Loading...
HomeMy WebLinkAboutWater Model ResultsScenario: ADD + FIRE J-6 J-8 FIRE SERVICE J-9 J-10 J-4 J-11 J-7 J-2 J-3 J-1 J-5 PMP-1 R-1 H-2 EX-H-1 EX-H-2 H-1 WATER MODEL.wtg Bentley Systems, Inc. Haestad Methods Solution Center WaterCAD [24.00.00.26] 2/11/2025 76 Watertown Road, Suite 2D Thomaston, CT 06787 USA +1-203-755- 1666 Page 1 of 1 WATER NETWORK MAP EXIST I N G 8 " M A I N - H A L L D R I V E - S R 1 3 8 6 EX I S T I N G 8 " M A I N PROPOSED BUILDING 2-IN WATER MAIN 6-IN WATER MAIN 8-IN WATER MAIN FlexTable: Junction Table ID Label Elevation (ft) Pressure (psi) Fire Flow (Available) (gpm) Pressure (Calculated Residual @ Total Flow Needed) (psi) Fire Flow (Needed) (gpm) 65 FIRE SERVICE 26.90 71 1,609 41 1,200 82 J-1 26.00 71 3,142 63 1,200 86 J-2 25.31 72 2,228 55 1,200 72 J-3 26.60 71 2,121 53 1,200 107 J-4 26.55 71 2,114 53 1,200 68 J-5 25.50 72 1,973 51 1,200 67 J-6 24.60 72 1,931 50 1,200 110 J-7 0.00 83 293 -765 1,200 112 J-8 0.00 83 212 -1,450 1,200 64 J-9 26.90 71 1,636 42 1,200 96 J-10 25.72 72 1,587 41 1,200 93 J-11 25.50 72 1,406 33 1,200 WATER MODEL.wtg Bentley Systems, Inc. Haestad Methods Solution Center WaterCAD [24.00.00.26] 2/11/2025 76 Watertown Road, Suite 2D Thomaston, CT 06787 USA +1-203-755-1666 Page 1 of 1 JUNCTION TABLE - ADF + FIRE FLOW 2-IN LINE 2-IN LINE FlexTable: Hydrant Table Label Pressure (psi) Fire Flow (Available) (gpm) Fire Flow (Needed) (gpm) Pressure (Calculated Residual @ Total Flow Needed) (psi) EX-H-1 70 2,991 1,000 64 EX-H-2 70 1,876 1,000 55 H-2 70 1,371 1,000 42 H-1 70 1,548 1,000 48 WATER MODEL.wtg Bentley Systems, Inc. Haestad Methods Solution Center WaterCAD [24.00.00.26] 2/11/2025 76 Watertown Road, Suite 2D Thomaston, CT 06787 USA +1-203-755-1666 Page 1 of 1 HYDRANT TABLE - ADF + FIRE FLOW