG COMPRESSED AIR OUTLET STATION COMPRESSED AIR OUTLET STATION COORDINATE ARRANGEMENT WITH OWNER, TYPICAL. COMPRESSED AIR OUTLET STATION RH01 RH03 RH02 RH04 AC-01 220MBH 220MBH 220MBH 220MBH 3/4" CA COMPRESSED AIR OUTLET STATION GWH1 COORDINATE EXPOSED PIPE ROUTING AND HEIGHTS WITH GENERAL CONTRACTOR COORDINATE EXPOSED PIPE ROUTING AND HEIGHTS WITH GENERAL CONTRACTOR NAT. GAS SEVICE BY GAS UTILITY NATURAL GAS SERVICE METER BY GAS UTILITY 199MBH 23551 E A H R D N O P TR HM.DVI A NGIN REE NH NOFO A N SEAL A L I OACR SES L I SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 PG101 FIRST LEVEL NAT. GAS AND COMPRESSED AIR PIPING PLAN 2022075.00 11/22/2024 1/8" = 1'-0"1 FIRST LEVEL NAT. GAS AND COMPRESSED AIR PIPING PLAN 0 11/22/24 ISSUED FOR CONSTRUCTION PLAN NORTH TRUE NORTH NN WC1 2" FD1 LAV1 WC1 LAV1 2" FD1 2" FD1 EWC1 2" FS1 SS1MS1 SK1 EW1 4" W 3" W 3" W 2" W 2" V4" W4" W SH1 2" W 4" W2" W2" W 2" V 2" V 2" W 2" W 2" W 2" W 2" V 2" W 3" W 2" V 3" W 2" V 2" V2" V 2" V 2"VTR 2" W 2" W ICE MAKER BY OTHERS EWC1 MS1 WC1 WC1 LAV1 LAV1 OB1 SS1 EW1 OB1 SK1 GWH1 3/4" HW 3/4" CW 1 1 / 4 " C W 3/ 4 " H W 1" C W 3/ 4 " H W 1" C W 1/ 2 " H W 1/ 2 " C W 1/2" CW 1/2" HW 1/2" CW 1/2" HW 1/ 2 " C W 1/2" CW 1/2" HW 1/2" HW 1/2" CW 3/ 4 " H W 1" C W 1/ 2 " C W 1/ 2 " H W 1/2" HW 3/4" CW1/2" CW 1/ 2 " C W 3/4" CW 3/4" HW 1/2" CW 1/2" CW 1/2" CW 1/2" HW 1/2" CW 1/ 2 " H W 1/ 2 " C W 1" C W 3/ 4 " C W 1/2" HW 1/2" CW HB1 HB1 ICE MAKER BY OTHERS SH1 23551 E A H R D N O P TR HM.DVI A NGIN REE NH NOFO A N SEAL A L I OACR SES L I SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 P-401 ENLARGED PLUMBING PLANS 2022075.00 11/22/2024 0'4'2'4' SCALE : 1/4" = 1'-0" 1/4" = 1'-0"1 ENLARGED WASTE-VENT PLAN 1/4" = 1'-0"2 ENLARGED DOMESTIC WATER PLAN 0 11/22/24 ISSUED FOR CONSTRUCTION NOTE: CLEANOUT TO BE FLUSH WITH FINISHED WALL. FLOOR CLEANOUT (FCO) WALL CLEANOUT (WCO) GRADE CLEANOUT (GCO) CLEANOUT AND ACCESS COVER. TOP OF COVER TO BE FLUSH WITH TOP OF FLOOR FLOOR LINE WASTE LINE BALANCE OF PIPING SAME AS CLEANOUT TO GRADE 1/8 BEND 16"SQUARE CONCRETE PAD TROWEL SMOOTH AND EDGE FINISH GRADE BRASS CLEANOUT PLUG WITH COUNTERSUNK HEAD WASTE LINE CHROME WALL COVER AND SCREW MAY EXTEND AS A DRAIN OR WASTE LINE WALL PLUGGED TEE WITH CLEANOUT PIPE NOTE: CLEANOUT TO BE FLUSH WITH FINISHED WALL. BALANCE OF PIPING SAME AS CLEANOUT TO GRADE RATED ACCESS COVER MAY EXTEND AS A DRAIN OR WASTE LINE WALL PLUGGED TEE WITH CLEANOUT PIPE WALL CLEANOUT (WCO) RATED WALL 1/8 BEND IF CLEANOUT OCCURS AT END OF LINE. 1/8 BEND IF CLEANOUT OCCURS AT END OF LINE. MAIN STAND OFF PIPE CLAMP SHUT OFF VALVE ARO QUICK CONNECT COUPLER FULL SIZE DRIP TRAP AND BLOW DOWN VALVE48 " U . N . O . 12 " M I N . M ~ SPRAY HEADS STAINLESS STEEL FLAG HANDLE STAINLESS STEEL FLOOR FLANGE (SEE DETAIL "A") DETAIL "A" FLOOR FLANGE 6-1/2"∅ STAINLESS STEEL BOWL 1/2" NPT FEMAL INLET 1/2" IPS STAINLESS STEEL STAY-OPEN BALL VALVE STAINLESS STEEL PIPE AND FITTINGS 1-1/4" NPT FEMALE OUTLET TEE CLOSED ONE END FLOOR (3) 7/16" MOUNTING HOLES ON 5-1/4" BOLT CIRCLE FRONT VIEW SIDE VIEW ASSE 1071 THERMOSTATIC MIXING VALVE COLD WATER SUPPLYHOT WATER SUPPLY TEPID WATER SUPPLY PIPE SUPPORT TYPICAL PIPE SUPPORT TYPICAL PIPE SUPPORT TYPICAL ~~ FINISHED FLOOR DRAIN PIPE FROM EQUIPMENT OR FIXTURE DOME STRAINER 2-INCH AIR GAP, MIN. BRANCH P-TRAP ~ AGA APPROVED GAS VALVE PRESSURE REGULATOR PRESSURE PORT GAS PIPING DIRT LEG AGA APPROVED GAS VALVE AGA APPROVED FLEXIBLE CONNECTOR GAS APPLIANCE 4232 NOTE: SEE NATURAL GAS USAGE SCHEDULE FOR QUANTITY USED BY FACILITY GAS COMPANY TO CONNECT TO PLUG VALVE LOCKOUT TYPE PLUG VALVE SUPPLY TO GAS APPLIANCES SWING JOINT BY CONTRACTOR GAS METER BY GAS COMPANY FINISHED GRADE ANODELESS RISER BY GAS COMPANYPOLYETHYLENE PIPING BY GAS COMPANY MAGNETIC WARNING AND IDENTIFICATION TAPE BY GAS COMPANY PLUG VALVE BY GAS COMPANY PLUGGED TEE W/ BUSHING AND 3/8" PLUG BY GAS COMPANY INSULATING UNION BY GAS COMPANY GAS PRESSURE REGULATOR BY GAS COMPANY TEE W/ BUSHING AND 3/8" PLUG BY GAS COMPANY DOMESTIC HOT WATER CONDENSATE DOMESTIC COLD WATER GAS NOTE: BASIS OF DESIGN MANUFACTURERS RECOMMENDED PIPING LAYOUT. OTHER MANUFACTURES MAY VARY. INSTALL PER MANUFACTURERS PIPING RECOMMENDATIONS H CG 1/2" TRAP PRIMER SUPPLY DOMESTIC WATER LINE TRAP PRIMER VALVE DISTRIBUTION UNIT, FOR UP TO 5 LINES AS REQUIRED 1/2" TRAP PRIMER LINE FLOOR DRAIN FLOOR SLAB SLEEVE THRU SLAB SHUTOFF VALVE 23551 E A H R D N O P TR HM.DVI A NGIN REE NH NOFO A N SEAL A L I OACR SES L I SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 P-501 PLUMBING DETAILS 2022075.00 11/22/2024 NO SCALE1CLEANOUT DETAILS NO SCALE2COMPRESSED AIR DROP NO SCALE3EYEWASH DETAIL NO SCALE4FLOOR SINK DETAIL NO SCALE5GAS APPLIANCE CONNECTION DETAIL NO SCALE6GAS SERVICE DETAIL NO SCALE7ELECTRIC WATER HEATER DETAIL NO SCALE8TRAP PRIMER DETAIL 0 11/22/24 ISSUED FOR CONSTRUCTION 2" FS1 2" W 2" W 2" W 2" W 2" W 2" FD1 LAV1 EWC1 2" W 3" W 3" W SS1 2" V 4" W 2" W SK1 2" V 2" V 2" V 2" V 2" V 2" V 2" V 4" W 2" FD1 2" W 3" W MS1 2" V 2" V 3" W WC1 4" W 2" W 2" W 2" FD1 WC1 4" W 4" W LAV1 SH1 2" V 2" V 2" V 2"VTR 4" W 4" W 1/2" TP 4" FD1 4" FD1 1/2" TP 2" V 2"VTR 4" W GCO 4" W 4" W 1/2" TP WCOWCO WCO WCO WCO WH1 HB1 3/ 4 " C W 1/ 2 " C W 3/4" CW OB1 LAV1 HB1 WC1 HB1 WC1 SH1 SS1 EW1 OB1 SK1MS1 GWH1 HB1 WH1 3/ 4 " C W 3/4" CW 1/2" CW 1 1 / 4 " C W 1 1/4" CW 1 1/4" CW 1 1/4" CW 1" CW 3/4" HW 3/4" CW 3/ 4 " H W 3/ 4 " C W 1/ 2 " H W 1/ 2 " C W 1/ 2 " H W 1/ 2 " C W 1/ 2 " H W 1/ 2 " C W 1/ 2 " H W 1/ 2 " C W 1" CW 3/4" HW 1/ 2 " C W 3/4" CW3/4" HW 1/ 2 " C W 1/ 2 " C W 1/ 2 " H W 1/ 2 " H W 1/ 2 " C W 1/2" CW 1/2" CW 1/2" HW 1/ 2 " C W 1/ 2 " H W 1/ 2 " C W 1/2" CW 1/2" HW 1/2" HW 1" CW 3/4" CW EWC1 LAV1 1/ 2 " C W 1/ 2 " H W 1/2" HW 1/2" CW 1/2" HW 1/2" CW MAIN SHUTOFF VALVE TRAP PRIMER FCO 4" W 4" W 2" V 2" V GCO 4" W 4" W 4" W 4" W 2" V FCO 24x24x24 CATCH BASIN 24x24x24 CATCH BASIN GCO GCO 4" W OS1 WCO WCO 2"VTR 2"VTR 23551 E A H R D N O P TR HM.DVI A NGIN REE NH NOFO A N SEAL A L I OACR SES L I SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 P-502 PLUMBING RISER DIAGRAMS 2022075.00 11/22/2024 1 WASTE-VENT RISER DIAGRAM 3 DOMESTIC WATER RISER DIAGRAM 2 HANGER BAY WASTE-VENT RISER DIAGRAM 0 11/22/24 ISSUED FOR CONSTRUCTION 23551 E A H R D N O P TR HM.DVI A NGIN REE NH NOFO A N SEAL A L I OACR SES L I SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1740 Airport Boulevard Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 P-503 PLUMBING U.L. DETAILS 2022075.00 11/22/2024 0 11/22/24 ISSUED FOR CONSTRUCTION MB ASPH PARK FLIGHTLINE ROAD CO WV WV FO WV WV WV T D D D D D D D D D PP JJ 2EP1-35 PIV E-100 2 PLAN NORTH TRUE NORTH NN PUSHPLATE AND LOW VOLTAGE CABLE PROVIDED AND INSTALLED BY SECURITY CONTRACTOR 3"DIA x 60" HIGH BOLLARD. BOLLARD MUST EXTEND MIN 36"ABOVE GRADE. PROVIDE SURFACE MOUNTED 2 GANG WEATHERPROOF BOX FOR GATE PUSH TO EXIT, BOLLARD AND WEATHERPROOF BOX PROVIDED BY ELECTRICAL CONTRACTOR 1 1/4"CND UNDERGROUND WITH NYLON PULL STRING DATA: PROVIDE 1 1/4"CND FROM ABOVE LAY-IN CEILING IN CONF RM [106] TO BELOW GRADE AND STUB UP 4" ABOVE GRADE AT GATE GATE POWER, 2 GANG WEATHERPROOF PROVIDED AND MOUNTED BY ELECTRICAL CONTRACTOR (TYP 2) GATE POWER 2EP2-35 GATE FENCE 2EP2-39 NOTE: ELECTRICAL CONTRACTOR MUST COORDINATE FINAL STUB-UP LOCATIONS OF POWER AND DATA CONDUITS, JUNCTION BOXES AND BOLLARD LOCATION WITH GENERAL CONTRACTOR AND OWNERS SECURITY CONTRACTOR PRIOR TO ROUGH-IN AND INSTALLATION. 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1820 FLightline Road Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 E-100 ELECTRICAL SITE PLAN 2022075.00 11/22/2024 3/32" = 1'-0"1 ELECTRICAL SITE PLAN GENERAL NOTES 1 ELECTRICAL CONTRACTOR MUST COORDINATE ALL INDERGROUND UTILITIES PRIOR TO TRENCHING FOR UNDERGROUND ELECTRICAL AND LOW VOLTAGE CONDUITS. 1 EXISTING UTILITY POLE (480V) 480V UNDERGROUND ELECTRICAL PROVIDED BY UTLILTY 480V ABOVE GROUND JUNCTION BOX PROVIDED BY UTLITY CT CABINET AND METER, SEE RISER DIAGRAM ON E-601 HOT BOX POWER D.S. 30A/1/3R, W/ 20AF PANEL 2EP2 PANEL 2EP1 PANEL 4EP1 FACP PROVIDE (2) 2"CND'S UNDERGROUND TO PROPERTY LINE, COORDINATE FINAL LOCATION WITH TELECOM UTILITY BFP TAMPER SW AND PIV SCALE : 3/32" = 1'-0" 0'10'10'5' TELECOM CABINET 1/4" = 1'-0"2 GATE POWER AND DATA PLAN 1 1 0 11/22/24 ISSUED FOR CONSTRUCITON 1 2025.01.31 GFO HANGAR PERMIT SET 01/31/2025 LOAD SUMMARY VOLTAGE PHASE 480 3 1.732 LARGEST MOTOR APPROX. AMPS 91 AMPS LARGEST MOTOR APPROX. AMPS x .25 23 AMPS HVAC AH01 13,258 VA HP01 5,824 VA SFO'S (QTY 2)2,784 VA EF'S (QTY 4)3,030 VA RH'S (QTY 4)480 VA FO'S (QTY 2)4,381 VA DAH01 & DHP01 4,326 VA EUH01 750 VA SUB-TOTAL HVAC DEMAND 34,834 VA SUB-TOTAL HVAC DEMAND 42 AMPS EQUIPMENT HYDRAULIC DOORS (QTY 2)56,536 VA GWH1 200 VA AC-01 7,566 VA AC POWER CART 42,402 VA AIRCRAFT PORTABLE AC UNIT 4,014 VA TUG CHARGER 64,018 VA HYD POWER UNIT 75,658 VA FRENCH DR REFRIG 1,800 VA DISHWASHER 792 VA MICROWAVE 1,668 VA ICE MAKER 792 VA GATE POWER 360 VA COMMERCIAL DRINK REFRIG 1,200 VA SUB-TOTAL EQUIPMENT DEMAND 257,006 VA SUB-TOTAL EQUIPMENT DEMAND 309 AMPS ADD FOR LARGEST MOTOR 23 AMPS TOTAL EQUIPMENT DEMAND 332 AMPS LIGHTING LIGHTS (INTERIOR, BASED ON NEC 220.12)17,084 VA LIGHTS (EXTERIOR)1,761 VA SIGN (QTY 4)3,000 VA TOTAL LIGHTING LOAD 21,845 VA TOTAL DEMAND FOR LIGHTING 26 AMPS RECEPTACLES RECEPTACLES 19,984 VA FIRST 10000VA 10,000 VA REMAINDER @ 50%4,992 VA TOTAL DEMAND FOR RECEPTACLE/POWER PANELS 14,992 VA TOTAL DEMAND FOR RECEPTACLE/POWER PANELS 18 AMPS TOTAL DEMAND BUILDING AMPS 418 AMPS TOTAL DEMAND BUILDING VA 347,590 VA TOTAL BUILDING CONNECTED LOAD 333,669 VA AT PNL 4EP1: 52,032 AMPS AT PNL 2EP1: 5,828 AMPS AT PNL 2EP2: 5,775 AMPS NOTE: 1. SHORT CIRCUIT CALCULATION COMPLETED ON 11/26/2024. BASED ON A 300KVA POLE MOUNTED TRANSFORMER BANK @ 1.7% IMPEDANCE, AND 2.37 X/R. VERIFY ACTUAL PARAMETERS WITH UTILITY COMPANY AND EQUIPMENT CHARACTERISTICS PRIOR TO INSTALLATION. 2. SERVICE EQUIPMENT SHALL BE LEGIBLY MARKED WITH MAX. AVAILABLE FAULT CURRENT, INCLUDING THE DATE THE FAULT CURRENT CALCULATIONS WERE PERFORMED, PER NEC 110.24 AVAILABLE FAULT CURRENT GROUND PER NEC 250 DETAIL #2/0 BARE CU (2) 3" CONDUITS EACH CONTAINING 4-350kcmil CONDUCTORS SURGE PROTECTION DEVICE (SPD) SHALL BE MOUNTED TO KEEP LEADS AS SHORT AS POSSIBLE. SPD's ARE SHOWN WITH A 30A, 3 POLE BREAKER IN PANELBOARD BEING PROTECTED, MAKE CONNECTION WITH 4#10AWG CONDUCTORS, IF SPD MANUFACTURER RECOMMENDS LARGER BREAKER OR LEADS, PROVIDE AT NO ADDITIONAL COST TO OWNER. ELECTRICAL [110] SPD EGB PANEL "4EP1" 600A 480/277V, 3∅, 4W SERVICE EQUIPMENT LISTED 3#2/0 & 1#6GND- 2"CND E-501 10 E-501 9 "2EP1" 200A 208/120V, 3∅, 4W #2 BARE CU 4#3/0 & 1#6GND- 2"CND "T-2EP1 112.5KVA, 480-208/120V, 3ɸ, 4W GROUND PER NEC 250, SEE DETAIL 3/E-502 E-501 1TYP. 'NAME' 'WARNING' 'WORKING SPACE 'NAME' 'WARNING' 'WORKING SPACE E-501 6 'NAME''WARNING' E-501 3 SPD "2EP2" 200A 208/120V, 3∅, 4W 'NAME' 'WARNING' 'WORKING SPACE SPD NOTE (SURGE PROTECTION DEVICE) CT CABINET GRADE METERBASE AND METER 480V ABOVE GROUND JUNCTION BOX PROVIDED BY UTILITY, EC MUST COORDINATE LOCATION WITH UTILITY PRIOR TO TRENCHING AND INSTALLATION FOR SERVICE CONDUIT AND CONDUCTORS 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1820 FLightline Road Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 E-601 ELECTRICAL RISER DIAGRAM AND SCHEDULES 2022075.00 11/22/2024 Notes: Lighting 8420 VA 100.00% 8420 VA Total Est. Demand:76.6 A RCPT 21244 VA 73.54% 15622 VA Total Conn.:83.3 A Power 560 VA 100.00% 560 VA Total Est. Demand:63665 VA Other 3558 VA 100.00% 3558 VA Total Conn. Load:69287 VA HVAC 35515 VA 100.00% 35515 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Legend: Total Amps:422.4 A 394.7 A 396.8 A Total Load:116939 VA 109345 VA 109828 VA 41 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 42 39 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 40 37 LTS: EXTERIOR OVER BAY DOOR 20.0 A 1 915 VA 0 VA 1 20.0 A SPARE 38 35 14133 VA 0 VA 1 20.0 A SPARE 36 33 14133 VA 0 VA 1 20.0 A SPARE 34 31 AC PCU D.S.70.0 A 3 14133 VA 696 VA 1 20.0 A LTS: PERIMETER EXTERIOR 32 29 21615 VA 100 VA 1 20.0 A LTS: CANOPY AT MAIN ENTRY 30 27 21615 VA 2700 VA 1 20.0 A LTS: HANGAR 28 25 TUG CHARGER D.S.100.0 A 3 21615 VA 2700 VA 1 20.0 A LTS: HANGAR 26 23 0 VA 25495 VA 24 21 0 VA 25495 VA 22 19 AC PCU D.S.70.0 A 3 0 VA 25495 VA 3 125.0 A HYD POWER UNIT D.S. 20 17 9423 VA 0 VA 18 15 9423 VA 0 VA 16 13 HYDRAULIC DOOR #1 D.S.,60.0 A 3 9423 VA 0 VA 3 70.0 A AC PCU D.S. 14 11 29644 VA 9423 VA 12 9 26557 VA 9423 VA 10 7 XFMR T-2EP1 (PANEL 2EP1 & 2EP2)175.0 A 3 32541 VA 9423 VA 3 60.0 A HYDRAULIC DOOR #2 D.S., 8 5 0 VA 0 VA 6 3 0 VA 0 VA 4 1 SPD 30.0 A 3 0 VA 0 VA 3 70.0 A AC PCU D.S. 2 CKT Circuit Description Trip Pol es A B C Pol es Trip Circuit Description CKT Notes: Enclosure:NEMA 1 MCB Rating:600.0 A Mounting:SURFACE Wires:4 Mains Rating:600.0 A Supply From: Phases:3 Mains Type:MAIN CB Location:ELEC/ IT 114 Volts:480Y/277 A.I.C. Rating:65,000 AMPS SYMMETRICAL Branch Panel: 4EP1 1. PROVIDE GFCI BREAKER. Notes: Total Est. Demand:110.5 A RCPT 16012 VA 81.23% 13006 VA Total Conn.:118.8 A Power 560 VA 100.00% 560 VA Total Est. Demand:39807 VA Other 3000 VA 100.00% 3000 VA Total Conn. Load:42813 VA HVAC 23241 VA 100.00% 23241 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Legend: Total Amps:174.1 A 166.2 A 172.6 A Total Load:20787 VA 19945 VA 20613 VA 53 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 54 51 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 52 49 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 50 47 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 48 45 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 46 43 BLDG SIGNS 20.0 A 1 1200 VA 0 VA 1 20.0 A SPARE 44 41 SPARE 20.0 A 1 0 VA 2080 VA 42 39 BLDG SIGN 20.0 A 1 600 VA 2080 VA 2 35.0 A DHP01 D.S.40 37 SIGN 20.0 A 1 1200 VA 4419 VA 38 35 HOT BOX POWER 20.0 A 1 1500 VA 4419 VA 36 33 2912 VA 4419 VA 3 50.0 A AH01 D.S. 34 31 HP01 D.S.60.0 A 2 2912 VA 400 VA 1 20.0 A FACP ELECT/IT [114]32 29 GWH1 D.S.20.0 A 1 200 VA 720 VA 1 20.0 A RCPTS/FLR BOX: CONF [106]30 27 RCPT: FIRST RESPONDERS CABINET ELECT/IT [114]20.0 A 1 180 VA 900 VA 1 20.0 A RCPTS: CONF [106]28 25 RCPT: FIRST RESPONDERS CABINET ELECT/IT [114]20.0 A 1 180 VA 1080 VA 1 20.0 A RCPTS: OFFICE [105]26 23 RCPTS: EXTERIOR MAIN ENTRY 20.0 A 1 360 VA 720 VA 1 20.0 A RCPTS: OPEN OFFICE [103]24 21 RCPT: EWC (NOTE 1)20.0 A 1 430 VA 900 VA 1 20.0 A RCPTS: OPEN OFF [103]22 19 RCPT: DISHWASHER BREAK [111] (NOTE 1)20.0 A 1 792 VA 1080 VA 1 20.0 A RCPTS: ENTRY/LOBBY [101] & OPEN OFF [103]20 17 RCPT: MICROWAVE BREAK [111]20.0 A 1 1650 VA 900 VA 1 20.0 A RCPTS: ENTRY/LOBBY [101]18 15 RCPT: BREAK [111]20.0 A 1 360 VA 360 VA 1 20.0 A RCPTS: RESTROOMS [107] & [108]16 13 RCPT: COFFEE BREAK [111]20.0 A 1 180 VA 720 VA 1 20.0 A RCPTS: JAN [109], CORRIDORS [102] & [110]14 11 RCPT: RFRIG BREAK [111]20.0 A 1 1800 VA 5544 VA 12 9 RCPTS: BREAK [111]20.0 A 1 540 VA 5544 VA 10 7 RCPTS: PARTS STORAGE [116]20.0 A 1 720 VA 5544 VA 3 70.0 A AC-01 D.S. 8 5 RCPTS: PARTS STORAGE [116]20.0 A 1 720 VA 0 VA 6 3 RCPTS: TELE BACKBOARD ELECT/IT [114]20.0 A 1 720 VA 0 VA 4 1 RCPTS: ELECT/IT [114]20.0 A 1 360 VA 0 VA 3 30.0 A SPD 2 CKT Circuit Description Trip Pol es A B C Pol es Trip Circuit Description CKT Notes: Enclosure:NEMA 1 MCB Rating:200.0 A Mounting: Wires:4 Mains Rating:200.0 A Supply From:T-2EP1 Phases:3 Mains Type:MAIN CB Location:ELEC/ IT 114 Volts:208Y/120 A.I.C. Rating:10,000 AMPS SYMMETRICAL Branch Panel: 2EP1 1. PROVIDE GFCI BREAKER. Notes: Total Est. Demand:53.8 A Lighting 1367 VA 100.00% 1367 VA Total Conn.:53.8 A RCPT 5232 VA 100.00% 5232 VA Total Est. Demand:19371 VA Other 558 VA 100.00% 558 VA Total Conn. Load:19371 VA HVAC 12274 VA 100.00% 12274 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals Legend: Total Amps:101.1 A 55.1 A 78.4 A Total Load:11757 VA 6612 VA 9031 VA 41 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 42 39 GATE POWER 20.0 A 1 180 VA 0 VA 1 20.0 A SPARE 40 37 SPARE 20.0 A 1 0 VA 0 VA 1 20.0 A SPARE 38 35 GATE POWER 20.0 A 1 180 VA 0 VA 1 20.0 A SPARE 36 33 913 VA 636 VA 1 20.0 A LTS: OFFICE AREA 34 31 913 VA 942 VA 1 20.0 A LTS: OFFICE AREA 32 29 F02 15.0 A 3 913 VA 1392 VA 1 20.0 A EF02 D.S.30 27 913 VA 0 VA 1 20.0 A SPARE 28 25 913 VA 1392 VA 1 20.0 A EF01 D.S.26 23 F01 15.0 A 3 913 VA 0 VA 1 20.0 A SPARE 24 21 SPACE -- 1 -- 1392 VA 1 20.0 A SF01 D.S.22 19 4014 VA 750 VA 1 20.0 A EUH01 D.S.20 17 PORTABLE AC UNIT D.S.60.0 A 2 4014 VA -- 1 --SPACE 18 15 RH01, RH01, RH03, RH04 20.0 A 1 480 VA 0 VA 16 13 SF02 D.S.20.0 A 1 1392 VA 0 VA 2 60.0 A PORTABLE AC UNIT D.S. EXTERIOR 14 11 SPACE -- 1 -- 720 VA 1 20.0 A RCPTS: EAST WALL HANGAR [101] & EXT.12 9 0 VA 1200 VA 1 20.0 A RCPT: REFRIGERATED CABINET AGR 1002 HANGAR...10 7 PORTABLE AC UNIT D.S.60.0 A 2 0 VA 792 VA 1 20.0 A RCPT: ICE MAKER 8985 HANGAR [100]8 5 RCPTS: NORTH AND EAST WALLS HANGAR [100] & EXT.20.0 A 1 900 VA 0 VA 6 3 RCPTS: WEST AND NORTH WALL HANGAR [100] & EXT.20.0 A 1 900 VA 0 VA 4 1 RCPTS: WEST WALL HANGAR [100] & EXT.20.0 A 1 720 VA 0 VA 3 30.0 A SPD 2 CKT Circuit Description Trip Pol es A B C Pol es Trip Circuit Description CKT Notes: Enclosure:NEMA 1 MCB Rating:200.0 A Mounting: Wires:4 Mains Rating:200.0 A Supply From:T-2EP1 Phases:3 Mains Type:MAIN CB Location:ELEC/ IT 114 Volts:208Y/120 A.I.C. Rating:10,000 AMPS SYMMETRICAL Branch Panel: 2EP2 NO SCALE1RISER DIAGRAM 1 1 1 1 0 11/22/24 ISSUED FOR CONSTRUCITON 1 2025.01.31 GFO HANGAR PERMIT SET 01/31/2025 OD O OS OS OS OS OD OF OS OF O D OD OD DD OD 3 3 ODOD D D PE PE T D D OF OS OS PE PE PE 1 6 3 4 5 2 1.1 5.9 GF.9ABB.1 DC E F HANGAR 100 ENTRY/ LOBBY 101 CONFERENCE 106 PARTS STORAGE 116 ELEC/ IT 114 OPEN OFFICE 103 RISER 115 OFFICE 105 CORR 110 RESTROOM 107 RESTROOM 108 JAN 109 BREAK 111 CLOSET 112 CORR 102 A BB B C CE C C C C C C C C B B B BB B B B B B A A A A A A A A A A A AA A A A A B A A A D D D D D D D H H H H H H H H H H H H H H H H B B EF04 EF03 2EP14EP1 2EP2 FACP 4EP1-26 4EP1-28 2EP2-32 F 2EP2-34 K K K K K 4EP1-37 4EP1-32 L L L L L L L L L L L L MOUNT PHOTOCELL #1 AS HIGH ON WALL AND BELOW EAVE AS POSSIBLE VIA PE #1 4EP1-30 MOUNT PHOTOCELL #2 AS HIGH ON WALL AND BELOW EAVE AS POSSIBLE VIA PE #2 X1 X2G X3 X3 X3 X3 E E E E E MOUNT FIXTURE ABOVE FIRE DOOR (~11'-0"AFF) E E E E E E E E E E E E E E E E E E J J J J J J J J J M MM M P P EF05 D TYPE D FIXTURE AND SWITCH MOUNTED IN ATTIC TYPE P FIXTURE MOUNTED ON ROOF, SEE ARCHITECTURAL PLAN/DETAILS FOR MOUNTING TYPE P FIXTURE MOUNTED ON ROOF, SEE ARCHITECTURAL PLAN/DETAILS FOR MOUNTING E D X1 X1 MOUNT PHOTOCELL #3 AS HIGH ON WALL AND BELOW CANOPY AS POSSIBLE VIA PE #3 MOUNT PHOTOCELL #3 AS HIGH ON WALL AND BELOW EAVE AS POSSIBLE MOUNT PHOTOCELL #4 AS HIGH ON WALL AND BELOW EAVE AS POSSIBLE PLAN NORTH TRUE NORTH NN 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1820 FLightline Road Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 EL101 ELECTRICAL FLOOR PLAN - LIGHTING 2022075.00 11/22/2024 1/8" = 1'-0"1 FLOOR PLAN - LIGHTING 0'8'4'8' SCALE : 1/8" = 1'-0" 1 0 11/22/24 ISSUED FOR CONSTRUCITON 1 2025.01.31 GFO HANGAR PERMIT SET 01/31/2025 CR CR CR CR CR J J J PP PLAN NORTH TRUE NORTH NN 1 6 3 4 5 2 1.1 5.9 GF.9ABB.1 DC E F HANGAR 100 ENTRY/ LOBBY 101 CONFERENCE 106 PARTS STORAGE 116 ELEC/ IT 114 OPEN OFFICE 103 RISER 115 OFFICE 105 CORR 110 RESTROOM 107 RESTROOM 108 JAN 109 BREAK 111 CLOSET 112 CORR 102 HYDRAULIC DOOR #2 D.S. 60A/3/1, W/ 60AF HYDRAULIC DOOR #1 D.S. 60A/3/1, W/ 60AF 4EP1 T-2EP1 2EP1 EP401 1 EP401 2 WP WP WP WP WP HYD POWER UNIT (480V, 125A PIN & SLEEVE) AC PCU (480V, 100A PIN & SLEEVE) TUG CHARGER D.S. (480V, 100A PIN & SLEEVE) PORTABLE AC UNIT (208V, 60A PIN & SLEEVE) AC PCU (480V, 100A PIN & SLEEVE) PORTABLE AC UNIT (208V, 100A PIN & SLEEVE) AC PCU (480V, 100A PIN & SLEEVE) PORTABLE AC UNIT (60A PIN & SLEEVE) AC PCU (100A PIN & SLEEVE) 2EP2-1 2EP2 REFRIGERATED CABINET AGR 1002 ICE MAKER 8985 2EP2-8 2EP2-10 2EP2-3 WP 2EP1-23 2EP2-5 2EP2-12 4EP1-2,4,6 2EP2-7,9 3#4 & 1#8GND- 1"CND 2#6 & 1#8GND- 3/4"CND 4EP1-13,15,17 3#6 & 1#8GND- 1"CND 4EP1-8,10,12 3#6 & 1#8GND- 1"CND 2#6 & 1#8GND- 3/4"CND 2EP2-14,16 3#4 & 1#8GND- 1"CND 4EP1-19,21,23 2EP2-17,19 2#6 & 1#8GND- 3/4"CND 4EP1-14,16,18 3#4 & 1#8GND- 1"CND 4EP1-25,27,29 3#3 & 1#8GND- 1 1/4"CND 4EP1-20,22,24 4EP1-31,33,35 FIRST RESPONDERS CABINET 3#4 & 1#8GND- 1"CND 3#1 & 1#6GND- 1 1/4"CND FACP AC-01 D.S. 100A/3/1, W/ 70AF 2EP1-8,10,12 3#4 & 1#10GND- 1"CND CT CABINET METER SPDSPD HYD POWER UNIT D.S. 200A/3/3R, W/ 125AF HINGED TELECOM CABINET TELECOM BACKBOARD WAP CAM-1CAM-2 CAM-3 CAM-4 CAM-5 CAM-6 CAM-7 2EP1-39 SIGN VIA PHOTOCELL #3, SEE EL101 FOR LOCAITON SIGN VIA PHOTOCELL #4, SEE EL101 FOR LOCAITON 2EP1-43 SIGN 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1820 FLightline Road Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 EP101 ELECTRICAL FLOOR PLAN - POWER 2022075.00 11/22/2024 1 1/8" = 1'-0"1 FLOOR PLAN - POWER KEYNOTES 1 HYDRAULIC DOOR: THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR OBTAINING THE LATEST DRAWINGS FOR PURCHASED EQUIPMENT FROM THE HYDRAULIC DOOR PROVIDER. THE ELECTRICAL CONTRACTOR MUST COORDINATE ALL EQUIPMENT VOLTAGES, RECOMMENDED BREAKER RATINGS, MANUFACTURERS RECOMMENDED FUSE SIZES, DOOR CONTROLS, CONDUIT, CABLE AND CONDUCTOR INSTALLATION REQUIREMENTS FOR THIS PROJECT. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING AND INSTALLING ALL EQUIPMENT REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM. NOTIFY THE ARCHITECT / ENGINEER IF PURCHASED EQUIPMENT DIFFERS FROM THE INFORMATION PROVIDED IN THIS DESIGN. 2 CONTRACTOR MUST COORDINATE ALL RECEPTACLE CONFIGURATIONS FOR AIRCRAFT SUPPORT EQUIPMENT WITH OWNER BEFORE ROUGH-IN AND PROCUREMENT OF DEVICES. CONTRACTOR MUST CONTACT ENGINEER FOR DIRECTION IF EQUIPMENT PURCHASED DOES NOT HAVE SAME ELECTRICAL CHARACTERISTICS AS DESIGNED. 0'8'4'8' SCALE : 1/8" = 1'-0" # 1 1. ALL RECEPTACLE OUTLETS LOCATED IN THE BAY AND OFFICE AREAS MUST BE MOUNTED AT 24" ABOVE FINISHED FLOOR TO THE BOTTOM OF THE OUTLET. RECEPTACLE NOTE 2 2 2 2 2 2 2 2 2 1 1 0 11/22/24 ISSUED FOR CONSTRUCITON 1 2025.01.31 GFO HANGAR PERMIT SET 01/31/2025 FIRE ALARM SYSTEM NOTES 1. PROVIDE AN NFPA 72 COMPLIANT FIRE DETECTION AND ALARM SYSTEM. THE SYSTEM SHALL BE A CLASS “B” TWO WIRE ADDRESSABLE TYPE, WITH A 24VDC NOMINAL OPERATING VOLTAGE, SMOKE DETECTORS, DOUBLE ACTION TYPE MANUAL STATIONS, A SOLID STATE, MICROPROCESSOR CONTROLLED FIRE ALARM CONTROL PANEL WITH INTEGRAL LCD ANNUNCIATOR, AND RECHARGING BATTERY SUPPLY. THE SYSTEM SHALL PROVIDE LOCAL ANNUNCIATION VIA ALARM INDICATING APPLIANCES AND REMOTE ANNUNCIATION VIA TELEPHONE LINES OR CELLULAR MODEM. PROVIDE A DEDICATED 120 VAC BRANCH CIRCUIT WITH BREAKER LOCKING MEANS FOR THE FACP. PROVIDE A DUAL LINE UNIVERSAL DIGITAL ALARM COMMUNICATOR (UDACT) AND CONNECT TO TELEPHONE LINES OR CELLULAR MODEM. ALL INDICATING APPLIANCE WIRING SHALL BE #14 AWG MINIMUM. INITIATING DEVICE CIRCUITS SHALL BE SIZED AS REQUIRED BY THE SYSTEM MANUFACTURER. 2. THE CONTRACTOR SHALL FURNISH ALL PARTS, MATERIALS, LABOR, ACCESSORIES, CONNECTIONS, EQUIPMENT, PROGRAMMING, ETC. CUSTOMARILY REQUIRED OR PROVIDED FOR A COMPLETE AND OPERATING CODE-COMPLIANT SYSTEM IN ACCORDANCE WITH ALL APPLICABLE REQUIREMENTS, EVEN IF EACH NEEDED ITEM IS NOT SPECIFICALLY SHOWN OR DESCRIBED ON THE CONTRACT DRAWINGS OR SPECIFICATIONS. ALL SYSTEM COMPONENTS SPECIFIED HEREIN, AS WELL AS THEIR INSTALLATION, SHALL COMPLY WITH APPLICABLE STANDARDS OF THE NATIONAL ELECTRICAL CODE, NATIONAL FIRE PROTECTION ASSOCIATION, AND LOCAL CODES. ALL EQUIPMENT SHALL BE UL LISTED FOR FIRE ALARM SYSTEM USE. 3. THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND SHALL BE INSTALLED AND CONNECTED UNDER THE DIRECTION AND SUPERVISION OF A MANUFACTURER'S REPRESENTATIVE. ALL FIRE ALARM EQUIPMENT AND DEVICES SHALL BE INSTALLED AND TERMINATED BY A NICET LEVEL 2 FIRE ALARM TECHNICIAN. THE MANUFACTURER'S AUTHORIZED REPRESENTATIVE SHALL PROVIDE SUPERVISION OF FINAL SYSTEM CONNECTIONS, MAKE REQUIRED ADJUSTMENTS, PERFORM A COMPLETE FUNCTIONAL TEST OF THE SYSTEM, PROVIDE ALL DOCUMENTATION, TESTING AND CERTIFICATION SERVICES AS REQUIRED BY ALL PERTINENT CODES AND THE AUTHORITY HAVING JURISDICTION (AHJ) AND CERTIFY IN WRITING THAT THE SYSTEM IS PROPERLY INSTALLED AND FUNCTIONS AS SPECIFIED. THE REPRESENTATIVE SHALL ALSO PROVIDE A WRITTEN REPORT ATTESTING TO THE PROPER OPERATION OF THE COMPLETED SYSTEM. 4. ALL CONDUCTORS AND CABLE SHALL BE INSTALLED CONCEALED UNO. ALL WIRING SHALL BE UL LISTED FIRE RATED CABLE AND COLOR CODED TO ALLOW EASE OF IDENTIFICATION OF THE DIFFERENT CIRCUITRY REQUIRED FOR THE SYSTEM. NO CIRCUIT SHALL CHANGE COLOR AT ANY POINT END TO END. 5. ALL WORK SHALL BE IN COMPLIANCE WITH NFPA 70 AND 72 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. ALL EQUIPMENT SUPPLIED SHALL BE LISTED FOR THE PURPOSE FOR WHICH IT IS USED AND INSTALLED IN ACCORDANCE WITH INSTRUCTIONS INCLUDED IN ITS LISTING. IT SHALL ALSO BE NEW, WITH A FULL WARRANTY (PARTS AND LABOR) OF AT LEAST ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE. FURNISH SERVICE AND MAINTENANCE OF THE SYSTEM FOR ONE YEAR FROM DATE OF FINAL ACCEPTANCE. 6. ALL WORK PERFORMED AND ALL MATERIAL FURNISHED UNDER THIS CONTRACT SHALL BE FREE FROM DEFECTS AND SHALL REMAIN SO FOR A PERIOD OF AT LEAST ONE YEAR FROM THE DATE OF ACCEPTANCE. THE CONTRACTOR SHALL PROVIDE A ONE YEAR WARRANTY FOR THE ALARM SYSTEM, ALONG WITH OTHER FORMS OR CERTIFICATE REQUIRED BY THE LOCAL JURISDICTION. 7. EQUIPMENT SHALL CONSIST OF THE FOLLOWING: 7.1 FIRE ALARM CONTROL PANEL WITH BATTERY BACK-UP. BATTERY SUPPLY CAPACITY SHALL PROVIDE FOR 60 HOURS IN STANDBY FOLLOWED BY 15 MINUTES WITH ALL DEVICES IN ALARM. 7.2 MANUAL STATION: MANUAL STATIONS SHALL BE CONSTRUCTED OF HIGH IMPACT, RED LEXAN WITH RAISED LETTERING. MANUAL STATIONS SHALL BE LOCATED NOT MORE THAN FOUR FEET ABOVE THE FINISHED FLOOR TO THE CENTER OF THE BOX. STATIONS SHALL BE LOCATED NOT MORE THEN FIVE FEET FROM EACH DESIGNATED EXIT-WAY AND THE TRAVEL DISTANCE SHALL NOT EXCEED 200 FEET. 7.3 SMOKE DETECTOR: NFPA 72, SOLID STATE ADDRESSABLE PHOTOELECTRIC TYPE WITH TWO WIRE OPERATION AND 360" SMOKE ENTRY. PROVIDE STAND ALONE IONIZATION TYPE WITH HORN AND BATTERY BACKUP FOR EACH UNIT. 7.4 REMOTE LCD ALPHANUMERIC ANNUNCIATOR, FLUSH MOUNTED. 8. SYSTEM OPERATION 8.1 WHEN A FIRE ALARM CONDITION IS DETECTED AND REPORTED BY ONE OF THE SYSTEM INITIATING DEVICES OR APPLIANCES, THE FOLLOWING FUNCTIONS SHALL IMMEDIATELY OCCUR: a. THE SYSTEM ALARM LED SHALL FLASH. b. A LOCAL PIEZO-ELECTRIC SIGNAL IN THE CONTROL PANEL SHALL SOUND. c. THE FACP DISPLAY SHALL INDICATE ALL INFORMATION ASSOCIATED WITH THE FIRE ALARM CONDITION, INCLUDING THE TYPE OF ALARM POINT AND ITS LOCATION WITHIN THE PROTECTED PREMISES. d. ALL SYSTEM OUTPUT PROGRAMS ASSIGNED VIA CONTROL-BY-EVENT EQUATIONS TO BE ACTIVATED BY THE PARTICULAR POINT IN ALARM SHALL BE EXECUTED, AND THE ASSOCIATED SYSTEM OUTPUTS (ALARM NOTIFICATION APPLIANCES AND/OR RELAYS) SHALL BE ACTIVATED. EXACT PROGRAMMING SHALL BE PROVIDED BY THE CONTRACTOR TO MEET THE OWNER'S REQUIREMENTS. e. ACTIVATE ALL FIRE ALARM NOTIFICATION APPLIANCES IN THE BUILDING, SOUNDING CONTINUOUSLY UNTIL THE INITIATING DEVICE AND CONTROL UNIT HAVE BEEN RESET TO NORMAL CONDITION. f. ACTIVATE DIGITAL ALARM COMMUNICATOR. g. DEACTIVATE CONTROL RELAYS TO CAUSE A GLOBAL SHUT DOWN OF ALL HVAC AIR HANDLING UNITS. 8.2 THE DEVICE FROM WHICH THE ALARM ORIGINATED SHALL BE INDICATED AT THE CONTROL PANEL, BOTH AUDIBLY AND VISUALLY, AND AT THE REMOTE ANNUNCIATOR(S). THE INIATING DEVICE LED SHALL PULSE AND SHALL BE ILLUMINATED CONTINUOUSLY AFTER IT HAS BE ACKNOWLEDGED AT THE CONTROL PANEL. 8.3 IN THE EVENT OF A SPRINKLER SYSTEM VALVE CLOSURE THAT ACTIVATES A TAMPER SWITCH, THE SUPERVISORY SIGNALS (BOTH AUDIBLE AND VISUAL) SHALL ACTIVATE AT THE CONTROL PANEL. IT SHALL BE POSSIBLE TO TEMPORARILY SILENCE THE AUDIBLE ALARM BY MEANS OF A SILENCING SWITCH. THE AUDIBLE ALARM SHALL REACTIVATE AUTOMATICALLY ON A PERIODIC BASIS UNTIL THE SYSTEM IS CORRECTED. IT SHALL NOT BE POSSIBLE TO EXTINGUISH THE SUPERVISORY LIGHT UNTIL THE SYSTEM IS CORRECTED. 9. SLEEVE AND SEAL ALL PENETRATIONS THROUGH RATED WALLS AND FLOORS. 10. NOTIFICATION APPLIANCE CIRCUITS SHALL BE A MINIMUM OF NO. 14 AWG UNLESS OTHERWISE NOTED. 11. IN SPACES WHERE MORE THAN TWO VISIBLE NOTIFICATION APPLIANCES ARE IN ANY FIELD OF VIEW, THEY SHALL FLASH IN SYNCHRONIZATION. 12. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR FIRE ALAM MODULES TO SHUTDOWN HVAC EQUIPMENT DURING AN ALARM CONDITION. 13. PROVIDE A 1” MINIMUM RACEWAY FOR A DEDICATED PHONE LINE FOR THE FACP DIALER AND BACKUP LINE FROM EXTERIOR CABINET TO FACP. 14. SHOP DRAWINGS MUST BE SUBMITTED BY THE FIRE ALARM CONTRACTOR COMPLYING WITH THE FIRE ALARM PLAN REVIEW REQUIREMENTS POLICY - JANUARY 2006 BEFORE PERMITTING BY THE WILMINGTON FIRE DEPARTMENT. THESE DRAWINGS DO NOT CONSTITUTE APPROVAL AND MAY CHANGE AFTER A FULL REVIEW BY THE WILMINGTON FIRE DEPARTMENT. A SEPARATE PERMIT MUST BE OBTAINED PRIOR TO INSTALLATION. PIV M M M MM F F F F FF F F M M TB (SYMBOLS SHOWN FOR REFERENCE ONLY AND MAY NOT IMPLY CONTRACTUAL REQUIREMENTS) F M M I C C F F FIRE ALARM LEGEND SYMBOL DESCRIPTION FACP 15cd FIRE ALARM MANUAL STATION, 48" AFF FIRE ALARM HORN/STROBE DEVICE, 80" AFF, "15cd" INDICATES CANDELA RATING SMOKE DETECTOR, CEILING MOUNTED ISOLATION MODULE FIRE ALARM CONTROL PANEL (FACP) FA REMOTE ANN FIRE ALARM REMOTE ANNUNCIATOR PANEL HEAT DETECTOR, CEILING MOUNTED SPRINKLER TAMPER SWITCH SPRINKLER FLOW SWITCH FIRE WATER FLOW ALARM, 80" AFF CONTROL MODULE CONTROL MODULE, WALL MOUNTED MONITOR MODULE MONITOR MODULE, WALL MOUNTED WP TERMINAL BOX NOTE: DETAIL SHOWN FOR REFERENCE ONLY, NOT ALL DEVICES ARE INDICATED ON PLANS. EXIT (3 ' - 6 " M I N I M U M , 4'- 0 " M A X I M U M ) FINISHED FLOOR CL CL NEVER HERE HORN OR SPEAKER SMOKE/ HEAT DETECTOR STROBEHORN / STROBE OR SPEAKER / STROBE CONTROL PANEL SMOKE/ HEAT DETECTOR MANUAL PULL STATION INSTALL PER NATIONAL ELECTRIC CODE STRIKE SIDE HINGE SIDE DOOR 5'-0" MAXIMUM CL 3' - 8 " 5' - 6 " 80 " M I N I M U M BO T T O M O F DE V I C E 96 " M A X I M U M TO P O F D E V I C E CONDUIT AIR SUPPLY DIFFUSER OR RETURN AIR OPENING MOUNT AUDIBLE & VISUAL DEVICES ON APPROVED BOXES 0'-4" MIN 1'- 0 " M A X . 0' - 4 " MI N . 3'-0" MINIMUM 0'-4" MINIMUM MOUNT ON AN APPROVED BOX 0'- 6 " MI N . FIRE ALARM CONTROL PANEL LOCATED INSIDE HE I G H T A S R E Q ' D LENGTH AS REQUIRED RED LAMICORE PLACARD WITH 3/4" WHITE ENGRAVED LETTERS MACHINE SCREW WITH ACORN NUT AND LOCKWASHER, TYP. HVAC SHUTDOWN FIRE ALARM CONTROL PANEL FIRE ALARM REMOTE ANNUNCIATORAPPROVED CELLULAR/ INTERNET COMMUNICATOR INTEGRAL BATTERYPANEL 2EP1-32 NOTE: RISER DIAGRAM IS DEPICTIVE (FUNCTIONAL) ONLY. ALL DEVICES ARE NOT SHOWN FIRST RESPONDERS: PROVIDE MODULES FOR THE FOLLOWING ALARMS: 1.AC FAIL 2. LOW BATTERY 3.CHARGER FAIL 4. BOOSTER FAIL 5.ANTENNA MALFUNCTION 6. SYSTEM COMPONENT FAIL COORDINATE EXACT LOCATIONAND QUANTITIES WITH FIRE PROTECTION PLANS WP INLINE SURGE PROTECTION,TYP FIRST FLOORGRADE BACKFLOW PREVENTER FIRE DOOR SHUTTER FIRST RESPONDERS (SEE NOTES ABOVE) 2 # 12 GND- 3/4" CND ELECTRIC BELL (ON EXTERIOR OF BUILDING) GRADE FIRE DOOR SHUTTER HLV FANS PROVIDE SMOKE DETECTOR AT FACP JUNCTION ABOVE CEILING (PAINTED RED) METALLIC CONDUIT FLEX METALLIC CONDUIT (6" MIN.) STEEL "T-BAR" SUPPORTED EACH END BY CEILING GRID CHANNEL FIXTURE BOX MTS. TO "T-BAR" CEILING GRID CHANNEL CEILING GRID CHANNELSMOKE DETECTOR NOTES: SECURELY MOUNT TRANSIENT ARRESTOR IN ACCESSIBLE JUNCTION BOX OR PROPER METAL ENCLOSURE ADJACENT TO THE PANELBOARD. PROVIDE ENGRAVED LABEL INDICATING ITS LOCATION ARRESTOR TO PANELBOARD NEUTRAL OR GROUND BAR AS INDICATED BY INSTALLATION INSTRUCTIONS TO PANELBOARD CIRCUIT WITH CLIP LOCK 120VAC BRANCH CIRCUIT HOT (BLACK) CONDUCTOR TO FIRE ALARM CONTROL COIL, 5 TO 10, ABOUT 1" DIAMETER, TIE WRAPPED FIRE ALARM SYSTEM CONTROL MATRIX SYSTEM OUTPUTS SYSTEM INPUTS NOTE ACTUATE COMMON ALARM SIGNAL INDICATOR ACTUATE NOTIFICATION APPLIANCES (NOTE 6) ACTUATE SLEEPING ROOM SOUNDER BASE ONLY ACTUATE EXTERIOR ELECTRIC BELL ACTUATE COMMON TROUBLE SIGNAL INDICATOR ACTUATE COMMON SUPERVISORY SIGNAL INDICATOR ALARM SIGNAL TO MONITORING SERVICE SUPERVISORY SIGNAL TO MONITORING SERVICE TROUBLE SIGNAL TO MONITORING SERVICE DISPLAY/PRINT CHANGE OF STATUS RECALL ELEVATOR TO PRIMARY RECALL FLOOR RECALL ELEVATOR TO ALTERNATE RECALL FLOOR ACTIVATE FIRE HAT SIGNAL SHUNT TRIP ELEVATOR CONTROLLER FEEDER CIRCUIT BREAKER START FIRE PUMP SHUTDOWN HLV FAN RECORD EVENTS IN SYSTEM MEMORY SIGNAL HVAC CONTROL SYSTEM A B C D E F G H I J K L M N O P Q R 1 INITIATING DEVICES 2 SMOKE DETECTORS X X X X X 3 MANUAL PULL STATIONS X X X X X 4 TROUBLE INPUTS 5 SYSTEM TROUBLE CONDITION X X X 6 LOSS OF FACU AC POWER 1 X X X 7 FACP LOW BATTERY X X X 8 SHORT CIRCUIT X X X 9 NAC POWER SUPPLY LOW BATTERY X X X 10 GROUND FAULT X X X 11 OPEN CIRCUIT X X X 12 AHU SHUTDOWN X X X 13 FIRE SUPPRESSION SYSTEM 14 SPRINKLER SYSTEM FLOW SWITCH 2 X X X X X X X 15 SPRINKLER SYSTEM TAMPER SWITCH 2 X X X 16 SPRINKLER PRESSURE SWITCH 2,3 X X X 17 POST INDICATOR VALVE TAMPER SWITCH 2 X X X 18 RPZ TAMPER SWITCHES 2 X X X 19 FIRST RESPONDERS CABINET 20 AC FAIL X X X 21 CHARGER FAIL X X X 22 ANTENNA MALFUNCTION X X X 23 LOW BATTERY X X X 24 BOOSTER FAIL X X X 25 SYSTEM COMPONENT FAIL X X X NOTES: 1 ONLY AFTER LOSS OF POWER FOR > 3 HOURS. 2. 3. TYPICAL, QUANTITIES OF DEVICES ARE NOT SHOWN, REFER TO FIRE PROTECTION SYSTEM RECORD DRAWINGS FOR QUANTITIES AND LOCATIONS. IF INSTALLED. ACTIVATE FIRE DOOR SHUTTER S X X X LEVEL WITH BOTTOM OF SUSPENDED LIGHT EMT CONDUIT, HORN/STROBE EMT CONDUIT CEILING SURFACE MOUNTED JUNCTION BOX 023311 LA W . RCNLE I BB I L SES RCAO I L A SEAL N A OFON EE RNIGN R T PON R H E SHEET NUMBER SHEET TITLE PROJECT NUMBER DATE REVISIONS GFO Hangar COPYRIGHT © 2024 THE WILSON GROUP ARCHITECTS ALL RIGHTS RESERVED • PRINTED OR ELECTRONIC DRAWINGS AND DOCUMENTATION MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION FROM THE WILSON GROUP ARCHITECTS WK DICKSON CIVIL ENGINEER THE WILSON GROUP PO BOX 5510 CHARLOTTE, NC 28299 (704) 331-9747 www.twgarchitects.com NC Cert. No.: 51140 - A R C H I T E C T S - Wilmington International Airport 1820 FLightline Road Wilmington, NC 28405 AN ARDURRA COMPANY 300 N. Third Street, Suite 301 Wilmington. NC 28401 WOODS ENGINEERING, PA STRUCTURAL ENGINEER 254 N. Front St., Suite 201 Wilmington. NC 28401 CBHF ENGINEERS, PLLC MECHANICAL, ELECTRICAL AND PLUMBING ENGINEER 2246 Yaupon Drive Wilmington. NC 28401 ENGINEERING CONSULTING SERVICES (ECS) GEOTECHNICAL ENGINEER 6714 Netherlands Drive Wilmington. NC 28405 MONTEITH CONSTRUCTION GENERAL CONTRACTOR 208 Princess Street Wilmington. NC 28401 F-001 FIRE ALARM LEGEND, NOTES, RISER AND DETAILS 2022075.00 11/22/2024 NO SCALE1FIRE ALARM RISER NO SCALE2FIRE ALARM DEVICES MOUNTING HEIGHTS NO SCALE3FA PLACARD DETAIL NOT TO SCALE4 TYPICAL CEILING MOUNTED DETECTOR MOUNTING DETAIL NO SCALE5TRANSIENT ARRESTOR INSTALLATION DETAIL NO SCALE7TYPICAL SYSPENDED DEVICE DETAIL 1 1 0 11/22/24 ISSUED FOR CONSTRUCITON 1 2025.01.31 GFO HANGAR PERMIT SET 01/31/2025 Transmittal 2246 Yaupon Drive, Wilmington, NC 28401 Page 1 of 2 PROJECT:Ardent ILM Hangar 24140 DATE:1/31/2025 SUBJECT:GFO Hangar Permit Set PME&F TRANSMITTAL ID:00010 PURPOSE:For your review and comment VIA:Info Exchange FROM NAME COMPANY EMAIL PHONE Greg Herring 2246 Yaupon Drive Wilmington NC 28401 United States CBHF Engineers gherring@cbhfengineers.com 910-791-4000 TO NAME COMPANY EMAIL PHONE Colleen Coons United States ccoons@monteithco.com 910-791-8101 Frank D'Andrea Monteith Construction Corp.FDAndrea@monteithco.com 910.899.7473 REMARKS:Colleen, Here is the link to download the GFO Hangar Permit Set of PME&F drawings. Electrical and FA Combined drawings have been updated with the revised drawings. Individual drawings of the revised Electrical and FA drawings are attached. Mechanical and Plumbing drawings do not have any revised drawings, the Issue for Construction Drawings dated 11/22/24 are attached. Greg Herring Senior Electrical Designer CBHF Engineers, PLLC 2246 Yaupon Drive Wilmington, NC 28401 (910) 791-4000x127 gherring@cbhfengineers.com www.cbhfengineers.com Confidentiality Note: This e-mail may contain information which is privileged and confidential. If you are not the intended recipient, you are hereby notified that any copying of or disclosure of this e-mail or its message is strictly prohibited. If you have received this in error, please call 910-791-4000, ext. 100. Thank you. Transmittal DATE:1/31/2025 TRANSMITTAL ID:00010 Page 2 of 2 DESCRIPTION OF CONTENTS QTY DATED TITLE NOTES 1 1/31/2025 24140 Electrical Combined.pdf 1 1/31/2025 24140 Fire Alarm Combined.pdf 1 11/27/2024 24140 Mechanical Combined.pdf 1 11/26/2024 24140 Plumbing Combined.pdf 1 1/31/2025 E-100 - ELECTRICAL SITE PLAN.pdf 1 1/31/2025 E-601 - ELECTRICAL RISER DIAGRAM AND SCHEDULES.pdf 1 1/31/2025 EL101 - ELECTRICAL FLOOR PLAN - LIGHTING.pdf 1 1/31/2025 EP101 - ELECTRICAL FLOOR PLAN - POWER.pdf 1 1/31/2025 F-001 - FIRE ALARM LEGEND, NOTES, RISER AND DETAILS.pdf COPIES: Allen Cribb (CBHF Engineers) Brent Stanley (CBHF Engineers) David Hahn (CBHF Engineers) John Barker